[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-029","fire-106-1-alarm-evacuation-029",106,1,29,"瓦斯濃度達到警報濃度值後，其濃度仍繼續存在，即發出警報，但瓦斯洩漏濃度越高，則警報延遲動作時間越短，此種檢知瓦斯之警報發出方式稱作何種型式？",{"A":16,"B":17,"C":18,"D":19},"反誤報警報型","警報延時型","即時警報型","反限時警報型","D",null,[],false,"本題考點：瓦斯漏氣火警自動警報設備中,檢知器依警報發出方式所作的型式分類。\n【正解理由】瓦斯檢知器的警報發出方式分為即時警報型、警報延時型與反限時警報型三種。題幹描述「濃度達警報濃度值後仍持續存在才發出警報」,顯示具有延時判定以防誤報;而「瓦斯洩漏濃度愈高,警報延遲時間愈短」則表示延遲時間與濃度成反比,亦即動作時間隨激發量增加而縮短,這正是電機保護電驛所稱「反限時(inverse time)」特性套用在瓦斯檢知上的命名。兩項特徵合起來即為反限時警報型,故選 D。\n【逐項排除】\n(A) 反誤報警報型並非我國瓦斯漏氣檢知器的正式型式分類名稱,係干擾用選項。\n(B) 警報延時型雖有延時,但其延遲時間為固定值,不隨瓦斯濃度高低改變,與題幹「濃度愈高延遲愈短」不符。\n(C) 即時警報型是濃度一達警報設定值即刻發出警報,完全不設延時,與題幹「濃度仍繼續存在才發出警報」矛盾。\n(D) 正確,兼具延時判定與延時隨濃度反比縮短兩項特徵者,即反限時警報型。\n【記憶點】即時型不等、延時型固定等、反限時型濃度愈濃等愈短。","瓦斯漏氣火警自動警報設備依《各類場所消防安全設備設置標準》設於使用天然氣、液化石油氣或以管線輸送可燃氣體之場所,系統由檢知器、警報裝置與受信總機組成。檢知器的偵測原理主要有半導體式、接觸燃燒式與氣體熱傳導式,其中半導體式最普遍:氧化錫等金屬氧化物半導體在加熱狀態下吸附可燃氣體時電阻下降,藉電阻變化判定濃度。\n之所以要區分三種警報發出方式,關鍵在於誤報成本。瓦斯檢知器裝設於廚房、鍋爐間等本來就可能短暫出現微量可燃氣體的位置(例如點火瞬間、爐具熄火的殘氣),若採純即時警報型,極易因瞬間濃度尖峰而動作,長期下來使用人會對警報麻痺,甚至私自斷電,反而降低整體安全。警報延時型以固定延遲濾掉瞬間干擾,但缺點是遇到大量洩漏時仍需等滿固定秒數,喪失寶貴反應時間。反限時警報型結合兩者優點:低濃度時給較長的確認時間以濾除干擾,高濃度時大幅縮短延遲、近乎即時動作,使風險與反應速度呈合理配對。\n記憶對照可與探測器的分類並列:定溫式局限型看到達設定溫度才動作、差動式局限型看溫升速率,而具備兩者特性的補償式(定溫差動補償式)則兼收並蓄——同樣是「固定閾值」與「變化速率」的組合思維,反限時警報型在瓦斯檢知上扮演的正是類似角色。\n相關數值考點:瓦斯漏氣檢知器之警報設定濃度一般為爆炸下限的四分之一以下;檢知器裝設位置依瓦斯比重而異,比空氣輕者裝於天花板附近且與燃燒器具水平距離 8 公尺以內、下端在天花板下方 30 公分範圍內,比空氣重者裝於接近地面且水平距離 4 公尺以內、上端距樓地板 30 公分範圍內。這組數值與本題的型式分類常在同一份考卷中交叉出現。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-028","大型建築物警報設備使用許多中繼器來連結探測器與受信總機，但下列何者不是警報設備中繼器主要功能？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-030","在某飯店檢查瓦斯漏氣火警自動警報設備時，何項試驗必須切換成緊急電源之狀態？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-027","避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度，應在多少勒克司（lx）以上？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-031","在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-026","樓梯或斜坡通道以外之場所，廣播區域之殘響時間在 3 秒以上時，揚聲器之裝設需符合 r = 3 \u002F 4 QSα\u002Fπ (1 −α) 之計算公式，S 的定義為何？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-032","針對瓦斯漏氣火警自動警報設備進行性能檢查，使用噪音計進行瓦斯漏氣檢知區域警報裝置之音量檢測時，距離警報裝置 1 公尺處，其音壓量應在多少分貝以上方為合格？",32,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-029",110,"有關瓦斯漏氣檢知器之設置，當瓦斯對空氣之比重小於 1 時，應設於距瓦斯燃燒器具水平距離 A 公尺以內；當瓦斯對空氣之比重大於 1 時，應設於距瓦斯燃燒器具水平距離 B 公尺以內，其中 A 及 B 分別為：",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-029",109,"有關瓦斯漏氣火警自動警報設備檢知器外觀檢查選取之檢查數量，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-029",108,"消防安全設備測試報告書測試方法及判定要領中規定，火警自動警報設備外觀試驗，其定溫式感知線型探測器之判定要領中，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-alarm-evacuation-029",107,"依各類場所消防安全設備設置標準規定，有關標示設備之敘述，何者正確？",1785123172880]