[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-law-033":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-消防法規概要-033","fire-106-1-fire-law-033",106,1,33,"建築物在五樓以上，且總樓地板面積在 3,000 平方公尺以上者，其火警自動警報設備鳴動方式之規定敘述，何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"起火層為地上二層以上時，限該樓層與其直上二層及其直下層鳴動","起火層為地面層時，限該樓層與其直上層及地下層各層鳴動","起火層為地下層時，限地面層及地下層各層鳴動","起火層為十層以上時，全樓各層應同時鳴動","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》火警自動警報設備「分區鳴動」之適用門檻與法定鳴動範圍。\n【正解理由】依《各類場所消防安全設備設置標準》第 113 條,建築物在五層以上且總樓地板面積在三千平方公尺以上者,其火警自動警報設備之鳴動方式應為分區鳴動,而法條僅列出三種鳴動情形:起火層為地上二層以上、起火層為地面層、起火層為地下層,並未以「起火層為十層以上」作為全樓同時鳴動之分類。分區鳴動的立法本意,是讓受威脅最深的樓層先行避難,避免全棟人員同時湧入梯間造成擁塞,故選 D。\n【逐項排除】\n(A) 敘述正確。起火層為地上二層以上時,限該樓層與其直上二層及其直下層鳴動;取直上二層是因熱煙上升最先威脅上方樓層,取直下層是因起火層下方人員仍需及早離開。\n(B) 敘述正確。起火層為地面層時,限該樓層與其直上層及地下層各層鳴動;地下層無外部開口、排煙不易,煙一旦下灌避難極困難,故一併納入。\n(C) 敘述正確。起火層為地下層時,限地面層及地下層各層鳴動;地下各層的避難動線都要經地面層出口,故地面層必須同時警示。\n(D) 敘述錯誤,為本題應選項。法定分區鳴動只依「起火層位於何處」分類,並無十層以上即全樓同時鳴動之條文。\n【記憶點】分區鳴動看「起火層在哪」,不看「大樓幾層高」;五層以上再加三千平方公尺,才有分區鳴動的適用。","分區鳴動制度來自高層建築火災的避難經驗。早期火警自動警報設備一響即全棟鳴動,結果每層人員同時衝入梯間,反而讓最需要先撤離的起火層與其上方樓層受阻;日本消防法規先行採取「區分鳴動」,我國《各類場所消防安全設備設置標準》亦隨之納入,以「五層以上且總樓地板面積三千平方公尺以上」作為適用門檻——樓層數代表垂直避難距離,樓地板面積代表同時避難人數,兩個條件同時成立時,一次全棟鳴動的風險才顯著。\n\n鳴動範圍的口訣可記成「上二下一、地面加地下、地下配地面」:起火層在地上二層以上者,該層＋直上二層＋直下層;起火層在地面層者,該層＋直上層＋地下層各層;起火層在地下層者,地面層＋地下層各層。三句話涵蓋全部情形,凡是題目出現「全樓同時鳴動」「直上三層」「直下二層」等變體數字,幾乎都是錯誤選項的製造方式。命題者最愛動的手腳就是把「直上二層」改成「直上一層」、把「地下層各層」改成「直下一層」,作答時先確認起火層屬於哪一類,再逐一比對層數。\n\n易混淆之處有三:其一,分區鳴動與火警分區(每一火警分區樓地板面積與邊長之限制)是兩個不同概念,前者管「響哪裡」,後者管「怎麼劃探測範圍」;其二,鳴動方式屬於火警自動警報設備的規定,與緊急廣播設備的啟動層別規定形式相近但條文各自獨立,兩者常被合併出題;其三,受信總機的手動全區鳴動能力屬設備功能要求,不是分區鳴動的法定分類之一,選項若把「可以手動全區鳴動」寫成「應全樓同時鳴動」即屬偷換。\n\n相關考點延伸:同一條文常與火警受信總機之設置場所、警鈴音壓、探測器裝置高度合併命題;高層建築物另有緊急廣播設備與火警設備連動之要求,考題亦可能以「何者非分區鳴動之情形」反向詢問。答題時先鎖定門檻條件(五層以上、三千平方公尺以上),再套三句口訣,通常一眼即可挑出唯一不合條文的敘述。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-law-032","水霧滅火設備水源，應連結加壓送水裝置。其用於防護電氣設備者，出水壓力達每平方公分多少公斤以上？",32,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-law-034","各類場所之管理權人應委託檢修專業機構或消防法第 7 條規定之人員辦理檢修，並於檢修完成後幾日內，向當地消防機關申報？",34,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-law-031","下列有關消防法施行細則第 15 條自衛消防編組規定之敘述，何者正確？",31,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-law-035","下列有關建築物消防安全設備竣工查驗程序規定之敘述，何者錯誤？",35,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-law-030","下列有關百貨商場收容人員之計算規定之敘述，何者錯誤？",30,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-law-036","下列有關各類場所消防安全設備檢修及申報作業基準行政函釋之敘述，何者錯誤？",36,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-033",111,"依消防法施行細則規定，供公眾使用建築物應遴選防火管理人並制定消防防護計畫，其相關規定下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-033",110,"依消防安全設備及必要檢修項目檢修基準規定，有關固定式泡沫滅火設備（低發泡）綜合檢查之檢查方法，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-033",109,"依各類場所消防安全設備檢修及申報作業基準之規定，各類場所之管理權人應委託檢修專業機構或消防法第 7 條規定之人員辦理檢修，並於檢修完成後多少日內，分別填具消防安全設備檢修申報表及檢附消防安全設備檢修報告書，向當地消防機關申報？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-law-033",108,"依各類場所消防安全設備檢修及申報作業基準規定，有關配線絕緣阻抗試驗合格之判定，若電壓超過 300 V 者，其絕緣電阻值至少應為多少以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-fire-law-033",107,"依各類場所消防安全設備設置標準之規定，防災中心樓地板面積應在多少平方公尺以上？",1785123160079]