[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-law-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-消防法規概要-026","fire-106-1-fire-law-026",106,1,26,"下列有關防火水幕設備之水源容量規定之敘述，何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"儲槽容量未達 10,000 公秉者，不得小於防護該儲槽連續放水 180 分鐘之水量","儲槽容量達 10,000 公秉以上者，不得小於防護該儲槽連續放水 240 分鐘之水量","消防用水與普通用水合併使用者，應採取必要措施，確保前款水源容量，在有效水量範圍內","與其他滅火設備水源併設時，其總容量不得小於防護同一儲槽各滅火設備應設水量之合計","A",null,[],false,"本題考點：公共危險物品儲槽防火水幕設備之水源容量規定，以及水源與其他用水、其他滅火設備併用時的計算原則。\n【正解理由】依防火牆及防火水幕設置基準關於水源容量之規定，水源容量以「防護該儲槽連續放水之時間」換算，且依儲槽容量是否達10,000公秉分為兩級，容量愈大者所需連續放水時間愈長。本選項所載未達10,000公秉者之連續放水時間數值與基準所定不符，屬錯誤敘述；題目問「何者錯誤」，故選 A。\n【逐項排除】\n(A) 錯誤。分級門檻10,000公秉無誤，錯在未達該門檻時所對應之連續放水時間，本選項所寫的180分鐘並非基準所定數值。\n(B) 正確。儲槽容量達10,000公秉以上者，屬較高一級的水源要求，其連續放水時間為240分鐘。\n(C) 正確。消防用水與普通用水合併使用者，應採取必要措施確保前款水源容量在有效水量範圍內，避免日常用水把消防水位耗掉。\n(D) 正確。與其他滅火設備水源併設時，總容量不得小於防護同一儲槽各滅火設備應設水量之合計，即水量採相加而非取大值。\n【記憶點】「大槽四小時、併用要相加、合併用水看有效水量」——先抓分級門檻，再核對時間。","防火水幕設備出現在公共危險物品場所的脈絡，與一般建築物的滅火設備不同：大型儲槽區一旦起火，火焰高度與輻射熱足以引燃鄰槽，形成連鎖延燒，因此規範重點不是「把火撲滅」，而是「用水膜隔絕輻射熱、保護鄰接對象」。這種以水幕取代實體防火牆的設計，得以在儲槽區維持操作與檢查所需的通行空間，因此設置基準把防火牆與防火水幕並列為可替代方案。\n\n水源容量的立法邏輯是時間×流量：水幕的價值在於「持續」，中途斷水等同防護歸零，所以基準以連續放水時間直接規定水源下限，而非以單次滅火水量計。儲槽容量愈大，火災延燒時間與熱輻射持續時間愈長，所需連續放水時間也隨之拉長，這就是以10,000公秉為界分成兩級的理由。應試時要牢記的是「分級門檻10,000公秉」與「大容量級為240分鐘」，並理解時間分級只有兩級、沒有中間級距。\n\n併用規則同樣考得很細，且方向相反的兩個原則常被混淆：其一，消防用水與「普通用水」合併時，重點是確保消防所需水量始終落在有效水量範圍內，也就是普通用水不得侵蝕消防水位；其二，與「其他滅火設備」水源併設時，採各設備應設水量「合計」而非取最大值，因為同一起火事故可能同時啟動多套設備，若只取大值將導致實戰時水量不足。\n\n相關考點連結：同一基準另常考防火水幕的放水量與防護高度之關係、配管是否得與他系統併用、加壓試驗之壓力與持續時間；與《公共危險物品設置標準》合併命題時，則會問儲槽防液堤容量、儲槽間距與安全距離之計算。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-law-025","依公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，下列有關六類物品製造場所之敘述，何者正確？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-law-027","下列有關防火牆及防火水幕設置基準規定之敘述，何者錯誤？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-law-024","下列有關消防安全設備檢修專業機構管理辦法規定之敘述，何者錯誤？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-law-028","依可燃性高壓氣體儲存場所防護牆設置基準規定，鋼筋混凝土製防護牆，其厚度應在多少 mm 以上？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-law-023","下列有關消防設備師及消防設備士管理辦法規定之敘述，何者錯誤？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-law-029","下列有關簡易自動滅火設備規定之敘述，何者錯誤？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-026",111,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，液化石油氣備用量，供營業使用者，不得超過 X 公斤；供家庭使用者，不得超過 Y 公斤，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-026",110,"依各類場所消防安全設備設置標準規定，裝設火警自動警報設備之建築物，其火警分區劃定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-026",109,"原有照護思覺失調患者的康復之家想增設自動滅火設備，如採用小區劃型撒水頭（以第一種感度為限），依各類場所消防安全設備設置標準，其撒水頭間距要在多少公尺以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-law-026",108,"依防火牆及防火水幕設置基準規定，若防火水幕之防護高度為 12 公尺，請問其每公尺水幕長度放水量應在每分鐘多少公升以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-fire-law-026",107,"公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法所稱高閃火點物品，指閃火點在攝氏 X 度以上之第 Y 類公共危險物品，X、Y 分別為多少？",1785123160013]