[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-106-1-water-chemical-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-036","fire-106-1-water-chemical-036",106,1,36,"低壓式二氧化碳噴頭之放射壓力為每平方公分多少公斤以上？",{"A":16,"B":17,"C":18,"D":19},"1","5","9","14","C",null,[],false,"本題考點：二氧化碳滅火設備全區放射方式中，高壓式與低壓式噴頭放射壓力的法定下限值。\n【正解理由】依《各類場所消防安全設備設置標準》第 84 條，二氧化碳滅火設備之噴頭，全區及局部放射方式者，其放射壓力，高壓式（常溫貯存）應在每平方公分 14 公斤以上，低壓式（貯存於攝氏零下 18 度左右之低溫容器）應在每平方公分 9 公斤以上，故選 C。\n【逐項排除】\n(A) 1：此為自動撒水設備撒水頭放水壓力的量級（1 kgf\u002Fcm² 以上），與二氧化碳藥劑必須靠自身蒸氣壓迅速氣化擴散的需求不同。\n(B) 5：無此法定值。5 kgf\u002Fcm² 不足以使液態二氧化碳在管線末端維持設計流量與噴射距離。\n(C) 9：正是低壓式的下限。低溫貯存使容器內壓約 21 kgf\u002Fcm²，扣除管損後末端仍須達 9 kgf\u002Fcm² 以上。\n(D) 14：數值本身正確，但屬高壓式的下限，題目問的是低壓式，選項對象錯置。\n【記憶點】二氧化碳噴頭壓力「高十四、低九」，高壓常溫、低壓冷藏。","二氧化碳滅火設備依貯存方式分兩大系統。高壓式將二氧化碳以液態常溫貯存於鋼瓶，容器內壓隨環境溫度變動，常溫下約 60 kgf\u002Fcm²，夏季高溫時更高，故鋼瓶與配管耐壓要求嚴格；低壓式則以冷凍機把貯槽維持在攝氏零下 18 度上下，內壓穩定在 21 kgf\u002Fcm² 附近，適合藥劑量大的場所，可減少大量鋼瓶的佔用空間與定期換裝作業。兩者貯存壓力差了近三倍，末端噴頭能保證的放射壓力自然不同，法規因此分列 14 與 9 兩個下限。\n放射壓力的物理意義在於霧化與滲透：液態二氧化碳自噴頭噴出時瞬間減壓氣化，體積膨脹約 450 倍並產生乾冰微粒，靠稀釋氧氣與冷卻雙重機制滅火。壓力不足會使氣化不完全、噴射距離縮短，藥劑滯留在噴頭附近，防護區劃內濃度分布不均，設計濃度形同虛設。這也是為何條文同時要求全區放射須於一定時間（一般為 1 分鐘，深層火災為 7 分鐘）內放射完畢——壓力與時間共同保證濃度曲線。\n單位換算提醒：1 kgf\u002Fcm² 約等於 0.098 MPa，也約等於 10 公尺水頭。故 14 kgf\u002Fcm² 約 1.37 MPa，9 kgf\u002Fcm² 約 0.88 MPa，看到以 MPa 出題時要能立刻換回。\n同一條文的延伸考法包括：局部放射方式的放射壓力是否相同（相同）、全區放射的放射時間、以及與海龍替代品（如 IG-541、HFC-227ea）噴頭壓力規定的比較。易混淆的是「貯存容器壓力」與「噴頭放射壓力」——前者是源頭、後者是末端，題目問哪一個要看清楚。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-035","乾式比濕式系統的撒水頭數量應追加百分之多少？",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-037","消防幫浦之全閉揚程應為性能曲線上全揚程之百分之多少以下，方符合檢修基準要求？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-034","第一種乾粉滅火藥劑，全區放射方式所需滅火藥劑量為多少 kg\u002Fm ？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-106-1-water-chemical-038","乾粉全區放射所核算之滅火藥劑量須於幾秒內放射完畢？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-033","二氧化碳局部放射方式依規定所核算之滅火藥劑量，應於多少秒內全部放射完畢？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-106-1-water-chemical-039","泡沫滅火設備使用低發泡水成膜泡沫液，其泡沫 25%還原時間應在多少分鐘以上？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-036",111,"二氧化碳滅火設備，採用低壓式滅火藥劑儲存容器時，壓力在何範圍會發出警報？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-036",110,"依消防安全設備及必要檢修項目檢修基準，自動撒水設備之加壓送水裝置，在減壓措施方面，補助撒水栓放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-036",109,"任一消防專用蓄水池至建築物各部分之水平距離不得超過多少公尺？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-036",108,"依各類場所消防安全設備設置標準之規定，高發泡放出口在全區放射防護區域內，樓地板面積每多少平方公尺應至少設置 1 個，且能有效放射至該區域，並附設泡沫放出停止裝置？",{"webId":70,"year":71,"stem":72,"number":13},"fire-107-1-water-chemical-036",107,"有關自動撒水設備末端查驗閥之敘述，下列何者正確？",1785123168532]