[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-022":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-022","fire-106-1-water-chemical-022",106,1,22,"下列那一泡沫滅火設備之泡沫濃度，不符泡沫原液與水混合使用濃度之規定？",{"A":16,"B":17,"C":18,"D":19},"6%之蛋白質泡沫液","6%之合成界面活性泡沫液","3%之蛋白質活性泡沫液","6%之水成膜泡沫液","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》泡沫滅火設備中,各類泡沫原液與水混合使用之法定濃度組合。\n【正解理由】依《各類場所消防安全設備設置標準》泡沫滅火設備之規定,泡沫原液與水混合使用之濃度為:蛋白質泡沫液百分之三或百分之六;合成界面活性泡沫液百分之一或百分之三;水成膜泡沫液百分之三或百分之六。合成界面活性泡沫液並無百分之六的法定濃度規格,B 選項的組合不在條文所列範圍內;題目問何者不符規定,故選 B。\n【逐項排除】\n(A) 符合規定,蛋白質泡沫液的法定濃度為 3% 或 6%,6% 為其常用高濃度型。\n(B) 不符規定,合成界面活性泡沫液僅有 1% 與 3% 兩種法定濃度,6% 並非本類藥劑的規格。\n(C) 符合規定,蛋白質系泡沫液以 3% 混合使用屬條文明列的濃度之一。\n(D) 符合規定,水成膜泡沫液的法定濃度為 3% 或 6%,兩者皆可採用。\n【記憶點】蛋白質與水成膜走「3 或 6」,合成界面活性走「1 或 3」,唯獨它沒有 6%。","泡沫濃度規格並非任意訂定,而是由藥劑本身的發泡能力決定。合成界面活性泡沫液以界面活性劑為主成分,發泡力極強,只需極低的添加比例即可產生大量泡沫,因此法定濃度落在 1% 與 3%;若強行提高到 6%,不僅浪費藥劑,泡沫過稠反而降低流動性與覆蓋速度。蛋白質泡沫液由動物性蛋白水解物製成,黏性高、耐熱與抗回燃性佳,但發泡效率較低,需要 3% 或 6% 的較高添加率。水成膜泡沫液(AFFF)含氟界面活性劑,能在油面形成一層水膜抑制蒸氣逸出,滅火速度最快,規格同為 3% 或 6%。\n\n實務上濃度規格與比例混合裝置是綁定的:選定 3% 型藥劑,混合器就必須是 3% 規格,兩者不可互換使用,否則濃度偏差會直接導致泡沫品質不合格。這也是為什麼法規要把濃度寫死成幾個標準值,而非給一個範圍——標準化才能確保藥劑、混合器與設備彼此相容。\n\n記憶對照表可整理為:蛋白質 3\u002F6、氟蛋白 3\u002F6、水成膜 3\u002F6、合成界面活性 1\u002F3。口訣是「只有合成界面活性有 1%,也只有它沒有 6%」,本題正是直接考這個唯一的例外。另需注意,水溶性液體(如酒精、丙酮)火災須使用抗酒精型泡沫,否則泡沫會被溶解破泡,這是濃度以外的另一個選用面向。\n\n泡沫的滅火機制包含窒息、冷卻、遮斷可燃蒸氣三項,其中窒息為主。發泡倍率、還原時間(泡沫水溶液還原四分之一所需時間)與泡沫水溶液量,是評估泡沫品質的三個指標;檢修基準對蛋白質泡沫要求發泡倍率五倍以上,合成界面活性與水成膜亦有各自標準,常與本題的濃度規定合併命題。\n\n同條文的延伸考點包括:泡沫頭的種類(泡水噴頭、泡沫噴頭)與其放射量、防護面積規定、固定式與移動式泡沫滅火設備的水源容量差異,以及泡沫原液儲槽與比例混合裝置的設置要求。把「濃度、發泡倍率、還原時間、放射量」四項串成一組,可覆蓋泡沫章節多數選擇題。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-021","裝置水霧滅火設備之室內停車空間，其排水設備應符合之規定，下列何者錯誤？",21,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-023","泡沫滅火設備進行綜合檢查時，有關蛋白質泡沫滅火藥劑之發泡倍率至少應為何？",23,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-020","水霧滅火設備之加壓送水裝置使用消防幫浦時，其出水量及出水壓力，下列敘述何者錯誤？",20,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-024","公共危險物品等場所設置移動式泡沫滅火設備時，其水源容量與放水量之規定，下列何者錯誤？",24,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-019","進行密閉濕式撒水設備綜合檢查時，末端查驗管之放水壓力應在那個範圍？",19,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-025","某一防護對象物長寬高分別為 5 公尺、4 公尺及 1 公尺，若以高發泡局部放射泡沫滅火系統進行防護，依各類場所消防安全設備設置標準之規定，其防護面積應為多少平方公尺？",25,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-022",111,"有關水道連結型自動撒水設備進行綜合檢查時，其放水壓力應為多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-022",110,"同一建築基地內有二棟以上建築物時，建築物間外牆與中心線水平距離第一層在 X 公尺以下，第二層在 Y 公尺以下，且合計各棟該第一層及第二層樓地板面積在 Z 平方公尺以上者，應設置消防專用蓄水池。X、Y、Z 分別為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-022",109,"室內消防栓之箱面字樣，每字不得小於多少平方公分？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-022",108,"有關潔淨藥劑氣體滅火設備滅火藥劑主要成分之敘述，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-022",107,"可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽設置滅火器，其設置規定，下列敘述何者正確？",1785123168400]