[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-106-1-fire-science-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"火災學概要","fire-science","火災學 · Fire Science","火災學",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-火災學概要-038","fire-106-1-fire-science-038",106,1,38,"一般研究建築物室內火災行為特性時，將室內所產生的煙與熱，區分成上層區（熱區）及下層區（冷區），進而研究的模式稱為：",{"A":16,"B":17,"C":18,"D":19},"場模式（field model）","區域模式（zone model）","控制體積模式（control volume model）","網路模式（network model）","B",null,[],false,"本題考點：火災模擬計算模式的分類,考的是把室內空間簡化為上下兩層來求解的模式名稱。\n【正解理由】依火災工程學對數值模式的分類,將起火室的空間假設為性質均勻的「上部熱煙層」與「下部冷空氣層」兩個控制區,再以質量守恆與能量守恆方程式求解各層溫度、煙層厚度與界面高度者,稱為區域模式(zone model),代表軟體如 CFAST、BRI2;其最大特徵就是題幹所描述的上下兩區劃分,故選 B。\n【逐項排除】\n(A) 場模式(field model)是把空間切成數十萬個網格,逐格解流體力學守恆方程式的計算流體力學方法(如 FDS),不做兩層假設,精度高但耗時,與題意不符。\n(B) 正是把煙與熱分為上層熱區、下層冷區的雙區間模式,與題幹描述完全一致,為正確答案。\n(C) 控制體積模式是流體力學中通用的分析手法名稱,泛指對任一選定體積作守恆分析,並非火災學中「上下兩層」這一特定模式的專有名稱。\n(D) 網路模式(network model)把每個房間視為一個節點、以開口為流路連結,用於全棟建築的煙流與壓力分布分析,著眼於房間之間而非單一房間內的上下分層。\n【記憶點】上下兩層叫區域、逐格計算叫場、房間串成節點叫網路。","火災模擬模式的三分法是火災學必考的架構題。網路模式(network model)精度最粗,把每個房間簡化成單一節點,只算房間之間的壓力與流量,適合大範圍煙控與加壓系統評估;區域模式(zone model)居中,單一房間分成上下兩層,以少量常微分方程式描述煙層下降、天花板噴流與門口流出量,在一般電腦上數秒到數分鐘即可算完,是性能式設計與避難時間評估最常用的工具;場模式(field model \u002F CFD)最細,以有限體積法離散納維－斯托克斯方程式,可解出每一點的速度、溫度與煙濃度場,適合幾何複雜、大空間或需要細部流場的案例,但計算成本高。\n\n區域模式之所以合理,來自實驗觀察:室內火災形成的煙羽流(plume)撞擊天花板後沿頂部擴散,形成溫度均勻的熱煙層,與下方相對乾淨的冷空氣層之間界面清楚,這個兩層結構在閃燃前相當穩定。因此其核心方程式包含質量守恆(煙層質量增量 = 煙羽流捲吸量 − 開口流出量)、能量守恆(熱釋放率扣除牆面熱損失與開口散熱),搭配 Zukoski 或 McCaffrey 的煙羽流捲吸公式求解。\n\n侷限也是考點:當火災接近閃燃、上下層溫差消失,或空間極為狹長、挑高中庭導致煙層界面不明顯時,兩層假設就會失真,此時應改用場模式;反之若只關心煙是否會經由管道間、樓梯間串樓,網路模式反而更有效率。\n\n延伸連結:區域模式的輸出常直接餵給性能式避難設計,計算可用避難時間(ASET)與必要避難時間(RSET)的比較,ASET 通常以煙層下降至 1.8 m 或能見度、溫度、毒性氣體達到危險判定基準的時刻為準,這組判定值與本題屬同一章節的高頻考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-fire-science-037","已知門扇高 2.13 m、寬 0.91 m，把手安置在靠近邊緣 0.076 m 處，兩邊壓為 75 Pa，壓力係數 Kd=0.91，克服門自鎖力為 53 N，求最少需多少力才能打開該門？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-fire-science-039","依據日本建設省建築研究所的模型實驗結果，影響閃燃時間（F.O.T.）最大的因素，不包括下列何者？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-fire-science-036","在一大氣壓力狀態下，假設空氣中氧（O2）之重量占整體空氣的 23%，試問 1 kg 之硫（S）完全燃燒，約需多少公斤之空氣？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-fire-science-040","下列何者會造成局部電阻值增加，而成為火災發生的原因？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-fire-science-035","五層樓的建築物，每層設有特別安全梯，樓梯採正壓且加壓壓力為 35 Pa，每層特別安全梯之前室採正壓且加壓壓力為 25 Pa，居室則未設煙控設計，居室避難到特別安全梯，需經過設有煙控之前室，且空間均為密閉構造，唯一開口為安全門，流動面積為 0.01 m2，試問每一排煙室設加壓煙控時，應送的風量為多少？",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-107-1-fire-science-001","在火場中會因吸入下列何種氣體，導致阻礙紅血球輸氧功能而造成窒息死亡？",107,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-science-038",111,"在長 10 m、寬 8 m、高 3 m 的居室燃燒 1 kg 的乳膠枕頭，其 Dm=0.65 m2\u002Fg，估算此火場出口標示燈能見度？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-science-038",110,"常見泡沫滅火藥劑含有界面活性劑成分，請問下列何者不是泡沫滅火藥劑滅火時界面活性劑的主要作用？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-science-038",109,"在橡膠中混入碳黑所製成的產品可防止人體帶靜電，其防止靜電發生的方法為？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-science-038",108,"可燃物不藉由火焰或電器火花引起燃燒，在大氣中僅因受熱而引發燃燒的最低溫度稱為：",{"webId":70,"year":51,"stem":71,"number":13},"fire-107-1-fire-science-038","以下那一現象為燃燒完全度高之火災特徵？",1785123164290]