[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-fire-law-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-消防法規概要-037","fire-106-1-fire-law-037",106,1,37,"下列有關消防幫浦之性能規定之敘述，何者正確？",{"A":16,"B":17,"C":18,"D":19},"全閉揚程應為性能曲線上全揚程之 150%以下","幫浦本體必須能耐最高水壓之 1.5 倍以上，且加壓 3 分鐘後，各部位仍無洩漏現象才算合格","幫浦所消耗之動力，在額定出水量，其軸動力應超過馬達之額定輸出馬力","幫浦之出水量在額定出水量之 150%時，其全揚程應達到額定出水量；性能曲線上全揚程之 85%以上","B",null,[],false,"本題考點：消防幫浦之性能規定,包含全閉揚程、耐水壓試驗、軸動力與額定出水量一五○％時之全揚程要求。\n【正解理由】依《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》所定消防幫浦性能規範,幫浦本體應能承受最高水壓之一點五倍以上,且在加壓三分鐘後各部位均無洩漏現象,始屬合格;此項耐水壓試驗係確認幫浦殼體、密封與接合部在超越運轉最高壓力狀態下的結構完整性,故選 B。\n【逐項排除】\n(A) 敘述錯誤。全閉揚程(出水量為零時之揚程)應在性能曲線上額定出水量對應全揚程之一四○％以下,寫成一五○％以下即放寬了限制,與規定不符。\n(B) 敘述正確。耐水壓為最高水壓之一點五倍以上、加壓三分鐘、各部位無洩漏,三個要件齊備才算合格,本選項完整敘明。\n(C) 敘述錯誤。幫浦在額定出水量時所消耗之軸動力,不得超過馬達之額定輸出馬力,否則馬達長期過載將燒損;本選項將「不得超過」寫成「應超過」,語意完全相反。\n(D) 敘述錯誤。出水量在額定出水量之一五○％時,其全揚程應達到額定出水量時性能曲線上全揚程之六五％以上,而非八五％以上;此要件是確保大流量時仍有足夠壓力送水。\n【記憶點】幫浦三個數字:全閉一四○％以下、大流量一五○％時揚程六五％以上、耐壓一點五倍撐三分鐘。","消防幫浦的性能規範,本質上是在管制一條性能曲線的形狀。橫軸為出水量、縱軸為全揚程,曲線最左端(出水量為零)即全閉揚程,規定其不得高於額定點全揚程之一四○％,目的在避免關閉出水時壓力飆升而危及配管、閥件與接頭;曲線右端要求出水量達額定值一五○％時,全揚程仍應維持額定點之六五％以上,目的在確保多個出水口同時使用、流量放大時,末端仍有足夠放水壓力。兩個限制一左一右,把曲線夾在合理的區間內,不致過陡或過平。\n\n單位換算是這一系列題目的基本功:1 kgf\u002Fcm² 約等於 10 公尺水頭,約等於 0.098 MPa;因此常見的 1.7 kgf\u002Fcm² 放水壓力約相當於 17 公尺水頭。全揚程的組成則為實揚程加上配管摩擦損失揚程,再加上瞄子或撒水頭所需之放水壓力換算水頭,這也是《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》名稱中「配管摩擦損失計算」的由來。軸動力(幫浦軸端所需之機械功率)與馬達額定輸出的關係則是另一組:軸動力與流量、揚程成正比,與幫浦效率成反比,故規定額定出水量時的軸動力不得超過馬達額定輸出,並要求馬達具備適當的傳動容許係數以留餘裕。\n\n數值口訣可記為「一四○、六五、一點五、三分鐘」:全閉揚程一四○％以下、一五○％流量時揚程六五％以上、耐水壓一點五倍、加壓維持三分鐘。命題最常見的手法就是把一四○改成一五○、把六五改成八五,或把「不得超過馬達額定輸出」反寫成「應超過」,只要把四個數字與一個方向性要件記牢,即可逐項排除。\n\n易混淆概念:全閉揚程與額定揚程不同,前者是零流量點、後者是設計點;幫浦效率與馬達效率也是兩件事,前者屬水力性能、後者屬電氣性能。相關考點延伸:同一基準另規範呼水裝置、防止水溫上升用排放裝置、性能試驗裝置、啟動用水壓開關裝置與底閥等附屬設備,常與室內消防栓及自動撒水設備的水源容量、放水壓力範圍合併命題,建議把幫浦本體性能與附屬裝置功能各做一張表交叉複習。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-law-036","下列有關各類場所消防安全設備檢修及申報作業基準行政函釋之敘述，何者錯誤？",36,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-law-038","下列有關建築技術規則建築設計施工編建築技術用語規定之敘述，何者錯誤？",38,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-law-035","下列有關建築物消防安全設備竣工查驗程序規定之敘述，何者錯誤？",35,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-law-039","依據建築技術規則建築設計施工編規定，下列用語定義何者正確？",39,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-law-034","各類場所之管理權人應委託檢修專業機構或消防法第 7 條規定之人員辦理檢修，並於檢修完成後幾日內，向當地消防機關申報？",34,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-fire-law-040","依公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，下列有關「六類物品製造場所，其外牆或相當於該外牆之設施外側，與廠區外鄰近場所之安全距離」之敘述，何者錯誤？",40,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-037",111,"依據乾粉滅火設備各種標示規格規定，其標示規格為長 480 mm 以上，寬 270 mm 以上，黃底黑字，每字大小為 25 mm×25 mm 以上，係屬下列何者？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-037",110,"有關二氧化碳滅火設備使用之各種標示規格，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-037",109,"依建築技術規則建築設計施工編之定義，每層陽臺面積之和，以不超過建築面積多少為限？其未達 8 平方公尺者，得建築 8 平方公尺。",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-law-037",108,"依避難器具支固器具及固定部之結構、強度計算及施工方法規定，裝置避難器具之固定部，應能承受承載荷重與附加荷重之和。若避難器具為緩降機，其承載荷重應為最大使用人數乘以多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-fire-law-037",107,"依防火牆及防火水幕設置基準之規定，有一儲槽其水平剖面最大半徑為 5 公尺，內裝有公共危險物品，該公共危險物品之閃火點為攝氏八十度，則假想火面高度為多少公尺？",1785123160115]