[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-017","fire-106-1-water-chemical-017",106,1,17,"有關撒水頭之設置，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"設於電影院放映室之撒水頭，任一點至撒水頭之水平距離在 1.7 公尺以下","在公共危險物品等場所設置自動撒水設備，防護對象任一點至撒水頭之水平距離在 1.7 公尺以下","高架儲存倉庫中，設於貨架之撒水頭，任一點至撒水頭之水平距離在 2.5 公尺以下","一防火構造之餐廳設置快速反應型撒水頭（第一種感度），各層任一點至撒水頭之水平距離在 2.3 公尺以下","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 47 條密閉式撒水頭之水平距離規定,以及快速反應型撒水頭在防火構造建築物的放寬值。\n【正解理由】依《各類場所消防安全設備設置標準》第 47 條,快速反應型撒水頭(小區劃型除外)各層任一點至撒水頭之水平距離,一般為 2.3 公尺以下,而建築物為防火構造者放寬為 2.6 公尺以下。D 選項將防火構造餐廳的快速反應型撒水頭寫成 2.3 公尺,誤用了非防火構造的數值,敘述與條文不符;題目問「何者錯誤」,故選 D。\n【逐項排除】\n(A) 正確,電影院放映室屬高感度需求空間,條文明定任一點至撒水頭水平距離在 1.7 公尺以下。\n(B) 正確,公共危險物品等場所設自動撒水設備時,防護對象任一點至撒水頭之水平距離同為 1.7 公尺以下,加密設置以因應高火載量。\n(C) 正確,高架儲存倉庫設於貨架之撒水頭,任一點至撒水頭之水平距離為 2.5 公尺以下。\n(D) 錯誤所在,防火構造建築物採快速反應型撒水頭時,水平距離應為 2.6 公尺以下,選項少算 0.3 公尺,把防火構造的放寬效果漏掉了。\n【記憶點】一般 2.1、防火構造 2.3;換成快速反應型整組加 0.3,變成 2.3 與 2.6。","第 47 條的水平距離,本質是撒水頭防護半徑的規範化。撒水頭撒水傘的有效撒布範圍近似圓形,任一點到最近撒水頭的水平距離越短,水量密度越高、動作越及時。條文因此依三個變數調整:建築構造(是否防火構造)、撒水頭型式(標準反應型或快速反應型)、場所危險度(放映室、公共危險物品場所、高架倉庫等特殊空間)。\n\n為什麼防火構造可以放寬?防火構造的樑柱牆板具一定時效的耐火性能,火勢在區劃內延燒速度受限,撒水頭有較充裕的動作時間,故容許防護半徑略大,由 2.1 提高至 2.3 公尺。快速反應型撒水頭的感熱元件熱慣性(RTI)遠低於標準型,動作時間可大幅縮短,等於用「早動作」換取「大間距」,因此整組再往上加 0.3 公尺,成為 2.3(一般)與 2.6(防火構造)。這種「加 0.3」的規律非常好記,也是本題最有效的解法。\n\n特殊場所的 1.7 公尺則是另一套邏輯。放映室早年使用硝酸纖維膠片,燃燒極為猛烈,是歷史火災事故留下的規範;公共危險物品場所則因儲存易燃液體,火勢成長率高,兩者都要求高密度配置。高架儲存倉庫的 2.5 公尺針對的是貨架內部撒水頭,重點在於貨架各層之間的縱向延燒,除水平距離外還另有貨架高度每隔一定距離加設撒水頭的規定。\n\n數值對照可整理成一張表:一般場所 2.1、防火構造 2.3、快速反應型 2.3、快速反應型+防火構造 2.6、小區劃型 2.6、高架倉庫貨架 2.5、放映室與公共危險物品場所 1.7。背表時建議由小到大排,1.7 最嚴、2.6 最寬,中間依構造與感度遞增。\n\n易混淆的是「小區劃型撒水頭」,它同屬快速反應型家族,但另有天花板面積與側牆設置的特別規定,不能直接套用一般快速反應型的數值。同條文的延伸考點還包括撒水頭與樑、與側牆的距離、迴水板下方淨空要求,以及免設撒水頭的處所列舉。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-016","自動撒水設備竣工時進行加壓試驗，下列何者正確？",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-018","公共危險物品等場所設置自動撒水設備時，使用密閉式撒水頭其水源容量，應在設置 X 個撒水頭繼續放水 Y 分鐘之水量以上，其中 X、Y 分別為：",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-015","某一高度危險工作場所，其建築物外面設有 4 具室外消防栓，則其水源容量至少應為多少？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-019","進行密閉濕式撒水設備綜合檢查時，末端查驗管之放水壓力應在那個範圍？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-014","達顯著滅火困難之公共危險物品室外儲存場所，設置室外消防栓設備，其緊急電源應使用發電機設備或蓄電池設備，供電容量應供其有效動作至少多久以上？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-020","水霧滅火設備之加壓送水裝置使用消防幫浦時，其出水量及出水壓力，下列敘述何者錯誤？",20,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-017",111,"惰性氣體滅火設備進行綜合檢查時，採低壓式者進行放射試驗時，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之多少以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-017",110,"密閉乾式或預動式之流水檢知裝置二次側配管，為有效排水，支管每 10 公尺傾斜 A 公分，主管每 10 公尺傾斜 B 公分。下列 A，B 何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-017",109,"某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-017",108,"依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備之第一種消防栓水帶及瞄子檢查方法，製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。則 X+Y 為若干？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-017",107,"一電氣設備室長寬高分別為 12 m、8 m 及 4 m，若採二氧化碳全區放射滅火設備防護，藥劑放射後採機械排放，則其排風機之風量應為每分鐘多少立方公尺？",1785123168345]