[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-021":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-021","fire-106-1-water-chemical-021",106,1,21,"裝置水霧滅火設備之室內停車空間，其排水設備應符合之規定，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"車輛停駐場所地面作 5%以上之坡度","車輛停駐場所，除面臨車道部分外，應設深 10 公分寬 10 公分以上之地區境界溝，並與排水溝連通","滅火坑具備油水分離裝置，並設於火災不易殃及之處所","車道之中央或二側設置排水溝","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》裝置水霧滅火設備之室內停車空間,其排水設備應符合的四項要件,尤其是地面坡度的法定數值。\n【正解理由】依《各類場所消防安全設備設置標準》關於室內停車空間水霧滅火設備排水設備之規定,車輛停駐場所地面應作百分之二以上之坡度,使放射後夾帶油料的水能自然流向排水溝與滅火坑。A 選項寫成百分之五以上,與條文所定的百分之二不符;題目問「何者錯誤」,故選 A。\n【逐項排除】\n(A) 錯誤所在,法定坡度為百分之二以上,並非百分之五;坡度只需足以導流,過大反而不利車輛停放與人員行走。\n(B) 正確,車輛停駐場所除面臨車道部分外,應設深十公分、寬十公分以上之地區境界溝,並與排水溝連通,用以攔截外流油水。\n(C) 正確,滅火坑應具備油水分離裝置,並設於火災不易殃及之處所,避免分離出的油品再度被引燃。\n(D) 正確,車道之中央或二側應設置排水溝,以承接由境界溝匯流而來的水量。\n【記憶點】停車空間排水四件套:坡度 2%、境界溝 10×10 公分、車道排水溝、滅火坑油水分離。","室內停車空間的排水設備規定,是水霧滅火設備條文中最具事故背景色彩的一段。停車空間的火災風險主因是車輛燃油與潤滑油;一旦油料洩漏並起火,水霧放射後會產生大量夾帶浮油的廢水,若任其在樓板漫流,火勢會沿著油膜擴散到其他車位,等於用滅火用水把火帶著走。整套規定的核心目的,就是「把油水集中、限制流向、最後分離」。\n\n四項要件其實對應一條完整的水流路徑:先以百分之二以上的地面坡度讓油水離開車位;再由深十公分、寬十公分以上的地區境界溝形成物理阻隔,防止油水橫向流入相鄰車位,並導向車道;車道中央或二側的排水溝負責匯集;最終進入設有油水分離裝置的滅火坑,油浮於上被攔截,水則排出。滅火坑之所以要設在火災不易殃及之處所,是因為坑內累積的是可燃液體,若位置不當等於在建築物內設了一個油池。\n\n數值記憶上,百分之二的坡度換算後,每十公尺落差二十公分,既能導流又不影響停車;若真如誘答所寫的百分之五,每十公尺落差達五十公分,車輛停放與輪椅通行都成問題,從工程合理性反推也能判定選項有誤。境界溝的十公分見方則要與其他常考尺寸區隔:例如儲槽防液堤、公共危險物品場所的集液坑各有不同規格,不可互套。\n\n易混淆概念對照:水霧滅火設備用於室內停車空間時強制要求排水設備,泡沫滅火設備用於同一場所則另有泡沫放出口與發泡倍率的規定;而乾粉、二氧化碳等氣體系統因不產生廢水,自然沒有排水設備的要求。這說明設備選擇與附屬設施是綁在一起的,考題常以「某場所設某設備,下列何者非其應設之附屬設施」的形式出現。\n\n同條文的延伸考點還包括:水霧滅火設備放射區域的面積規定、水源容量計算(以最大放射區域全部噴頭放水二十分鐘計)、防護電氣設備時噴頭與帶電體間的安全間距表,以及室內停車空間得以泡沫、乾粉或二氧化碳等設備替代的條件。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-020","水霧滅火設備之加壓送水裝置使用消防幫浦時，其出水量及出水壓力，下列敘述何者錯誤？",20,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-022","下列那一泡沫滅火設備之泡沫濃度，不符泡沫原液與水混合使用濃度之規定？",22,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-019","進行密閉濕式撒水設備綜合檢查時，末端查驗管之放水壓力應在那個範圍？",19,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-023","泡沫滅火設備進行綜合檢查時，有關蛋白質泡沫滅火藥劑之發泡倍率至少應為何？",23,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-018","公共危險物品等場所設置自動撒水設備時，使用密閉式撒水頭其水源容量，應在設置 X 個撒水頭繼續放水 Y 分鐘之水量以上，其中 X、Y 分別為：",18,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-024","公共危險物品等場所設置移動式泡沫滅火設備時，其水源容量與放水量之規定，下列何者錯誤？",24,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-021",111,"下列有關乾粉滅火設備設置之規定，何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-021",110,"依各類場所消防安全設備設置標準，應就水霧、泡沫、乾粉、二氧化碳滅火設備等選擇設置之場所，下列場所何者得使用預動式自動撒水設備？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-021",109,"室內消防栓中之減水警報裝置，應於水量減至多少時發出警報？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-021",108,"某鍋爐房樓地板面積為 20 m×15 m，依法其所需之滅火效能值為何？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-021",107,"有關乾粉滅火設備配管設置規定，下列敘述何者正確？",1785123168387]