[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-011","fire-106-1-water-chemical-011",106,1,11,"鹵化烴滅火設備進行性能檢查時，控制裝置之遲延裝置檢查項目，於操作啟動按鈕後至容器閥開放裝置動作，其所需時間應為：",{"A":16,"B":17,"C":18,"D":19},"10 秒以內","10 秒以上","15 秒以上","20 秒以上","D",null,[],false,"本題考點：《消防安全設備檢修及申報作業基準》中鹵化烴滅火設備性能檢查，控制裝置之遲延裝置所需動作時間。\n【正解理由】全區放射方式之氣體系滅火設備，於探測器或手動啟動裝置動作後，必須先鳴動音響警報並保留人員避難的時間，才可開放容器閥放射藥劑，此段緩衝即由遲延裝置擔任。依《消防安全設備檢修及申報作業基準》有關鹵化烴滅火設備性能檢查之控制裝置檢查項目，遲延裝置應確認自操作啟動按鈕後至容器閥開放裝置動作，所需時間在 20 秒以上，故選 D。\n【逐項排除】\n(A) 10 秒以內，方向完全相反：遲延裝置的規範是「不得短於」某時間，寫成上限即失去保護避難時間的意義。\n(B) 10 秒以上，時間過短，不足以完成警報鳴動與人員退出防護區域，未達基準所定秒數。\n(C) 15 秒以上，接近但仍低於基準要求，是典型的近似值干擾。\n(D) 正確：自按下啟動按鈕至容器閥開放裝置動作，應在 20 秒以上。\n【記憶點】遲延裝置至少 20 秒，先響警報再放藥劑。","遲延裝置是氣體系滅火設備的人命保護核心。二氧化碳、鹵化烴等藥劑在防護區域內建立設計濃度時，會使該空間短時間內不適合人員停留；若探測器一動作就立即放射，室內人員將來不及撤離。因此法規與檢修基準把「先警報、後放射」的時序寫死，並用遲延裝置確保中間留有足以離開的時間。20 秒這個數字是以一般防護區域內人員自任一位置移動至出入口所需時間為考量而訂，屬於下限規定——檢查時若量得時間短於 20 秒，即屬不良，須調整。\n\n與遲延裝置連動的還有一整串安全機構：音響警報裝置應在遲延期間持續鳴動，且防護區域內各處均能聽聞；出入口應設放射表示燈，於藥劑放射時亮起，警示外部人員不得進入；手動啟動裝置應設於防護區域外便於操作處，並設自動、手動切換裝置與明顯標示；開口部自動關閉裝置與通風換氣裝置停止機構亦應在放射前完成動作。這些項目在綜合檢查時會一併確認，常被整合成複選型考題。\n\n鹵化烴滅火設備本身的背景也值得一提：傳統海龍（鹵化烷）因破壞臭氧層，依蒙特婁議定書逐步禁用，其後以 HFC 系、FK 系等鹵化烴藥劑作為替代，滅火機制同樣以化學抑制為主並兼具部分冷卻效果，設計濃度、藥劑量與放射時間規定因藥劑種類而異，與二氧化碳系統的計算方式不可互換。\n\n易混淆點整理：遲延裝置談的是「啟動到放射」的時間，屬安全緩衝；放射時間談的是「開始放射到放射完畢」的時間，屬滅火效能；濃度維持時間則是放射後濃度須維持的時間，屬深部火災考量。三個時間概念分屬不同階段，考題常刻意把它們的數值互相調換，作答時先確認問的是哪一段時間軸，再對應數值。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-010","一汽車修理廠欲採用移動式乾粉滅火設備，則其外牆開口面積（常時開放部分）須符合下列那一規定？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-012","簡易自動滅火設備進行性能檢查時，其蓄壓式滅火藥劑量應與標示重量差異在何範圍以內？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-009","如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-013","有關室內消防栓之放水壓力，下列何者錯誤？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-008","乾粉滅火設備進行性能檢查時，滅火藥劑檢查注意事項中，溫度超過Ｘ℃以上，濕度超過Ｙ%以上時，應暫停檢查，Ｘ及Ｙ分別為：",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-014","達顯著滅火困難之公共危險物品室外儲存場所，設置室外消防栓設備，其緊急電源應使用發電機設備或蓄電池設備，供電容量應供其有效動作至少多久以上？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-011",111,"依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-011",110,"室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-011",109,"乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-011",108,"二氧化碳滅火設備使用氣體啟動者，啟動用氣體容器之內容積應有 1 公升以上，其所儲存之二氧化碳重量在 0.6 公斤以上，且其充填比應在多少以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-011",107,"加壓式乾粉滅火設備，於啟動裝置動作後，為使儲存容器壓力達設定壓力始開啟放出閥，應設置何種裝置？",1785123168283]