[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-013":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-013","fire-106-1-alarm-evacuation-013",106,1,13,"集合住宅計算收容人數以設置避難器具時，每戶收容人數以多少人計算？",{"A":16,"B":17,"C":18,"D":19},"2人","3人","4人","5人","B",null,[],false,"本題考點：避難器具設置基準所依據的收容人數計算方式，考的是集合住宅每戶折算人數，屬《各類場所消防安全設備設置標準》第 157 條規定。\n【正解理由】依《各類場所消防安全設備設置標準》第 157 條收容人數計算方法，集合住宅之收容人數以「其戶數乘以三」計算，即每戶以三人計；本題所問即為該折算基數，故選 B。\n【逐項排除】\n(A) 2人：每戶二人低於法定折算基數，將低估收容人數而導致避難器具設置數量不足，非條文所採。\n(B) 3人：與第 157 條附表「集合住宅：以其戶數乘三計算」之規定相符，係以戶為單位乘固定係數的折算方式，為正解。\n(C) 4人：四人係其他用途場所（如以床位或面積折算者）可能出現的數值，並非集合住宅的戶數乘數。\n(D) 5人：每戶五人高估收容人數，法條亦無此規定，屬單純加大的干擾項，且與住宅平均戶量的統計基礎不符。\n【記憶點】集合住宅收容人數＝戶數乘三，算出人數後再依第 160 條推算避難器具應設具數，兩段一氣呵成。","收容人數是避難器具設置與否、設置幾具的計算起點，也是決定部分場所是否需設火警自動警報設備、標示設備的門檻參數，因此《各類場所消防安全設備設置標準》第 157 條用一整條附表逐類場所訂定計算方法。其邏輯是把「難以逐一清點的實際人數」換算為可稽核的客觀量，計算基礎大致分四類：以從業員人數計、以座椅或床位數計、以樓地板面積除以每人所占面積計、以固定單元數乘固定係數計。集合住宅屬第四類，以戶數乘以三計算。\n\n之所以採「每戶三人」，是取自住宅平均戶量的統計概念，並在安全裕度與合理性之間折衷：若以實際登記人口計算，會隨住戶異動而浮動、難以在建築審查階段確定；若以面積折算，又會使大坪數住宅得出不合理的高人數。以戶為單位乘固定係數，既穩定又易於稽核。\n\n收容人數算出後，接續適用第 160 條有關避難器具設置數量的規定：以場所類別對應的每一定收容人數設置一具，超過部分依比例增設。例如某些用途場所以每一百人設一具、每二百人設一具不等，考題常把「收容人數計算」與「器具具數計算」串成兩段式計算題，第一段錯就全錯，因此第 157 條的折算係數必須記牢。\n\n常考折算基數可整理成對照表：集合住宅為戶數乘三；供從業員使用者以從業員人數計；有觀眾席者以固定席位數計，長椅式則以正面寬度除以零點四公尺所得整數計；遊藝場所、飲食店等以樓地板面積除以三平方公尺；旅館、飯店則以客房內床位數加上其他部分面積折算後合計。\n\n易混淆概念是「收容人數」與「使用人員數」：前者為法定折算值，用於設備設置判斷；後者為實際在場人數，屬防火管理與避難計畫的範疇，兩者不可互換使用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-012","依據緊急照明燈認可基準進行充電試驗時，蓄電池電壓降達額定電壓多少以內時，需能自動充電？",12,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-014","依各類場所消防安全設備檢修及申報作業基準規定，火警自動警報設備之受信總機前應確保多少公尺以上空間以進行檢查及操作使用？",14,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-011","Ｐ型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，不得超過 X 個。受信總機之探測器回路電阻，應在 Y 以下。下列何者正確？",11,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-015","依緩降機認可基準規定，緩降機之最大使用載重，應在最大使用人數乘以 W 所得數值以上。下述 W 值何者正確？",15,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-010","緩降機設置周圍為避免有操作障礙，因此限制必要操作面積為 M 平方公尺以上（不含避難器具所占面積），但邊長應為 N 公分以上。下列何者正確？",10,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-016","瓦斯漏氣火警自動警報設備裝置於瓦斯對空氣之比重未滿一之建築物室內時，檢知器設置位置應距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離多少以內？",16,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-013",110,"容易受風影響之場所（如大廳、禮拜堂、大樓頂上之機械室等），依消防安全設備及必要檢修項目檢修基準之規定，可在下列何種探測器中進行選設？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-013",109,"無線電通信輔助設備設置之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-013",108,"有關避難器具之外觀試驗，下列何者不屬於外觀試驗？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-alarm-evacuation-013",107,"依各類場所消防安全設備設置標準規定，火警自動警報設備之配線，除依屋內線路裝置規則外，其電源回路導線間及導線與大地間之絕緣電阻值，以直流 250 伏特額定之絕緣電阻計測定，對地電壓在 150 伏特以下者，應該在多少 MΩ 以上？",1785123172719]