[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-030":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-030","fire-106-1-alarm-evacuation-030",106,1,30,"在某飯店檢查瓦斯漏氣火警自動警報設備時，何項試驗必須切換成緊急電源之狀態？",{"A":16,"B":17,"C":18,"D":19},"瓦斯漏氣表示試驗","綜合動作試驗","同時動作試驗","回路導通試驗","B",null,[],false,"本題考點：《消防安全設備檢修及申報作業基準》中,瓦斯漏氣火警自動警報設備各項試驗的檢查條件差異。\n【正解理由】依《消防安全設備檢修及申報作業基準》關於瓦斯漏氣火警自動警報設備之綜合檢查,綜合動作試驗係在「將電源切換為緊急電源狀態」下,以加瓦斯試驗器對任一檢知器加入試驗用氣體,確認受信總機之瓦斯漏氣表示、區域警報裝置鳴動與相關連動功能均能正常作動。其設計用意在於模擬真實災害情境——瓦斯外洩往往伴隨切斷常用電源,故必須驗證系統在緊急電源供電下仍具完整功能與足夠容量,故選 B。\n【逐項排除】\n(A) 瓦斯漏氣表示試驗屬受信總機的性能檢查,以試驗裝置確認表示燈與音響,在常用電源下即可執行。\n(B) 正確,綜合動作試驗明定須切換為緊急電源狀態進行,是本設備唯一有此要求的試驗項目。\n(C) 同時動作試驗是使兩回路檢知器同時動作以確認受信總機不致失能,屬性能檢查範疇,不要求切換電源。\n(D) 回路導通試驗係量測配線是否斷線,以常用電源操作總機導通試驗開關即可完成。\n【記憶點】名字有「綜合」的,就是切到緊急電源整套跑一次。","《消防安全設備檢修及申報作業基準》把檢修拆成外觀檢查、性能檢查與綜合檢查三個層級,這個三分法是本科最值得先建立的骨架。外觀檢查靠目視,看變形、腐蝕、標示、周圍障礙;性能檢查針對單一元件或單一機能,例如檢知器加氣動作、受信總機的表示試驗、回路導通試驗;綜合檢查則是把整套系統當一個整體,在最接近實際災害的條件下驗證端到端功能,因此才會要求切換至緊急電源。\n緊急電源在本設備通常為蓄電池設備,《各類場所消防安全設備設置標準》要求其容量須能使設備有效動作一定時間。以緊急電源執行綜合動作試驗,同時檢驗了三件事:一是充電裝置是否確實把蓄電池維持在可用狀態;二是自動切換裝置能否在常用電源喪失時無縫接手;三是蓄電池容量是否足以支撐受信總機與警報裝置同時作動的尖峰負載。若只在常用電源下試驗,前述三項全部被略過,而它們恰是實際火災中最常失效的環節。\n易混淆對照整理:瓦斯漏氣表示試驗確認的是「顯示」;同時動作試驗確認的是「多回路併發時不失能」;回路導通試驗確認的是「線路完好」;綜合動作試驗確認的是「緊急電源下全系統可用」。以火警自動警報設備類比,其綜合檢查同樣以同時動作試驗與緊急電源切換為核心,兩套設備的檢修邏輯可相互援引記憶。\n另一組常一併命題的判定基準是:瓦斯漏氣受信總機自檢知器動作至發出警報之時間應在 60 秒以內;區域警報裝置於距離 1 公尺處音壓 70 分貝以上。將「綜合動作試驗須切換緊急電源」與這兩個數值一起記,可覆蓋本設備檢修題的大半分數。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-029","瓦斯濃度達到警報濃度值後，其濃度仍繼續存在，即發出警報，但瓦斯洩漏濃度越高，則警報延遲動作時間越短，此種檢知瓦斯之警報發出方式稱作何種型式？",29,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-031","在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",31,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-028","大型建築物警報設備使用許多中繼器來連結探測器與受信總機，但下列何者不是警報設備中繼器主要功能？",28,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-032","針對瓦斯漏氣火警自動警報設備進行性能檢查，使用噪音計進行瓦斯漏氣檢知區域警報裝置之音量檢測時，距離警報裝置 1 公尺處，其音壓量應在多少分貝以上方為合格？",32,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-027","避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度，應在多少勒克司（lx）以上？",27,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-033","針對某百貨公司美食街進行檢修，下列何項試驗必須使用加瓦斯試驗器，使兩個回路之任一檢知器（各回路一個）同時動作，以確認其性能是否異常？",33,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-030",110,"火警自動警報設備之緊急電源，其容量能使其有效動作 A 分鐘以上；緊急廣播設備之緊急電源，其容量能使其有效動作 B 分鐘以上，其中 A 及 B 分別為：",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-030",109,"有關緊急廣播設備標示燈外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準規定相同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-030",108,"利用各種減光罩對光電式分離型探測器進行測試，以確認其火災動作試驗、不作動試驗、故障警報試驗並判定是否符合規定，下列方式何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-alarm-evacuation-030",107,"偵煙式探測器除光電式分離型外，下列裝置規定何者錯誤？",1785123172893]