[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-009","fire-106-1-alarm-evacuation-009",106,1,9,"差動式分布型探測器為熱電偶式時，熱電偶應裝置在裝置面下方多少公分範圍內？",{"A":16,"B":17,"C":18,"D":19},"30 公分","40 公分","45 公分","50 公分","A",null,[],false,"本題考點：差動式分布型探測器中熱電偶式之裝置位置，屬《各類場所消防安全設備設置標準》第 116 條所定的裝置面下方距離。\n【正解理由】依《各類場所消防安全設備設置標準》第 116 條，分布型的差動式探測器若採熱電偶感測方式，其感測元件須落在裝置面下方三十公分的範圍以內；此一限制是為了讓接點停留在火災初期天花板噴流的有效厚度內，才能及時感應溫升，故選 A。\n【逐項排除】\n(A) 30 公分：與條文所定「裝置面下方三十公分範圍內」相符，且與同標準第 115 條探測器一般裝置於天花板下方三十公分範圍內的原則一致，為正解。\n(B) 40 公分：法無此數值，屬單純加大干擾項；若真裝到四十公分，熱電偶可能落在頂端熱氣流層之外而延遲動作。\n(C) 45 公分：四十五公分在探測器規定中並無對應條文，考生常與其他設備的斜角或間距數值混記而誤選。\n(D) 50 公分：五十公分為差動式分布型「空氣管式」中，空氣管距樓板或牆壁面之相關限制易混淆的數值範疇，並非熱電偶式的裝置面下方距離。\n【記憶點】熱電偶式與一般探測器同尺規，都是「裝置面下方三十公分內」。","差動式分布型探測器以「一定範圍內的平均溫升速率」動作，與差動式局限型只感測一點的方式不同，適用於大空間、天花板較高或有階梯狀天花板的場所。其型式主要有三種：空氣管式、熱電偶式與熱半導體式。空氣管式靠管內空氣受熱膨脹推動膜片接點；熱電偶式利用兩種不同金屬接合點受熱產生熱電動勢（席貝克效應，Seebeck effect），當熱起電力達設定值即動作；熱半導體式則以熱敏電阻的阻值變化偵測。\n\n《各類場所消防安全設備設置標準》第 116 條把三種型式的裝置細節分款規定。空氣管式部分包括：露出部分在每一火警分區應在二十公尺以上、裝接於一個檢出器的空氣管長度在一百公尺以下、空氣管裝置在裝置面下方三十公分範圍內、自裝置面任一邊起一點五公尺以內、相對兩邊之間隔在九公尺（主要構造為防火構造者）或六公尺以下。熱電偶式的重點則是熱電偶應裝置在裝置面下方三十公分範圍內，以及每一火警分區之熱電偶數量下限與接於一個檢出器之數量上限。\n\n記憶策略是抓住「三十公分」這個共通尺規：不論偵煙式、差動式局限型、差動式分布型空氣管式或熱電偶式，感測元件基本都要落在裝置面下方三十公分之內，因為火災初期天花板噴流（ceiling jet）的有效厚度大致就在這個量級，超出即進入溫度快速衰減的區域。真正需要分別記憶的，反而是各型式的長度、間隔與數量限制。\n\n易混淆概念對照：差動式是「溫升速率」動作，適合溫度平時穩定的場所；定溫式是「達到設定溫度」動作，適合廚房、鍋爐房等平時即有溫度變化之處；補償式則兼具兩者特性。把動作原理與適用場所綁在一起記，遇到情境題就不會選錯型式。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-008","天花板設排氣口或回風口時，偵煙式探測器應裝置於排氣口或回風口周圍多少距離範圍內？",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-010","緩降機設置周圍為避免有操作障礙，因此限制必要操作面積為 M 平方公尺以上（不含避難器具所占面積），但邊長應為 N 公分以上。下列何者正確？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-007","如設置救助袋做為避難器具，下列敘述何者錯誤？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-011","Ｐ型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，不得超過 X 個。受信總機之探測器回路電阻，應在 Y 以下。下列何者正確？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-006","樓梯、斜坡通道、昇降機之昇降路及管道間等場所，其頂層相差在二層以下、水平距離多少範圍內，視為一火警分區？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-012","依據緊急照明燈認可基準進行充電試驗時，蓄電池電壓降達額定電壓多少以內時，需能自動充電？",12,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-009",110,"瓦斯漏氣火警自動警報設備之性能試驗中，下列有關串接配線試驗之測試及判定，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-009",109,"有關避難方向指示燈裝設之敘述，下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-009",108,"緩降機固定架或支固器具使用錨定螺栓固定時，選用螺紋標稱為 M12×1.75 之螺栓，試問其螺栓埋入混凝土內不含灰漿部分之深度（mm）及轉矩值須為多少（kgf-cm）？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-alarm-evacuation-009",107,"以下有關各類場所消防安全設備設置標準對火警分區的規定，何者錯誤？",1785123172678]