[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-004","fire-106-1-alarm-evacuation-004",106,1,4,"依各類場所消防安全設備檢修及申報作業基準規定，1 種光電式局限型偵煙探測器於使用加煙試驗器確認動作之時間，加煙後至動作應在多少時間內方為合格？",{"A":16,"B":17,"C":18,"D":19},"30 秒","45 秒","60 秒","90 秒","A",null,[],false,"本題考點：《各類場所消防安全設備檢修及申報作業基準》對偵煙探測器加煙試驗的動作時間判定,考的是一種、二種、三種各自的合格秒數。\n【正解理由】依《各類場所消防安全設備檢修及申報作業基準》有關火警自動警報設備之性能檢查規定,光電式局限型偵煙探測器以加煙試驗器施加煙霧後,其動作時間依感度種別判定:一種應在三十秒內動作、二種應在六十秒內動作、三種應在九十秒內動作,逾時即判定不合格。題目問一種,故選 A。\n【逐項排除】\n(A) 正確。三十秒為一種偵煙探測器的合格上限,一種感度最高、應最早響應。\n(B) 四十五秒並非本項判定所採用的級距,基準中的秒數以三十、六十、九十三段呈現,四十五秒屬誘答數值。\n(C) 六十秒是二種偵煙探測器的判定值,套用於一種會放寬標準,使感度不足的探測器誤判為合格。\n(D) 九十秒是三種偵煙探測器的判定值,標準最寬,與一種的要求相差三倍。\n【記憶點】偵煙加煙試驗:一種三十秒、二種六十秒、三種九十秒,種別愈大愈慢。","這組秒數的設計邏輯,來自探測器「感度種別」與「有效探測面積」的對應關係。感度愈高者(一種),對低濃度煙即能反應,因此在同樣的加煙條件下應最快動作,設置時可分配到較大的有效探測面積;感度較低者(二種、三種)反應較慢,面積相對縮小,並在裝置高度上受更嚴格的限制。檢修基準把現場判定簡化成一支加煙試驗器與一只碼錶,即是把出廠時的感度規格,轉換成可在竣工後逐年重複驗證的現場指標——探測器長期暴露於灰塵、油煙與濕氣,受光部或發光部積污會使感度衰減,動作時間拉長正是劣化的早期徵兆。\n概念上要分清三組容易混淆的名詞。第一,偵煙式與定溫式、差動式屬不同偵測原理,前者偵測煙霧粒子對光的散射或遮蔽,後兩者偵測溫度絕對值或上升率,檢修方法也不同(熱式用加熱試驗器,判定值另有規定)。第二,光電式「局限型」偵測的是本體周圍一點的煙濃度,「分離型」則以送光部與受光部間的光軸遮蔽率判定,適用於挑高空間與大空間,兩者的檢修方式並不相同。第三,「一種、二種」在偵煙探測器指感度,在其他設備條文中可能指構造種別,不可跨設備硬套。\n相關考點延伸包括:偵煙探測器不得設於廚房、浴室等平時有蒸氣或油煙之處所以免誤報;設於走廊、通道時的步行距離規定;設於樓梯、斜坡通道時的垂直距離規定;以及裝置面高度超過一定值時可用的探測器種類限制。記憶上把「三十、六十、九十」與「一、二、三種」對齊成等差數列,再補一句「感度愈好、秒數愈短」即可穩定作答。",true,[28,32,36,40,44,47],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-003","裝設緊急廣播設備之建築物之規定，下列何者錯誤？",3,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-005","依各類場所消防安全設備設置標準規定，下列何種場所如設置高感度密閉式撒水頭自動撒水設備，得免設火警自動警報設備？",5,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-002","對於消防安全設備緊急供電系統之配線之規定，下列何者正確？",2,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-006","樓梯、斜坡通道、昇降機之昇降路及管道間等場所，其頂層相差在二層以下、水平距離多少範圍內，視為一火警分區？",6,{"webId":45,"stem":46,"number":12,"year":11,"session":12},"fire-106-1-alarm-evacuation-001","某一 KTV 視聽歌唱場所設於大樓地下層，依規定樓地板面積如合計超過多少，應設置瓦斯漏氣火警自動警報設備？",{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-106-1-alarm-evacuation-007","如設置救助袋做為避難器具，下列敘述何者錯誤？",7,[52,56,60,64,68],{"webId":53,"year":54,"stem":55,"number":13},"fire-114-1-alarm-evacuation-004",114,"某電影院放映場所火警自動警報設備所使用之蓄積型偵煙探測器有 10 秒之蓄積時間，其所使用之中繼器有 10 秒之蓄積時間，則其受信總機之蓄積時間，最多可為多少秒？",{"webId":57,"year":58,"stem":59,"number":13},"fire-112-1-alarm-evacuation-004",112,"依據一一九火災通報裝置檢修基準之性能檢查，下列何者非預備電源檢查方法之項目？",{"webId":61,"year":62,"stem":63,"number":13},"fire-110-1-alarm-evacuation-004",110,"有一棟總樓地板面積 4,000 平方公尺的七層辦公建築物，當起火層為地上第二層時，下列有關其火警自動警報設備分區鳴動方式的敘述，何者正確？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-alarm-evacuation-004",109,"某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-alarm-evacuation-004",108,"某一防火構造建築物，地上 5 層且為無開口樓層，1 至 2 層供辦公室用途使用，3 至 5 層供餐廳用途使用，各樓層樓地板面積皆為 200 平方公尺，依照各類場所消防安全設備設置標準之規定，請問本場所火警自動警報設備之設置情形，下列何者正確？",1785123172626]