[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-006":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-006","fire-106-1-alarm-evacuation-006",106,1,6,"樓梯、斜坡通道、昇降機之昇降路及管道間等場所，其頂層相差在二層以下、水平距離多少範圍內，視為一火警分區？",{"A":16,"B":17,"C":18,"D":19},"25 公尺","40 公尺","50 公尺","60 公尺","C",null,[],false,"本題考點：火警分區劃定中「垂直豎穴」的特別規定，考的是《各類場所消防安全設備設置標準》第 113 條但書所定的水平距離門檻。\n【正解理由】依《各類場所消防安全設備設置標準》第 113 條，垂直貫通的豎穴類空間——包括樓梯與斜坡通道、昇降機昇降路、以及各式管道間——只要彼此頂層高度差在二層以內，且相互之水平距離不超過五十公尺，即得合併視為一個火警分區；問的正是這個距離上限，數值為五十公尺，故選 C。\n【逐項排除】\n(A) 25 公尺：此數值屬火警分區一般規定中「一邊長」的概念範疇（一分區邊長在五十公尺以下、面積六百平方公尺以下），並非豎穴合併的水平距離門檻，數值明顯偏小。\n(B) 40 公尺：法條並無四十公尺此一門檻，屬憑印象湊數的干擾項，記憶時容易與探測器警戒範圍距離混淆。\n(C) 50 公尺：與條文所定「水平距離在五十公尺以下」完全相符，且與火警分區邊長五十公尺的數值互相呼應，為正解。\n(D) 60 公尺：六十公尺在本條並無對應規定，考生常誤把面積六百平方公尺的「六」誤植為距離六十公尺而落入陷阱。\n【記憶點】豎穴合併看兩件事：頂層相差二層以下、水平距離五十公尺以下，兩者同時成立才算一個火警分區。","火警分區的立法設計目的，是讓受信總機能把警報訊號對應到一個「人員可在合理時間內走到並確認火點」的空間單元。《各類場所消防安全設備設置標準》第 112 條先定下一般原則：每一火警分區不得超過一樓層，面積在六百平方公尺以下，任一邊長在五十公尺以下；第 113 條再處理垂直貫通空間這種例外。\n\n樓梯、斜坡通道、昇降機之昇降路、管道間屬於典型的豎穴空間，煙流在其中以浮力驅動快速上升，若照樓層逐一劃分火警分區，會出現一支樓梯被切成十幾個分區、警報訊號零碎難以判讀的情形。因此條文允許把「垂直方向連續、且彼此靠近」的豎穴合併為一個火警分區，判定要件有兩個：頂層高度相差在二層以下，以及彼此水平距離在五十公尺以下。兩個條件是併存關係，缺一即須分別劃分。\n\n數值記憶對照可整理如下：一般分區面積六百平方公尺以下、邊長五十公尺以下；設有光電式分離型探測器時邊長可放寬至一百公尺；主要出入口可直接觀察樓地板面時面積可放寬至一千平方公尺；豎穴合併的水平距離五十公尺以下、頂層相差二層以下。可用「六百／五十」為基準數，豎穴借用同一個五十。\n\n易混淆概念是「火警分區」與「防護區劃」：前者是警報訊號的辨識單元，屬火警自動警報設備的設計概念；後者是滅火藥劑或煙控的密閉範圍，兩者範圍常不一致，不可互相套用。同一條文的另一常見考法，是問「地下層與地上層可否合併為同一分區」，答案為不得合併，因兩者避難方向相反、煙流行為亦不同。另一個延伸考點是豎穴在垂直方向的分區高度限制：地下層與地上層之豎穴部分應分別劃定，且垂直距離每達一定高度即須另設一分區，避免單一分區涵蓋過長的垂直範圍而失去定位意義。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-005","依各類場所消防安全設備設置標準規定，下列何種場所如設置高感度密閉式撒水頭自動撒水設備，得免設火警自動警報設備？",5,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-007","如設置救助袋做為避難器具，下列敘述何者錯誤？",7,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-004","依各類場所消防安全設備檢修及申報作業基準規定，1 種光電式局限型偵煙探測器於使用加煙試驗器確認動作之時間，加煙後至動作應在多少時間內方為合格？",4,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-008","天花板設排氣口或回風口時，偵煙式探測器應裝置於排氣口或回風口周圍多少距離範圍內？",8,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-003","裝設緊急廣播設備之建築物之規定，下列何者錯誤？",3,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-009","差動式分布型探測器為熱電偶式時，熱電偶應裝置在裝置面下方多少公分範圍內？",9,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-006",110,"緊急廣播設備在樓梯或斜坡通道以外之場所，其設置之揚聲器採性能設計時，在揚聲器標示上如加註下列那二種項目者，該廣播區域內任一點至揚聲器之水平距離方可不受到 10 公尺以下的限制？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-006",109,"差動式局限型探測器進行性能檢查時，使用加熱式試驗器加熱確認動作時間，加熱後到探測器動作應在多少時間以內？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-006",108,"探測器應依裝置場所高度選擇探測器種類裝設，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-alarm-evacuation-006",107,"下列何種使用瓦斯之場所，應設置瓦斯漏氣火警自動警報設備？",1785123172648]