[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-002","fire-107-1-alarm-evacuation-002",107,1,2,"差動式分布型探測器為熱半導體式時，裝接於一個檢出器之感熱器數量，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"1","10","20","30","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 121 條把差動式分布型探測器依感熱媒介分成三種型式，各型式對「一個檢出器能承載多少前端元件」分別訂數，本題問的是熱半導體式那一組。\n【正解理由】依《各類場所消防安全設備設置標準》第 121 條第三款，熱半導體式者，探測器下端裝設在裝置面下方三十公分範圍內，各探測區域依探測器種類及裝置面高度所定有效探測範圍設置，且該款明定「裝接於一個檢出器之感熱器數量，在二個以上十五個以下」。兩個端點都有由來：下限二個對應同款「每一有效探測範圍至少設置二個」的設置原則；上限十五個則因檢出器須彙整各感熱器的阻值變化再判定溫升率，掛得愈多，單一元件的訊號在合成值中被稀釋得愈嚴重。四個選項僅十個落在二至十五之間，故選 B。\n【逐項排除】\n(A) 一個低於下限二個，一個檢出器只掛一具感熱器等於退化為單點偵知，失去分布型以面偵知的前提。\n(B) 十個落在二個以上十五個以下的合法區間，是四個選項中唯一未低於下限也未超過上限者。\n(C) 二十個是同條第二款熱電偶式所定「裝接於一個檢出器之熱電偶數，在二十個以下」的上限，命題者刻意擺進來釣型式張冠李戴的考生。\n(D) 三十個大幅超過上限，檢出器將難以辨識個別感熱器的阻值變化，靈敏度被稀釋。\n【記憶點】同條三型式各記一個數：空氣管一百公尺以下、熱電偶二十個以下、熱半導體感熱器二至十五個。","差動式分布型探測器的原理是以「面」偵知：不像局限型只看一個點，它把感熱元件分布於整個探測區域，靠溫升率觸發。《各類場所消防安全設備設置標準》第 121 條依感熱媒介把它分成三種型式——空氣管式以管內空氣受熱膨脹推動膜片；熱電偶式以熱電偶產生熱電動勢；熱半導體式以熱敏元件的阻值變化為訊號。三者共通的元件是檢出器，負責彙整前端訊號並判定是否為火災，數量上限的意義正在於此：接得愈多，單一感熱器的訊號在合成值中被稀釋得愈嚴重，靈敏度隨之下降。同條並要求檢出器應設於便於檢修處，且與裝置面不得傾斜五度以上——檢出器靠比對微小訊號動作，傾斜會使基準偏移，這也是它與探測器本體分開規範的原因。\n數量與面積的關係要對照著背。同條第二款熱電偶式附表規定，防火構造建築物之探測區域樓地板面積在八十八平方公尺以下者至少四個，超過者應設四個並每增加二十二平方公尺（包括未滿）增設一個；其他建築物則為七十二平方公尺以下至少四個，超過者每增加十八平方公尺增設一個。熱半導體式改採「有效探測範圍」制：裝置面高度未滿八公尺時，防火構造建築物一種六十五平方公尺、二種三十六平方公尺，其他建築物為四十與二十三平方公尺；八公尺以上未滿十五公尺僅列一種，防火構造五十、其他建築物三十平方公尺。且每一有效探測範圍至少設置二個，裝置面高度未滿八公尺時至少設置一個。\n配套規定一併記：第 119 條規定探測區域指裝置面四周以淨高四十公分以上之樑或類似構造體區劃包圍者，但差動式分布型及偵煙式探測器須為六十公分以上；第 115 條規定天花板設有出風口時，除火焰式、差動式分布型及光電式分離型外應距出風口一點五公尺以上；第 114 條的裝置場所高度表則顯示，八公尺以上未滿十五公尺仍可選用差動式分布型。易混淆對照：熱電偶式數的是熱電偶、熱半導體式數的是感熱器、空氣管式量的是管長，計量對象不同，考題最愛把二十個與十五個對調。",true,[28,31,35,40,44,48],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-107-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，除供甲類場所、地下建築物、高層建築物或應設置偵煙式探測器之場所外，若要以自動撒水設備免設火警自動警報設備，有關密閉型撒水頭之規定，下列那一項正確？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-107-1-alarm-evacuation-003","下列何者非屬定溫式探測器可裝設場所？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-106-1-alarm-evacuation-040","有關出口標示燈具閃滅或音聲引導功能者，依規定下列何者錯誤？",40,106,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-004","下列那一種探測器，不可以裝設於室內天花板或屋頂板高度 15 公尺以上未滿 20 公尺之空間？",4,{"webId":45,"stem":46,"number":47,"year":39,"session":12},"fire-106-1-alarm-evacuation-039","具有效採光，且直接面向室外之通道或走廊居室得免設緊急照明；所謂有效採光面積應達該居室樓地板面積多少比率方得免設？",39,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-005","有一地下三層地上十層之建築物，總樓地板面積 5000 平方公尺，若起火樓層位於三樓時，下列那一樓層火警自動警報設備須鳴動？",5,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-002",110,"某樓高 12 層觀光旅館於最高樓層開設之餐廳，依各類場所消防安全設備設置標準之規定，其位於同樓層的廚房無須設置下列何種裝置？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-002",109,"使用「加瓦斯試驗器」進行瓦斯漏氣檢知器性能檢查時，若檢測對象的瓦斯對空氣之比重大於 1 者，應使用何種氣體來檢測？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-002",108,"特別安全梯的安全梯與緊急昇降機兼用時，其排煙機、進風機之排煙量、進風量須在每秒多少立方公尺以上？",{"webId":66,"year":39,"stem":67,"number":13},"fire-106-1-alarm-evacuation-002","對於消防安全設備緊急供電系統之配線之規定，下列何者正確？",1785123172164]