[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-002","fire-106-1-alarm-evacuation-002",106,1,2,"對於消防安全設備緊急供電系統之配線之規定，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"電氣配線應設專用回路，必要時得與一般電路相接","緊急用電源回路及操作回路，使用 600 伏特耐熱絕緣電線，或同等耐熱效果以上之電線","電源回路之配線裝於金屬導線管槽內，並埋設於厚度為 25 毫米以上之混凝土內","電源回路採耐熱電纜，並按電纜裝設法敷設","B",null,[],false,"本題考點：緊急供電系統配線的四項法定要求，考的是專用回路、電線耐熱等級、埋設厚度與電纜種類的正確搭配。\n【正解理由】依《各類場所消防安全設備設置標準》第 235 條，緊急供電系統之配線除依用戶用電設備裝置規則外，緊急用電源回路及操作回路應使用 600 伏特耐熱絕緣電線，或具同等耐熱效果以上之電線，選項用語與條文一致，故選 B。\n【逐項排除】\n(A) 錯在「必要時得與一般電路相接」。條文明定電氣配線應設專用回路且不得與一般電路相接，避免一般電路短路跳脫時連帶使消防設備失效。\n(B) 正確。電源回路與操作回路的耐熱要求即為 600 伏特耐熱絕緣電線或同等以上，此為條文原文。\n(C) 錯在厚度。條文所定為裝於金屬導線管槽內並埋設於防火構造物之混凝土內，厚度 20 毫米以上，非 25 毫米。\n(D) 錯在電纜種類。電源回路採用的是耐燃電纜並依電纜裝設法敷設；耐熱電纜適用範圍為操作回路等，耐燃與耐熱等級不可互換。\n【記憶點】緊急配線「專用不共線、六百伏耐熱、混凝土埋二十毫米、電源用耐燃」。","緊急供電系統配線的規範核心只有一句話：火災延燒到配線時，消防設備必須還活著。因此條文從三個面向設防。第一是回路獨立性——專用回路且不得與一般電路相接，避免非消防負載的故障或跳脫波及；受信總機、緊急廣播、加壓送水裝置的控制電源都適用。第二是材料耐火等級——耐燃電纜（FR）要求在高溫火焰下仍能維持通電一定時間，等級高於耐熱電線（HR），故條文把電源回路交給耐燃電纜，操作回路等次要回路才允許耐熱等級，選項 D 正是把兩者對調的典型誘答。第三是物理保護——裝於金屬導線管槽並埋設於防火構造物混凝土內 20 毫米以上，等於用結構體本身當隔熱層，這個 20 毫米是純記憶數字，常被改成 15 或 25 出題。\n耐燃與耐熱的分辨口訣：「燃比熱高，電源用燃」。實務標示上耐燃電纜多為橘紅色外被並標示 FR，耐熱電線標示 HR，兩者的耐火試驗溫度與持續時間不同，不可互相替代或混用於同一回路等級要求。\n這條文與緊急電源本身的規定要串起來看：緊急電源分發電機設備、蓄電池設備與燃料電池設備，容量須能使各設備有效動作規定時間（例如火警自動警報設備 10 分鐘、緊急廣播設備 10 分鐘、加壓送水裝置依設備別 20 至 30 分鐘）。配線只是把電送過去，電源容量不足一樣白搭，兩者是同一題組的常客。\n記憶整理：專用回路不得與一般電路相接（回路面）、600 伏特耐熱絕緣電線或同等以上（材料面）、金屬導線管槽並埋設防火構造物混凝土內 20 毫米以上（保護面）、電源回路採耐燃電纜依電纜裝設法敷設（等級面）。四個面向各對應一個選項，命題者通常只動其中一項的數字或名詞，逐項比對條文用語即可快速判定。\n※ 條號請以現行法規為準，條文內容曾配合用戶用電設備裝置規則的修正調整用語，作答仍以該年度條文之要件為準。",true,[28,31,35,40,43,47],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-106-1-alarm-evacuation-001","某一 KTV 視聽歌唱場所設於大樓地下層，依規定樓地板面積如合計超過多少，應設置瓦斯漏氣火警自動警報設備？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-106-1-alarm-evacuation-003","裝設緊急廣播設備之建築物之規定，下列何者錯誤？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-114-1-alarm-evacuation-004","某電影院放映場所火警自動警報設備所使用之蓄積型偵煙探測器有 10 秒之蓄積時間，其所使用之中繼器有 10 秒之蓄積時間，則其受信總機之蓄積時間，最多可為多少秒？",4,114,{"webId":41,"stem":42,"number":38,"year":11,"session":12},"fire-106-1-alarm-evacuation-004","依各類場所消防安全設備檢修及申報作業基準規定，1 種光電式局限型偵煙探測器於使用加煙試驗器確認動作之時間，加煙後至動作應在多少時間內方為合格？",{"webId":44,"stem":45,"number":38,"year":46,"session":12},"fire-112-1-alarm-evacuation-004","依據一一九火災通報裝置檢修基準之性能檢查，下列何者非預備電源檢查方法之項目？",112,{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-106-1-alarm-evacuation-005","依各類場所消防安全設備設置標準規定，下列何種場所如設置高感度密閉式撒水頭自動撒水設備，得免設火警自動警報設備？",5,[52,56,60,64],{"webId":53,"year":54,"stem":55,"number":13},"fire-110-1-alarm-evacuation-002",110,"某樓高 12 層觀光旅館於最高樓層開設之餐廳，依各類場所消防安全設備設置標準之規定，其位於同樓層的廚房無須設置下列何種裝置？",{"webId":57,"year":58,"stem":59,"number":13},"fire-109-1-alarm-evacuation-002",109,"使用「加瓦斯試驗器」進行瓦斯漏氣檢知器性能檢查時，若檢測對象的瓦斯對空氣之比重大於 1 者，應使用何種氣體來檢測？",{"webId":61,"year":62,"stem":63,"number":13},"fire-108-1-alarm-evacuation-002",108,"特別安全梯的安全梯與緊急昇降機兼用時，其排煙機、進風機之排煙量、進風量須在每秒多少立方公尺以上？",{"webId":65,"year":66,"stem":67,"number":13},"fire-107-1-alarm-evacuation-002",107,"差動式分布型探測器為熱半導體式時，裝接於一個檢出器之感熱器數量，下列何者正確？",1785123172609]