[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-020":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-020","fire-106-1-alarm-evacuation-020",106,1,20,"差動式探測器之動作原理為感應火場中何種參數？",{"A":16,"B":17,"C":18,"D":19},"煙濃度","光強度","固定溫度","溫升率","D",null,[],false,"本題考點：差動式探測器之動作原理，考的是它感測的物理量究竟是溫度本身還是溫度變化率。\n【正解理由】依探測器分類之定義，差動式探測器係對「周圍溫度上升率」超過一定值時即動作之感熱式探測器；其局限型構造為一密閉感熱室，內部空氣受熱膨脹並推動膜片（隔膜）使接點閉合，感熱室另設排氣孔（漏氣孔），使緩慢的日常溫升可藉排氣洩壓而不動作，唯有溫度急遽上升、膨脹速率大於排氣速率時才會作動。可見它判別的參數是單位時間內的溫升幅度，即溫升率，故選 D。\n【逐項排除】\n(A) 煙濃度：這是偵煙式探測器（離子式感測游離電流變化、光電式感測散射或減光）所感測的參數，與感熱式的差動原理無關。\n(B) 光強度：光學量測屬火焰探測器（紫外線式、紅外線式）與光電式偵煙探測器的範疇，差動式並無受光元件。\n(C) 固定溫度：這是定溫式探測器的原理——周圍溫度達到標稱動作溫度時，靠雙金屬片彎曲或易熔絕緣物熔化使接點動作，與差動式恰成對照。\n(D) 溫升率：正確描述差動式以「單位時間溫度上升幅度」為動作條件的本質，為正解。分布型（空氣管式、熱電偶式）雖構造不同，判別的仍是溫升速率而非絕對溫度。\n【記憶點】差動看「差」——比的是溫度變化快不快；定溫看「定」——等的是溫度到不到。","感熱式探測器在《各類場所消防安全設備設置標準》第 19 條、第 115 條至第 120 條體系下分為差動式、定溫式與補償式（差動定溫兼用），並各分局限型與分布型。差動式局限型的心臟是感熱室加膜片加排氣孔的組合：常溫下室內外氣壓經排氣孔平衡；火災初期溫升率高時，室內空氣膨脹速度遠超排氣孔洩壓能力，膜片被推起、接點閉合送出火警信號。差動式分布型則以空氣管式最典型，將細銅管沿天花板佈設，管內空氣受熱膨脹推動檢出器內之膜片，優點是能涵蓋整個防護面積的平均溫升，適用於較大空間；另有熱電偶式與熱半導體式分布型，前者靠塞貝克效應產生熱電動勢，溫差越大電勢越高，達設定值即動作。\n定溫式局限型則以雙金屬片、易熔合金或密封液膨脹為機構，達到標稱動作溫度才動作，優點是不受環境緩慢升溫影響，適合廚房、鍋爐間、烘乾室等平時溫度高或有大幅溫度波動的場所；缺點是火災初期反應慢。補償式把兩種機構併入同一外殼，兼顧早期偵測與抗誤報。這組「差動／定溫／補償」的對照是本科最穩定的考點骨幹。\n設置面向的關鍵數值可一併記憶：探測器裝置面高度分為未滿四公尺、四公尺以上未滿八公尺、八公尺以上未滿十五公尺、十五公尺以上未滿二十公尺等區間，差動式局限型僅適用於未滿八公尺之裝置面；探測器下端須裝設在裝置面下方三十公分範圍內（偵煙式為六十公分）；差動式、補償式及定溫式特種或一種探測器，須裝設在距離牆壁或樑六十公分以上之位置。此外，設有排氣口或回風口時，偵煙式須距其一點五公尺以上，感熱式亦不得受氣流直接影響。\n誤報防制是差動式最常被延伸命題的方向：排氣孔阻塞會使緩慢溫升也造成膜片動作而誤報，排氣孔過大則火災時洩壓過快導致失報，故檢修時的「作動繼續試驗」與「加熱試驗」正是分別檢驗這兩種失效模式。理解排氣孔的雙向意義，差動式相關題型幾乎都能推導作答。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-019","一居室設置於地上層，該樓層亦非為無開口樓層，自內部任一點易於識別主要出入口，主要出入口之步行距離在多少以下者，得免設避難方向指示燈？",19,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-021","下列消防安全設備緊急供電系統之配線，何者需施予耐燃保護？",21,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-018","依各類場所消防安全設備檢修及申報作業基準規定，火焰探測器以動作試驗器確認探測器之動作應在多少時間內方為合格？",18,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-022","依出口標示燈及避難方向指示燈認可基準規定，燈具附有起動器者，應在多少時間內點燈？",22,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-017","檢查緩降機性能時，有關常溫下降試驗之判定中，緩降機最大下降速度應在多少以內？",17,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-023","一大樓內部某樓層設有不得供避難、通行及搬運以外用途之防火構造架空走廊一座，該樓層可依法減設多少具避難器具？",23,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-020",110,"有關辦公大樓排煙設備之啟動裝置在消防安全設備及必要檢修項目檢修基準之性能及綜合檢查的檢查及判定方法，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-020",109,"B 級出口標示燈且有顯示避難方向符號者，其有效距離係指步行至該燈多少公尺之距離？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-020",108,"依消防法令規定，觀光旅館、飯店、旅館、招待所（限有寢室客房者）等場所，採膠囊式經營時，須設置火警自動警報設備者，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-alarm-evacuation-020",107,"依各類場所消防安全設備設置標準規定，瓦斯漏氣警報裝置之檢知器所能檢知瓦斯漏氣之區域內，該檢知器動作時，該區域內之檢知區域警報裝置能發出警報音響，其音壓在距 1 公尺處應有多少分貝以上？",1785123172788]