[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-law-008":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-消防法規概要-008","fire-106-1-fire-law-008",106,1,8,"依據各類場所消防安全設備設置標準規定，對瓦斯漏氣檢知器設置，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"瓦斯對空氣之比重未滿一時，檢知器設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離 10 公尺以內","瓦斯對空氣之比重未滿一時，檢知器下端，裝設在天花板下方 30 公分範圍內","瓦斯對空氣之比重大於一時，檢知器設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離 5 公尺以內","瓦斯對空氣之比重大於一時，檢知器上端，裝設在距樓地板面 60 公分範圍內","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》瓦斯漏氣火警自動警報設備之檢知器設置位置,依瓦斯對空氣比重分為輕重兩套規定。\n【正解理由】依《各類場所消防安全設備設置標準》關於瓦斯漏氣檢知器之設置規定,瓦斯對空氣之比重未滿一者,檢知器應設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離 8 公尺以內,且檢知器下端裝設在天花板下方 30 公分範圍內;比重大於一者,水平距離為 4 公尺以內,檢知器上端裝設在距樓地板面 30 公分範圍內。選項 B 所述之天花板下方 30 公分完全符合輕瓦斯規定,故選 B。\n【逐項排除】\n(A) 錯誤。比重未滿一時水平距離為 8 公尺以內,寫 10 公尺已超出規定範圍。\n(B) 正確。比重未滿一之瓦斯較空氣輕,漏氣後上浮蓄積於天花板附近,故檢知器下端須在天花板下方 30 公分範圍內。\n(C) 錯誤。比重大於一時水平距離為 4 公尺以內,寫 5 公尺不符。\n(D) 錯誤。比重大於一時,檢知器上端應在距樓地板面 30 公分範圍內,寫 60 公分過高,會錯過貼地蓄積的瓦斯層。\n【記憶點】輕瓦斯貼天花板、重瓦斯貼地板,兩者都抓 30 公分;水平距離則是「輕 8 重 4」。","瓦斯漏氣火警自動警報設備由檢知器、警報裝置與受信總機組成,與火警自動警報設備最大的差別在於它偵測的不是燃燒產物,而是尚未起火的可燃氣體本身,屬於防止爆炸與火災發生的前端設備。設置規定的每一個數字,都是從氣體擴散行為推導出來的,理解物理現象比死背數字可靠。\n比重是全部規定的分岔點。天然氣主成分為甲烷,分子量約 16,對空氣比重約 0.55,屬於比重未滿一;液化石油氣主成分為丙烷與丁烷,分子量分別約 44 與 58,對空氣比重約 1.5 至 2.0,屬於比重大於一。輕瓦斯洩漏後浮升,沿天花板形成擴散層,因此檢知器要往上貼,規定下端在天花板下方 30 公分範圍內;重瓦斯洩漏後沉降,沿樓地板面流動蓄積於低處與凹陷處,檢知器要往下貼,規定上端在距樓地板面 30 公分範圍內。水平距離之所以輕的給 8 公尺、重的只給 4 公尺,是因為輕瓦斯上浮後在頂棚下橫向擴散快、涵蓋範圍大,重瓦斯貼地流動受家具與地形阻擋,擴散慢且路徑不確定,必須設得更密才不會漏偵。\n另有兩項常被併考的規定:檢知器不得設於出風口 1.5 公尺範圍內,因為氣流會把洩漏氣體吹散,造成濃度稀釋而延遲動作;也不得設於樓梯、通風管、走廊、昇降機、避難梯等處,因為這些位置氣流強且非蓄積點,偵測意義低。警報部分,瓦斯漏氣表示燈與檢知區域警報裝置的音壓、以及受信總機於檢知器動作後應在 60 秒內發出警報,也是常見數值題。\n易混淆的是本設備與火警自動警報設備的探測器規定。探測器分定溫式、差動式、偵煙式,其設置以感熱或感煙特性、樓板高度與裝置面為準;瓦斯漏氣檢知器則完全以氣體比重為準。兩者的距離數字不可互相套用,遇到題目先確認問的是探測器還是檢知器。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-law-007","依據各類場所消防安全設備設置標準規定，公共危險物品製造場所符合下列何者要件，則屬顯著滅火困難場所？",7,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-law-009","依據各類場所消防安全設備設置標準規定，公共危險物品等場所之滅火設備分類，下列敘述何者正確？",9,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-law-006","依據各類場所消防安全設備設置標準規定，集會堂使用之舞臺在設置自動撒水設備時，應選擇下列何者？",6,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-law-010","依據公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，公共危險物品之範圍及分類下列何者正確？",10,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-law-005","依各類場所消防安全設備設置標準規定，下列何種場所應設置連結送水管？",5,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-law-011","依據公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，儲存公共危險物品之數量在管制量 20 倍以下者，建築物之一部分在符合相關規定下，得供作室內儲存場所使用，下列何種公共危險物品可儲存於上述之室內儲存場所？",11,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-008",111,"可燃性高壓氣體儲存場所防爆牆設置規定，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-008",110,"依消防設備師及消防設備士管理辦法規定，消防設備師及消防設備士執行業務，應備業務登記簿，以書面簿冊形式或電子檔案方式，記載委託人姓名或名稱、住所、委託事項及辦理情形之詳細紀錄，並應妥善保存，以備各級消防機關之查核。上述業務登記簿保存年限至少幾年？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-008",109,"依消防安全設備檢修專業機構管理辦法之規定，消防安全設備檢修專業機構所屬消防設備師或消防設備士檢修不實經裁罰達 5 件以上者，多久時間內不得重新申請證書？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-law-008",108,"依公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，液化石油氣在常用溫度下或溫度在攝氏 35 度以下時，表壓力達每平方公分多少公斤以上時，為可燃性高壓氣體？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-fire-law-008",107,"依避難器具支固器具及固定部之結構、強度計算及施工方法之規定，以金屬膨脹錨定螺栓之施工方法（輕形混凝土或氣泡混凝土製造者除外），若使用金屬膨脹錨定螺栓之口徑為 M20，其埋入深度需為多少毫米？",1785123159803]