[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-law-005":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-消防法規概要-005","fire-106-1-fire-law-005",106,1,5,"依各類場所消防安全設備設置標準規定，下列何種場所應設置連結送水管？",{"A":16,"B":17,"C":18,"D":19},"五層建築物總樓地板面積在 4,000 平方公尺","六層建築物總樓地板面積在 5,000 平方公尺","七層以上建築物","總樓地板面積在 500 平方公尺以上之地下建築物","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》關於連結送水管應設置場所之樓層與樓地板面積門檻。\n【正解理由】依《各類場所消防安全設備設置標準》有關連結送水管之設置規定,應設置之場所為:七層以上之建築物;五層或六層建築物且總樓地板面積在 6,000 平方公尺以上者;以及總樓地板面積在 1,000 平方公尺以上之地下建築物。連結送水管的功能是讓消防車的水能藉固定配管送到高層或深層,因此門檻設計以「射水難以到達」為核心,七層以上不論面積一律應設,故選 C。\n【逐項排除】\n(A) 錯誤。五層建築物須總樓地板面積達 6,000 平方公尺以上才應設,4,000 平方公尺未達門檻。\n(B) 錯誤。六層建築物適用的門檻同為 6,000 平方公尺以上,5,000 平方公尺仍不足。\n(C) 正確。七層以上建築物屬無面積條件的絕對門檻,只要層數達標即應設置連結送水管。\n(D) 錯誤。地下建築物的門檻是總樓地板面積 1,000 平方公尺以上,500 平方公尺尚未達到。\n【記憶點】連結送水管記「七層免問面積,五六層看 6,000,地下看 1,000」。","連結送水管在消防安全設備體系中屬於消防搶救上之必要設備,與滅火設備、警報設備、避難逃生設備並列但目的不同:前三者服務的是場所內的人與初期火勢,連結送水管服務的是到場的消防人員。它的核心是一組由建築物外部送水口、立管、各樓層出水口與必要時的中繼幫浦組成的固定管路,消防車把水打進送水口,人員只需帶著水帶與瞄子上樓接出水口即可射水,不必從地面一路延長水帶。理解這個運作邏輯,門檻設計就很好記:層數高到水帶延長不可行、面積大到搶救動線過長、或位於地下而射水無從進入者,就是應設場所。\n數值上要與相鄰設備一起背才不會互相干擾。連結送水管的高度門檻是七層以上;中繼幫浦則是在建築物高度超過 60 公尺時,為克服摩擦損失與落差而須增設,並有中繼水箱的容量要求。出水口原則設於三層以上各樓層,並考慮設於樓梯間或緊鄰之場所,理由是搶救人員必然沿安全梯上樓,出水口設在動線上才有意義。這一組「七層、60 公尺、三層以上設出水口」是最常被交叉命題的三個數字。\n易混淆之處在於連結送水管與消防專用蓄水池、緊急電源插座同屬消防搶救上之必要設備,但門檻各自不同:消防專用蓄水池的判準走的是基地面積與各層樓地板面積合計;緊急電源插座則與高度 11 層以上或地下建築物有關。作答時先確認題目問的是哪一種設備,再套對應數字,否則數值背得再熟也會錯位。\n另可留意本設備與室內消防栓設備的分工:室內消防栓是供場所內人員初期滅火,水源與加壓送水裝置都在場所內;連結送水管本身不備水源,水由消防車供給,兩者在檢修基準上的測試項目也因此不同,前者測放水壓力與放水量,後者重在送水耐壓與各出水口的送水壓力。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-law-004","依各類場所消防安全設備設置標準規定，幼兒園按用途分類係屬於何種場所？",4,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-law-006","依據各類場所消防安全設備設置標準規定，集會堂使用之舞臺在設置自動撒水設備時，應選擇下列何者？",6,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-law-003","下列有關公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法之相關用語定義，何者正確？",3,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-law-007","依據各類場所消防安全設備設置標準規定，公共危險物品製造場所符合下列何者要件，則屬顯著滅火困難場所？",7,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-law-002","依據消防法規定，下列何者應舉辦防火教育及宣導？",2,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-law-008","依據各類場所消防安全設備設置標準規定，對瓦斯漏氣檢知器設置，下列敘述何者正確？",8,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-005",111,"有關公共危險物品儲存及處理場所之名詞解釋，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-005",110,"下列場所何者屬一定規模以上供公眾使用建築物，應由管理權人，遴用防火管理人，責其製定消防防護計畫，報請消防機關核備？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-005",109,"依消防設備師及消防設備士管理辦法之規定，直轄市、縣（市）之消防設備師或消防設備士達多少人以上者，得組織直轄市、縣（市）消防設備師公會或消防設備士公會：",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-law-005",108,"下列何者非符合消防法規所定一定規模以上供公眾使用建築物之範圍？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-fire-law-005",107,"依各類場所消防安全設備設置標準之規定，無線電通信輔助設備的無線電接頭之設置，下列何者錯誤？",1785123159768]