[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-106-1-water-chemical-039":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-106-1-水與化學系統消防安全設備概要-039","fire-106-1-water-chemical-039",106,1,39,"泡沫滅火設備使用低發泡水成膜泡沫液，其泡沫 25%還原時間應在多少分鐘以上？",{"A":16,"B":17,"C":18,"D":19},"0.5","1","2","5","B",null,[],false,"本題考點：泡沫滅火設備性能試驗中，低發泡水成膜泡沫液「25% 還原時間」的合格下限。\n【正解理由】依《消防安全設備檢修及申報作業基準》泡沫滅火設備之泡沫試料判定基準，低發泡之水成膜泡沫（AFFF）發泡倍率應在 5 倍以上，25% 還原時間應在 1 分鐘以上，故選 B。25% 還原時間指泡沫中所含泡沫水溶液還原（滴落）達其全量四分之一所需的時間，時間愈長代表泡沫愈安定、封面效果愈持久。\n【逐項排除】\n(A) 0.5：低於基準。半分鐘即還原四分之一，代表泡沫破泡過快，無法在油面維持連續水膜。\n(B) 1：正是水成膜泡沫的合格下限，與發泡倍率 5 倍以上並列判定。\n(C) 2：偏嚴。此為蛋白泡沫等安定性較高藥劑常見的實測值，非水成膜的法定下限。\n(D) 5：更遠離基準。5 分鐘屬高膨脹或特殊配方的表現，以此為門檻將使多數合格藥劑被誤判。\n【演算步驟】25% 還原量公式：泡沫水溶液量 = 泡沫試料淨重 ÷ 發泡倍率；25% 還原量 = 泡沫水溶液量 × 0.25。設試料淨重 180 g、發泡倍率 6 倍：180 g ÷ 6 = 30 mL；30 mL × 0.25 = 7.5 mL；量筒收集到 7.5 mL 所歷經之時間須 ≧ 1 分鐘方為合格。\n【記憶點】水成膜泡沫「發泡五倍、還原一分鐘」，兩項同時達標才算合格。","泡沫滅火設備的效能不只看發多少泡，更看泡沫撐多久。判定用的兩個指標互為表裡：發泡倍率是泡沫體積除以原泡沫水溶液體積，代表覆蓋能力；25% 還原時間是泡沫因排液、破泡而還原出四分之一水溶液所需時間，代表安定性。發泡倍率高但還原快，泡沫看似厚實卻迅速塌陷；還原慢但發泡不足，覆蓋面積不夠。故基準要求兩者同時達標。\n檢測方法採泡沫試料採集器在放射末端取樣，量測容器淨重換算水溶液量，再置於還原量測裝置以量筒逐時記錄滴落量。計算時關鍵是先把「泡沫重量」透過發泡倍率換回「水溶液體積」——因泡沫水溶液密度近似 1 g\u002FmL，重量與體積可直接對應，這是計算題最常被漏掉的一步。\n藥劑種類與機制對照：水成膜泡沫（AFFF）含氟界面活性劑，在油面上鋪展形成一層水膜，靠水膜與泡沫層雙重封阻可燃蒸氣，滅火速度快、流動性佳，適合機場、油槽區與停車空間；蛋白泡沫由動物性蛋白水解而成，泡沫強韌、耐熱與抗回火性佳，但流動慢；合成界面活性劑泡沫可做成高發泡，用於大空間充填；水成膜與其他藥劑不可任意混用，配方相斥會導致泡沫劣化。\n高、低發泡的區分也常入題：低發泡指發泡倍率 20 倍以下，高發泡為 80 倍至 1000 倍以下，兩者的試驗方法與判定基準不同，看到「低發泡」三個字就要鎖定 5 倍與 1 分鐘這組數字。相關延伸考點包括泡沫放出口種類（Ⅰ型、Ⅱ型、泡沫噴頭、泡沫栓）、泡沫原液混合方式（比例混合器、壓入式、環繞式）與泡沫水溶液量之計算。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-106-1-water-chemical-038","乾粉全區放射所核算之滅火藥劑量須於幾秒內放射完畢？",38,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-106-1-water-chemical-040","有一長 15 公尺、寬 12 公尺及高 3 公尺之密閉空間裝置二氧化碳滅火設備，假設空氣中氧氣之體積百分率濃度為 21%，在溫度壓力固定下，欲使氧氣濃度降至 15%以下，需注入多少立方公尺之二氧化碳？",40,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-106-1-water-chemical-037","消防幫浦之全閉揚程應為性能曲線上全揚程之百分之多少以下，方符合檢修基準要求？",37,{"webId":41,"stem":42,"number":12,"year":43,"session":12},"fire-107-1-water-chemical-001","撒水頭之設置位置規定中，撒水頭迴水板下方 A 公分內及水平方向 B 公分內，應保持淨空間，不得有障礙物，其中 A、B 分別為下列何者？",107,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-106-1-water-chemical-036","低壓式二氧化碳噴頭之放射壓力為每平方公分多少公斤以上？",36,{"webId":49,"stem":50,"number":51,"year":43,"session":12},"fire-107-1-water-chemical-002","有關連結送水管之送水口設置規定，下列何者錯誤？",2,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-039",111,"可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-039",110,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之遠隔啟動裝置，限用於儲存閃火點多少℃以下公共危險物品之室外儲槽？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-039",109,"公共危險品等場所中，所設置之室外消防栓設備，其緊急電源之供電容量應供其有效動作多久以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-039",108,"依各類場所消防安全設備設置標準之規定，公共危險物品室外儲槽場所之冷卻撒水設備如以幫浦方式進行加壓時，實際測得之放射量除以該冷卻撒水噴頭（噴孔）所防護儲槽側壁面積應在多少以上？",{"webId":70,"year":43,"stem":71,"number":13},"fire-107-1-water-chemical-039","為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",1785123168567]