[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-016":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-016","fire-106-1-water-chemical-016",106,1,16,"自動撒水設備竣工時進行加壓試驗，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"試驗壓力不得小於加壓送水裝置額定揚程 1.5 倍以上之水壓","水壓試驗壓力以繼續維持 1 小時無漏水現象為合格","密閉乾式管系應併行空氣壓試驗，應使空氣壓力達到 0.28 MPa 之標準","密閉乾式管系應併行空氣壓試驗，壓力持續 24 小時，漏氣減壓量應在 0.1MPa 以下","C",null,[],false,"本題考點：自動撒水設備竣工時之配管耐壓試驗規定,包含水壓試驗的壓力基準、維持時間,以及密閉乾式管系併行空氣壓試驗的壓力與漏氣容許值。\n【正解理由】依《各類場所消防安全設備設置標準》關於撒水設備配管試驗之規定,密閉乾式管系除水壓試驗外,應併行空氣壓試驗,使空氣壓力達到 0.28 MPa(2.8 kgf\u002Fcm²)之標準,並持續 24 小時,漏氣減壓量應在 0.01 MPa 以下方為合格。C 選項的空氣壓力數值與法定標準相符,故選 C。\n【逐項排除】\n(A) 錯在基準揚程取錯,水壓試驗壓力係以加壓送水裝置「全閉揚程」1.5 倍以上之水壓為準,而非額定揚程,全閉揚程高於額定揚程,取額定會低估試驗強度。\n(B) 錯在維持時間,水壓試驗須繼續維持二小時無漏水現象才算合格,一小時不足以暴露微量滲漏。\n(C) 正確,密閉乾式管系空氣壓試驗的法定壓力就是 0.28 MPa,此值為判斷乾式管系氣密性的門檻。\n(D) 前段的 24 小時持續時間正確,但漏氣減壓量寫成 0.1 MPa 過寬,法定容許值為 0.01 MPa 以下,差了一個數量級。\n【記憶點】乾式管系記「水壓 1.5 倍全閉揚程撐 2 小時、空壓 0.28 MPa 撐 24 小時掉不超過 0.01 MPa」。","竣工耐壓試驗的存在,是因為撒水設備平時不動作,配管的缺陷唯有靠試驗才會現形。水壓試驗以「全閉揚程的 1.5 倍」為基準,理由在於幫浦在出水閥全關時揚程最高,管路承受的靜壓也最大;若以額定揚程計算,試驗壓力會低於系統實際可能出現的最高壓力,等於沒有安全裕度。1.5 倍則是常見的耐壓安全係數,涵蓋水鎚等瞬間壓力波動。維持二小時而非數分鐘,是要讓螺紋接頭、法蘭墊片的緩慢滲漏有時間顯現。\n\n乾式管系為何要額外做空氣壓試驗?密閉乾式撒水設備平時管內充填壓縮空氣而非水,靠氣壓壓住乾式閥;一旦撒水頭因火熱動作,管內空氣洩出、氣壓下降,乾式閥才開啟放水。若管路氣密性不良,平時就會緩慢漏氣,導致空氣壓縮機頻繁啟動,甚至誤動作放水。因此法規要求充氣至 0.28 MPa 並靜置 24 小時,漏氣減壓量不得超過 0.01 MPa,亦即 24 小時內壓力衰減不到 3.6%。\n\n單位換算是本題型的隱藏陷阱:1 MPa ≈ 10.2 kgf\u002Fcm² ≈ 102 公尺水頭,所以 0.28 MPa 約 2.85 kgf\u002Fcm²,0.01 MPa 約 0.1 kgf\u002Fcm²。題目可能任意改用兩套單位出題,換算不熟就會被 0.1 與 0.01 這種一位小數之差騙過去。\n\n易混淆概念對照:密閉濕式管內常時充水,動作最快,適用不會結凍的一般場所;密閉乾式管內充氣,適用寒冷地區或不能容忍漏水的空間,但放水延遲;預動式則兼採探測器與撒水頭雙重動作,可降低誤放水損失。這三種的竣工試驗要求並不相同——只有乾式(及預動式的乾式部分)需要空氣壓試驗,濕式僅做水壓試驗,這正是命題者常設的分辨點。\n\n同條文的延伸考法包括問配管材質與管徑、問流水檢知裝置每一樓層設置的規定,以及問竣工時撒水頭放水壓力與放水量的下限(1 kgf\u002Fcm² 以上、80 公升\u002F分以上)。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-015","某一高度危險工作場所，其建築物外面設有 4 具室外消防栓，則其水源容量至少應為多少？",15,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-017","有關撒水頭之設置，下列敘述何者錯誤？",17,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-014","達顯著滅火困難之公共危險物品室外儲存場所，設置室外消防栓設備，其緊急電源應使用發電機設備或蓄電池設備，供電容量應供其有效動作至少多久以上？",14,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-018","公共危險物品等場所設置自動撒水設備時，使用密閉式撒水頭其水源容量，應在設置 X 個撒水頭繼續放水 Y 分鐘之水量以上，其中 X、Y 分別為：",18,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-013","有關室內消防栓之放水壓力，下列何者錯誤？",13,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-019","進行密閉濕式撒水設備綜合檢查時，末端查驗管之放水壓力應在那個範圍？",19,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-016",111,"乾粉滅火設備進行性能檢查時，關於滅火藥劑量之敘述，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-016",110,"某觀光飯店餐廳的廚房面積 750 平方公尺，其使用火源處所設置滅火器核算之最低滅火效能值應為多少？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-016",109,"製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-016",108,"依各類場所消防安全設備檢修及申報作業基準，公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之室內消防栓，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。則 X+Y 為若干？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-016",107,"有關乾粉滅火系統之放射時間，下列敘述何者正確？",1785123168337]