[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-106-1-alarm-evacuation-035":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-警報與避難系統消防安全設備概要-035","fire-106-1-alarm-evacuation-035",106,1,35,"執行檢修時，在室溫 15℃狀態下，使用加熱試驗器進行差動式局限型第二種探測器之性能檢查時，其動作時間應在多少秒內方為正常？",{"A":16,"B":17,"C":18,"D":19},"20","30","40","50","B",null,[],false,"本題考點：差動式局限型探測器以加熱試驗器進行性能檢查時之動作時間判定基準,依據《消防安全設備檢修及申報作業基準》。\n【正解理由】依《消防安全設備檢修及申報作業基準》關於火警自動警報設備探測器之性能檢查,以加熱試驗器對差動式局限型探測器加熱,其動作時間之判定基準為 30 秒以內(第一種、第二種相同);室溫僅影響是否須採用修正,在一般室溫條件下仍以 30 秒為判定值。題目所述室溫 15℃屬常態範圍,故動作時間應在 30 秒內方為正常,故選 B。\n【逐項排除】\n(A) 20 秒短於判定基準,以此判定會把仍屬正常的探測器誤判為不良而汰換。\n(B) 正確,差動式局限型探測器加熱試驗之動作時間判定值為 30 秒以內。\n(C) 40 秒超過判定基準,屬定溫式局限型等其他型式在特定條件下才可能適用的較長時限,不適用本題。\n(D) 50 秒更長,已明顯逾越差動式局限型的動作時間要求,採用將使反應遲鈍的探測器被誤判合格。\n【演算步驟】判定式:實測動作時間 t ≤ 30 s。設實測 t = 22 s,餘裕 = 30 s − 22 s = 8 s ≥ 0,判定正常;若實測 t = 34 s,則 34 s − 30 s = 4 s > 0 為超時,判定不良。故本題所求上限值 = 30 s。\n【記憶點】差動式局限型加熱一下,三十秒內要動,超過就不合格。","差動式局限型探測器的動作原理是感熱室內空氣受熱膨脹推動膜片,使接點閉合;膜片背面設有排氣孔(洩漏孔),使緩慢的日常溫升可經由排氣孔洩掉而不動作,唯有溫升速率夠快時膨脹量來不及洩出才會動作。因此它偵測的是「溫升速率」而非絕對溫度,適用於平時溫度變化不大、火災時溫度上升快的一般居室;而定溫式局限型偵測的是「絕對溫度」,達標稱動作溫度才動作,適用於廚房、鍋爐間等平時就有溫度變動的場所。第一種與第二種的差別在靈敏度與有效感知面積:同樣裝設高度下,第一種的感知面積較大,可涵蓋較大樓地板面積,第二種較小。\n檢修的加熱試驗器是一具內含電熱線的罩杯,罩住探測器後通電加熱以模擬火災溫升。判定關注兩件事:一是「會不會動作」,二是「多快動作」。動作時間過長,代表感熱室洩漏孔阻塞、膜片老化或接點間隙變大,火災時將延誤警報;完全不動作則須更換。檢查後須確認探測器可正常復歸,否則將造成持續發報。\n數值整理:探測器性能檢查抽驗同樣採每回路一定比例並逐年輪替,不逐一全檢;火警警鈴音壓於距 1 公尺處 90 分貝以上;火警自動警報設備配線之絕緣電阻一般判定為 0.1 MΩ 以上;差動式分布型(空氣管式)則以測試幫浦注入空氣,量測動作時間與接點水高,判定其是否在規定範圍。\n易混淆概念對照:補償式局限型兼具差動與定溫兩種機能,任一條件成立即動作,常設於溫度變化較大但仍需早期偵知的場所;偵煙式局限型則以離子式或光電式偵測煙粒子,其性能檢查改用加煙試驗器,動作時間依種別另有判定值。把「原理—適用場所—試驗器材—動作時間」四欄列表,是本科探測器題型最有效率的複習法。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-alarm-evacuation-034","在裝設定溫式感知線型探測器場所，進行回路合成阻抗試驗時，會使用下列何種檢查儀器？",34,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-alarm-evacuation-036","很多工程裝設局限型探測器時多緊鄰天花板上出風口，造成失效或延遲警報，因此，施工時依規定裝設位置應距該出風口多少公尺以上？",36,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-alarm-evacuation-033","針對某百貨公司美食街進行檢修，下列何項試驗必須使用加瓦斯試驗器，使兩個回路之任一檢知器（各回路一個）同時動作，以確認其性能是否異常？",33,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-alarm-evacuation-037","為避免探測死角，在安裝光電式分離型探測器時，其受光器及送光器應設在距其背部牆壁多少公分範圍內？",37,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-alarm-evacuation-032","針對瓦斯漏氣火警自動警報設備進行性能檢查，使用噪音計進行瓦斯漏氣檢知區域警報裝置之音量檢測時，距離警報裝置 1 公尺處，其音壓量應在多少分貝以上方為合格？",32,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，避難指標設於出入口裝設應距樓地板面的高度要求為多少？",38,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-035",110,"依各類場所消防安全設備設置標準規定，避難指標設於走廊或通道時，自走廊或通道任一點至指標之步行距離在多少公尺以下？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-035",109,"有關避難器具開口部周圍狀況外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-035",108,"依各類場所消防安全設備設置標準規定，在應設排煙設備之場所，有關其排煙設備設置之描述，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-alarm-evacuation-035",107,"依各類場所消防安全設備檢修及申報作業基準規定，緊急電源插座為單相交流 110 V 者，應用額定 150 V， X 安培之接地型插座。三相交流 220 V 者則適用額定 250 V，Y 安培接地型插座，並確認應無變形、損傷、顯著腐蝕或異物阻塞等，下列何者正確？",1785123172939]