[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-032","fire-106-1-alarm-evacuation-032",106,1,32,"針對瓦斯漏氣火警自動警報設備進行性能檢查，使用噪音計進行瓦斯漏氣檢知區域警報裝置之音量檢測時，距離警報裝置 1 公尺處，其音壓量應在多少分貝以上方為合格？",{"A":16,"B":17,"C":18,"D":19},"50","60","70","85","C",null,[],false,"本題考點：瓦斯漏氣檢知區域警報裝置之音壓判定基準,規定於《各類場所消防安全設備設置標準》第 141 條。\n【正解理由】依《各類場所消防安全設備設置標準》第 141 條,瓦斯漏氣之檢知區域警報裝置,其音壓在距離一公尺處應在 70 分貝以上;檢修即依此以噪音計於距警報裝置 1 公尺處實測,達 70 分貝以上判定合格。其用意在使警報聲明顯高於廚房、機房之背景噪音,故選 C。\n【逐項排除】\n(A) 50 分貝約為室內談話下限,低於法定判定值,無法穿透排油煙機等背景噪音。\n(B) 60 分貝仍未達本設備判定基準,以此驗收會使音壓不足之警報裝置被誤判合格。\n(C) 正確,70 分貝即距離 1 公尺處之音壓下限,為本設備之判定值。\n(D) 85 分貝屬緊急廣播設備 L 級揚聲器等更高音壓的量級,非本裝置之判定值。\n【演算步驟】判定式:實測音壓 L₁ ≥ 70 dB(距離 d = 1 m)。若改於 d = 2 m 量測,點音源衰減 ΔL = 20 log(2 m \u002F 1 m) = 20 × 0.301 = 6.02 dB;換算 L₁ = L₂ + 6.02 dB。設 2 m 處測得 66 dB,則 L₁ = 66 dB + 6.02 dB = 72.0 dB ≥ 70 dB,合格。\n【記憶點】一公尺、七十分貝,瓦斯漏氣區域警報就記這一組數。","《各類場所消防安全設備設置標準》第 141 條規範瓦斯漏氣火警自動警報設備之警報裝置,內容包含瓦斯漏氣表示燈、檢知區域警報裝置與音響警報裝置三類。檢知區域警報裝置的任務是讓「發生洩漏的那一區」的人立即知道,因此規定其音壓在距一公尺處達 70 分貝以上;若一警報裝置有效範圍內任一點至該裝置之水平距離超過規定,則須增設。表示燈則規定其亮燈在前方三公尺處能明確識別。\n分貝是對數尺度,這是本題延伸計算的關鍵。聲壓級 L = 20 log(p\u002Fp₀),參考聲壓 p₀ = 20 μPa。距離加倍時,點音源的聲壓減半,故聲壓級下降 20 log 2 ≈ 6 分貝,此即「距離加倍衰減 6 分貝」法則;能量觀點下聲強與距離平方成反比,10 log 4 同樣得 6 分貝,兩種算法一致。此外分貝不可直接相加:兩個等音壓聲源疊加只增加 10 log 2 ≈ 3 分貝,而非兩倍數值,考題常以此設計陷阱。\n音壓數值對照表便於整批記憶:瓦斯漏氣檢知區域警報裝置 1 公尺處 70 分貝以上;火警自動警報設備之火警警鈴音響在 1 公尺處 90 分貝以上;緊急廣播設備揚聲器 L 級 92 分貝以上、M 級 87 分貝以上、S 級 84 分貝以上,且 L 級適用樓地板面積超過 100 平方公尺之廣播區域。可歸納為「瓦斯 70、警鈴 90、廣播 84\u002F87\u002F92」。\n檢修實務面的判定要點:量測應在背景噪音較低的時段進行,噪音計採 A 加權;若背景噪音與警報聲差距不足 10 分貝,須就背景噪音作修正後再判定。相關考點連結尚有瓦斯漏氣受信總機自檢知器動作至警報發出應在 60 秒以內,以及緊急電源之有效動作時間要求,常與本題同卷出現。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-031","在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-033","針對某百貨公司美食街進行檢修，下列何項試驗必須使用加瓦斯試驗器，使兩個回路之任一檢知器（各回路一個）同時動作，以確認其性能是否異常？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-030","在某飯店檢查瓦斯漏氣火警自動警報設備時，何項試驗必須切換成緊急電源之狀態？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-034","在裝設定溫式感知線型探測器場所，進行回路合成阻抗試驗時，會使用下列何種檢查儀器？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-029","瓦斯濃度達到警報濃度值後，其濃度仍繼續存在，即發出警報，但瓦斯洩漏濃度越高，則警報延遲動作時間越短，此種檢知瓦斯之警報發出方式稱作何種型式？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-035","執行檢修時，在室溫 15℃狀態下，使用加熱試驗器進行差動式局限型第二種探測器之性能檢查時，其動作時間應在多少秒內方為正常？",35,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-032",110,"下列有關得免設緊急照明設備之處所，何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-032",109,"有關無線電通信輔助設備保護箱標示之外觀檢查的判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-032",108,"下列出口標示燈及避難方向指示燈之緊急電源描述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-alarm-evacuation-032",107,"依各類場所消防安全設備設置標準規定，下列何者非屬消防搶救上之必要設備種類？",1785123172905]