[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-019","fire-106-1-water-chemical-019",106,1,19,"進行密閉濕式撒水設備綜合檢查時，末端查驗管之放水壓力應在那個範圍？",{"A":16,"B":17,"C":18,"D":19},"1 kgf\u002Fcm２以上 6 kgf\u002Fcm２以下 ２ ２","1 kgf\u002Fcm 以上 7 kgf\u002Fcm 以下 ２ ２ ２ ２","1.7 kgf\u002Fcm 以上 7 kgf\u002Fcm 以下","1 kgf\u002Fcm 以上 10 kgf\u002Fcm 以下","D",null,[],false,"本題考點：《消防安全設備檢修及申報作業基準》中,密閉濕式自動撒水設備綜合檢查時,末端查驗管放水壓力的合格判定範圍。\n【正解理由】依《消防安全設備檢修及申報作業基準》關於自動撒水設備綜合檢查之規定,密閉濕式系統應打開末端查驗閥放水,其放水壓力應在 1 kgf\u002Fcm² 以上、10 kgf\u002Fcm² 以下,並確認流水檢知裝置動作、警報發出正常。下限 1 kgf\u002Fcm² 是確保最不利點撒水頭仍能形成有效撒水型態的最低壓力,上限 10 kgf\u002Fcm² 則是避免壓力過高造成撒水破碎、配管與接頭受損,故選 D。\n【逐項排除】\n(A) 下限 1 kgf\u002Fcm² 正確,但上限寫成 6 kgf\u002Fcm² 過於嚴苛,會把仍屬合格的高壓系統誤判為不合格。\n(B) 同樣把上限壓低為 7 kgf\u002Fcm²,7 kgf\u002Fcm² 是室內消防栓瞄子放水壓力的上限值,誤植到撒水設備綜合檢查。\n(C) 下限與上限兩處都錯,1.7 kgf\u002Fcm² 並非撒水設備的壓力門檻,7 kgf\u002Fcm² 的上限亦如 (B) 所述取自其他設備。\n(D) 正確,1 kgf\u002Fcm² 以上、10 kgf\u002Fcm² 以下即為末端查驗管放水壓力的法定合格範圍。\n【記憶點】末端查驗管壓力範圍記「一到十」,下限保撒水效果、上限保配管安全。","末端查驗管(末端試驗閥)裝設在密閉濕式撒水設備配管系統水力上最不利的末端,作用是模擬一個撒水頭動作時的放水情形。它配有與該系統撒水頭相同放水性能的試驗用限流孔,打開閥門後放水,可同時驗證三件事:最不利點壓力是否足夠、流水檢知裝置是否動作、受信總機是否收到警報並顯示正確樓層。這是綜合檢查中最能一次驗證整條水路與電路連動的項目。\n\n下限 1 kgf\u002Fcm² 的由來與撒水頭的放水量公式有關。標準撒水頭放水量近似 Q = K√P,K 值約 80,壓力以 kgf\u002Fcm² 代入時,P = 1 kgf\u002Fcm² 可得 Q = 80 × √1 = 80 公升\u002F分,恰好等於設置標準要求的放水量下限。換言之,1 kgf\u002Fcm² 不是隨意訂的數字,而是反推自「每一撒水頭放水量 80 公升\u002F分以上」這個更根本的要求。上限 10 kgf\u002Fcm² 約當 1 MPa 或 100 公尺水頭,超過此值時水滴過度霧化、動量不足,反而穿不透火羽流,同時配管接頭長期承壓也有破損風險。\n\n單位換算務必熟練:1 kgf\u002Fcm² ≈ 0.098 MPa ≈ 10 公尺水頭。因此 1 至 10 kgf\u002Fcm² 相當於約 0.1 至 1.0 MPa,若題目改以 MPa 出題,答案形貌完全不同但實質相同。\n\n容易混淆的鄰近數值有一整組:室內消防栓瞄子放水壓力 1.7 kgf\u002Fcm² 以上、7 kgf\u002Fcm² 以下;室外消防栓 2.5 kgf\u002Fcm² 以上、7 kgf\u002Fcm² 以下;水霧噴頭 2.7 kgf\u002Fcm² 以上(防護電氣設備者 3.5 kgf\u002Fcm² 以上);撒水頭 1 kgf\u002Fcm² 以上。本題的 (B)(C) 兩個誘答正是把消防栓那一組的 1.7 與 7 搬過來,只要把「撒水頭走 1 到 10、消防栓走 1.7\u002F2.5 到 7」這兩條線分清楚,就能一眼排除。\n\n同一檢修項目的延伸考法包括:綜合檢查時放水量的判定、流水檢知裝置警報延遲時間、密閉乾式與預動式系統改由末端查驗閥確認放水時間(需在一定時間內出水)的規定,以及外觀、性能、綜合三階段檢查的分工。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-018","公共危險物品等場所設置自動撒水設備時，使用密閉式撒水頭其水源容量，應在設置 X 個撒水頭繼續放水 Y 分鐘之水量以上，其中 X、Y 分別為：",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-020","水霧滅火設備之加壓送水裝置使用消防幫浦時，其出水量及出水壓力，下列敘述何者錯誤？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-017","有關撒水頭之設置，下列敘述何者錯誤？",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-021","裝置水霧滅火設備之室內停車空間，其排水設備應符合之規定，下列何者錯誤？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-016","自動撒水設備竣工時進行加壓試驗，下列何者正確？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-022","下列那一泡沫滅火設備之泡沫濃度，不符泡沫原液與水混合使用濃度之規定？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-019",111,"下列有關滅火器性能檢查之敘述，何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-019",110,"依各類場所消防安全設備設置標準，應設置室內消防栓設備之場所，下列規定何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-019",109,"某室內停車空間設置低發泡固定式泡沫滅火設備，每次檢修作業時，應選擇全部放射區域數多少比例以上之放射區域進行逐區放水試驗，測其放射分布及放射壓力？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-019",108,"依各類場所消防安全設備檢修及申報作業基準，有關高壓式二氧化碳滅火藥劑儲存容器之滅火藥劑量檢查方法之注意事項中，鈷 60 有效使用年限約為多少年，如已超過時，應即時連絡專業單位處理或更換？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-019",107,"可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽之滅火器，每具滅火器對普通火災應具有 X 個以上之滅火效能值，對油類火災應具有 Y 個以上之滅火效能值，其中 X、Y 分別為下列何者？",1785123168365]