[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-006":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-006","fire-106-1-water-chemical-006",106,1,6,"全區放射二氧化碳滅火設備進行綜合檢查時，如為低壓式儲存系統，在放射試驗時需放射多少藥劑量？",{"A":16,"B":17,"C":18,"D":19},"68 公升二氧化碳 5 瓶以上","放射區域所設滅火藥劑量之 5%以上","放射區域所設滅火藥劑量五分之一以上","40 公升氮氣 5 瓶以上","D",null,[],false,"本題考點：《消防安全設備檢修及申報作業基準》中，全區放射二氧化碳滅火設備綜合檢查（放射試驗）所使用的試驗用氣體種類與數量，且高壓式與低壓式的規定並不相同。\n【正解理由】依《消防安全設備檢修及申報作業基準》有關二氧化碳滅火設備綜合檢查之規定，放射試驗係就任一放射區域實施，並非把該區實際所需的滅火藥劑量整批放掉，而是以規定數量之試驗用氣體確認啟動裝置、選擇閥、容器閥開放裝置、配管與噴頭之動作及氣體是否確實到達防護區域。其中高壓式儲存系統係以規定瓶數之二氧化碳容器實施，低壓式儲存系統則規定使用 40 公升氮氣 5 瓶以上作為試驗用氣體，故選 D。\n【逐項排除】\n(A) 68 公升二氧化碳 5 瓶以上，這是高壓式儲存系統放射試驗的規定，本題問的是低壓式，主體套錯。\n(B) 放射區域所設滅火藥劑量之 5%以上，此比例並非低壓式放射試驗的法定數量，且檢修基準的放射試驗量並非以百分比方式規範低壓式。\n(C) 放射區域所設滅火藥劑量五分之一以上，把整區藥劑量的比例當作試驗量，數量過大且與檢修基準所定之試驗用氣體規格不符。\n(D) 正確：低壓式儲存系統之放射試驗，規定以 40 公升氮氣 5 瓶以上實施。\n【記憶點】高壓式放二氧化碳 68 公升 5 瓶，低壓式改放氮氣 40 公升 5 瓶。","綜合檢查是檢修申報三段（外觀檢查、性能檢查、綜合檢查）中最後也最關鍵的一段，目的在確認整套系統從探測、啟動、遲延、警報到藥劑放射的連動是否一氣呵成。二氧化碳屬於窒息性氣體，真的整區放射一次不僅藥劑成本高昂、再充填曠日費時，更有人員滯留窒息的重大風險，因此檢修基準設計成以少量試驗用氣體模擬放射，既能驗證流路暢通與各閥件動作，又不必真正把防護區域灌滿高濃度二氧化碳，這是理解本題規定的核心立法思維。\n\n低壓式之所以改用氮氣，是因為低壓式儲存容器是以冷凍機組維持在約零下 18 度、約 21 kgf\u002Fcm² 的低溫加壓狀態，容器為大型儲槽而非成排鋼瓶，無法像高壓式那樣單獨挑幾支瓶子出來試放；改以外接氮氣瓶充當試驗介質，可在不動用主儲槽存量、不影響低溫平衡的前提下完成流路與動作確認。氮氣本身為惰性、不助燃、無腐蝕性，且與二氧化碳同為壓縮氣體，流動特性足以檢驗選擇閥與噴頭是否阻塞。\n\n數值可整理成一組對照記憶：高壓式—二氧化碳容器 68 公升、5 瓶以上；低壓式—氮氣容器 40 公升、5 瓶以上。兩者「5 瓶以上」相同，差在氣體種類與容器容量，命題者最常把這四個數字交叉打散成選項，作答時先鎖定題目問的是高壓式還是低壓式，再選對氣體，正確率就會大幅提高。\n\n放射試驗的判定要點也常延伸命題：應確認警報裝置確實鳴動、遲延裝置動作時間符合規定、開口部自動關閉裝置確實作動、通風換氣裝置停止、放射表示燈亮起，以及氣體是否確實由噴頭放出且無明顯洩漏。實施前後尚須確認防護區域內無人滯留、出入口設有標示，這些都源自二氧化碳系統誤放造成人員傷亡的歷史事故教訓，也是同一條文群的高頻考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-005","某一鍋爐房之長寬高分別為 8 m、5 m 及 4 m，若設置全區放射 CO2 滅火設備，其所有開口皆可在放射前自動關閉，試問所需 CO2 藥劑量至少應為多少公斤？",5,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-007","依各類場所消防安全設備設置標準，二氧化碳滅火設備之藥劑放射時間，下列何者正確？",7,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-004","依滅火器認可基準，大型滅火器充填乾粉時，滅火藥劑量需在多少公斤以上？",4,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-008","乾粉滅火設備進行性能檢查時，滅火藥劑檢查注意事項中，溫度超過Ｘ℃以上，濕度超過Ｙ%以上時，應暫停檢查，Ｘ及Ｙ分別為：",8,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-003","有關滅火器設置間距之規定，下列何者錯誤？",3,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-009","如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",9,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-006",111,"消防幫浦之防止水溫上升用排放裝置，防止水溫上升用之排水管內之流水量，當幫浦在全閉狀態下連續運轉時，不使幫浦內部水溫，升高至攝氏多少度以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-006",110,"有關撒水頭位置裝置之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-006",109,"消防幫浦設置呼水槽時，防止水溫上升用排放裝置之標稱口徑不得小於多少毫米？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-006",108,"使用密閉式撒水頭之自動撒水設備末端之查驗閥，下列設置規定何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-006",107,"泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",1785123168239]