[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-law-027":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-消防法規概要-027","fire-106-1-fire-law-027",106,1,27,"下列有關防火牆及防火水幕設置基準規定之敘述，何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"防火水幕之防護高度在 10 公尺以下時，其每公尺水幕長度放水量應在每分鐘 100 公升以上","防火水幕之防護其防護高度超過 10 公尺者，高度每增加 1 公尺，放水量每分鐘應增加 10 公升","防火水幕配管之設置可與其他滅火設備水源配管併用","配管管系竣工時，應做加壓試驗，試驗壓力為加壓送水裝置全閉揚程 1.5 倍以上之水壓，須持續 2 小時無漏水現象","C",null,[],false,"本題考點：防火牆及防火水幕設置基準中，水幕放水量與防護高度之對應關係、配管專用原則與竣工加壓試驗要件。\n【正解理由】依防火牆及防火水幕設置基準關於配管之規定，防火水幕之配管應為專用，不得與其他滅火設備之水源配管併用，理由在於他系統一旦先行動作或發生洩漏，將直接削減水幕的放水量與壓力，使防護中斷。本選項稱配管「可與其他滅火設備水源配管併用」，與專用原則相違；題目問「何者錯誤」，故選 C。\n【逐項排除】\n(A) 正確。防護高度在10公尺以下時，每公尺水幕長度之放水量應在每分鐘100公升以上，此為基本放水量。\n(B) 正確。防護高度超過10公尺者，高度每增加1公尺，放水量每分鐘增加10公升，屬線性遞增的加成規定。\n(C) 錯誤。錯在「配管併用」；水源容量得併設計算是一回事，配管必須專用是另一回事，兩者不可混為一談。\n(D) 正確。配管管系竣工時應做加壓試驗，試驗壓力為加壓送水裝置全閉揚程1.5倍以上之水壓，且須持續2小時無漏水現象。\n【記憶點】「十公尺一百公升，每高一米加十公升；水量可併算，配管不可共用。」","防火水幕以水膜阻隔輻射熱，其防護效果與「單位長度放水量」成正比，也與水幕的高度有關：防護高度愈高，水滴下落過程中被熱氣流吹散、蒸發的比例愈高，抵達目標的有效水量遞減，因此基準以10公尺為基準高度訂出每公尺長度每分鐘100公升的底線，超過部分再以每公尺加10公升的方式線性補償。這種「基準值＋加成值」的立法技術，在消防法規中相當常見，記憶時只要抓住基準點與加成率兩個數字即可推算，例如防護高度15公尺者，每公尺水幕長度之放水量即為100＋(15−10)×10＝150公升\u002F分。\n\n配管專用原則的理由值得單獨理解。滅火設備的可靠度取決於「動作時能否取得設計流量與壓力」，若水幕與其他滅火設備共用配管，任一系統先行放水都會造成壓力驟降，水幕破口即成為輻射熱穿透的通道；此外共用配管也使故障排除與定期試驗互相干擾。相對地，水源（水池、水槽）容量得以合計方式併設，因為儲水是靜態容量問題，只要總量足夠，並不影響各系統的水力獨立性。把「水源可併、配管須專」當成一組對照記憶，可同時解決本題與水源容量題。\n\n竣工加壓試驗的數值也自成一套：試驗壓力採加壓送水裝置全閉揚程的1.5倍以上，持續2小時無漏水。所謂全閉揚程是幫浦出水閥全閉時的最大揚程，代表管系在運轉中可能承受的壓力上限，取其1.5倍即為安全係數的體現。\n\n相關考點連結：同一基準常與防火牆的構造、高度與設置位置合併命題；水力方面則會延伸到摩擦損失計算、幫浦性能曲線與全閉揚程、以及各類滅火設備竣工試驗壓力與時間的橫向比較。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-law-026","下列有關防火水幕設備之水源容量規定之敘述，何者錯誤？",26,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-law-028","依可燃性高壓氣體儲存場所防護牆設置基準規定，鋼筋混凝土製防護牆，其厚度應在多少 mm 以上？",28,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-law-025","依公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，下列有關六類物品製造場所之敘述，何者正確？",25,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-law-029","下列有關簡易自動滅火設備規定之敘述，何者錯誤？",29,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-law-024","下列有關消防安全設備檢修專業機構管理辦法規定之敘述，何者錯誤？",24,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-law-030","下列有關百貨商場收容人員之計算規定之敘述，何者錯誤？",30,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-027",111,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，儲存第五類公共危險物品分級屬 A 型，其儲存量達管制量 5 倍以上未達 10 倍者且周圍設有圍牆之室內儲存場所，其應保留空地寬度應為多少公尺以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-027",110,"依各類場所消防安全設備設置標準規定，自動撒水設備得依實際情況需要選擇適當型式設置。但下列何種場所應設開放式？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-027",109,"有一 500 平方公尺地下停車場，採水霧滅火設備，依各類場所消防安全設備設置標準，其水源容量應保持多少立方公尺以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-law-027",108,"下列有關二氧化碳滅火設備各種標示規格規定之敘述，何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-fire-law-027",107,"依公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法之規定，製造、儲存或處理六類物品達管制量多少倍以上之場所，應由管理權人選任管理或監督層次以上之幹部為保安監督人，擬訂消防防災計畫，報請當地消防機關核定，並依該計畫執行六類物品保安監督相關業務？",1785123160020]