[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-023":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-023","fire-106-1-water-chemical-023",106,1,23,"泡沫滅火設備進行綜合檢查時，有關蛋白質泡沫滅火藥劑之發泡倍率至少應為何？",{"A":16,"B":17,"C":18,"D":19},"3 倍以上","5 倍以上","6 倍以上","10 倍以上","B",null,[],false,"本題考點：《消防安全設備檢修及申報作業基準》泡沫滅火設備綜合檢查中,蛋白質泡沫滅火藥劑之發泡倍率合格判定值。\n【正解理由】依《消防安全設備檢修及申報作業基準》泡沫滅火設備綜合檢查之規定,採取泡沫試料量測發泡倍率時,蛋白質泡沫滅火藥劑之發泡倍率應在五倍以上;發泡倍率係泡沫體積與其還原後泡沫水溶液體積之比值,倍率不足代表混合比例、發泡器或放射壓力有問題,泡沫將無法有效覆蓋油面,故選 B。\n【逐項排除】\n(A) 三倍以上低於法定判定值,以此標準驗收會讓發泡能力不足的系統通過檢查。\n(B) 正確,蛋白質泡沫滅火藥劑的發泡倍率判定基準即為五倍以上。\n(C) 六倍以上並非本項判定值,6 是蛋白質泡沫液的常見混合濃度百分比,與發泡倍率是不同的物理量,選項刻意製造混淆。\n(D) 十倍以上遠高於法定基準,屬於高發泡系統的量級,不適用於蛋白質泡沫的低發泡綜合檢查判定。\n【記憶點】低發泡系藥劑發泡倍率一律看「五倍以上」,別把濃度的 3% 或 6% 誤當倍率。","發泡倍率的定義是:一定量泡沫水溶液發泡後所得泡沫體積,除以該泡沫完全還原成水溶液的體積。檢修時以容量一千毫升的泡沫試料容器承接放射中的泡沫,秤重後扣除容器重,依泡沫水溶液密度換算還原體積,即可算得倍率。與之搭配量測的還有「二十五percent還原時間」,即泡沫還原至四分之一水溶液量所需時間,蛋白質泡沫要求一分鐘以上,水成膜泡沫要求一分鐘以上,兩項指標一起看,才能同時評估泡沫的量與穩定度。\n\n倍率為何訂在五倍?泡沫滅火靠的是在燃燒液面形成連續覆蓋層,阻絕可燃蒸氣並冷卻表面。倍率太低表示含水多、泡沫稀薄,雖然冷卻好但覆蓋層易破;倍率太高則泡沫過乾、含水少,遇高溫迅速破泡,抗回燃性差。五倍是低發泡系統在覆蓋性與耐熱性之間的平衡下限。依發泡倍率可將泡沫分成三類:低發泡(二十倍以下)、中發泡(二十至二百倍)、高發泡(二百至一千倍)。滅火設備常用的固定式與移動式泡沫多屬低發泡;高發泡則用於室內停車空間、飛機庫等需要大量填充空間的場所,其判定標準與本題完全不同,不可互套。\n\n易混淆之處,正是本題誘答的設計來源:蛋白質泡沫液的混合濃度是 3% 或 6%,發泡倍率是 5 倍以上,兩個數字都出現在同一章節卻是不同維度。判別方法很簡單——濃度帶百分號、講的是原液與水的比例;倍率不帶單位、講的是泡沫與水溶液的體積比。考場上看到選項有「%」就往濃度規格想,看到「倍」就往發泡品質想。\n\n綜合檢查的其他項目還包括:放射壓力是否達標、泡沫放射量、泡沫水溶液的混合比例(以折射率或電導度法量測)、以及選擇閥與一齊開放閥的動作確認。這些項目與外觀檢查(藥劑儲槽外觀、配管腐蝕)、性能檢查(藥劑變質、幫浦性能)構成三階段檢查體系,命題時常以「下列何者屬綜合檢查項目」的形式出現,需分辨清楚。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-022","下列那一泡沫滅火設備之泡沫濃度，不符泡沫原液與水混合使用濃度之規定？",22,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-024","公共危險物品等場所設置移動式泡沫滅火設備時，其水源容量與放水量之規定，下列何者錯誤？",24,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-021","裝置水霧滅火設備之室內停車空間，其排水設備應符合之規定，下列何者錯誤？",21,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-025","某一防護對象物長寬高分別為 5 公尺、4 公尺及 1 公尺，若以高發泡局部放射泡沫滅火系統進行防護，依各類場所消防安全設備設置標準之規定，其防護面積應為多少平方公尺？",25,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-020","水霧滅火設備之加壓送水裝置使用消防幫浦時，其出水量及出水壓力，下列敘述何者錯誤？",20,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-026","消防專用蓄水池至建築物各部分之水平距離，應在多少公尺以下？",26,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-023",111,"簡易自動滅火設備進行性能檢查時，蓄壓式滅火藥劑儲存容器滅火藥劑量應與標示差異不超過多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-023",110,"下列場所何者可選擇第二種室內消防栓選擇設置之？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-023",109,"下列有關室內消防栓箱之敘述，何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-023",108,"依各類場所消防安全設備設置標準之規定，有關應設置室外消防栓設備之場所，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-023",107,"有關室內消防栓綜合檢查放水量及放水壓力之敘述，下列何者正確？",1785123168409]