[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-004","fire-107-1-alarm-evacuation-004",107,1,4,"下列那一種探測器，不可以裝設於室內天花板或屋頂板高度 15 公尺以上未滿 20 公尺之空間？",{"A":16,"B":17,"C":18,"D":19},"差動式局限型","光電式分離型一種","光電式局限型一種","離子式局限型一種","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》對探測器裝置場所高度的限制,考的是高度十五公尺以上未滿二十公尺時可用與不可用的探測器種類。\n【正解理由】依《各類場所消防安全設備設置標準》有關探測器裝置高度之規定,裝置面高度十五公尺以上未滿二十公尺之場所,僅得設置離子式局限型一種、光電式局限型一種、光電式分離型一種及火焰式探測器;熱感知型的差動式局限型探測器因高溫氣流上升途中大量稀釋、擴散,到達裝置面時溫升速率已不足以動作,故其可裝設高度上限遠低於此範圍,不得設於該高度。故選 A。\n【逐項排除】\n(A) 正確,為本題答案。差動式局限型屬熱感知型,受熱氣流稀釋影響最大,可裝設高度上限僅到未滿八公尺,無法用於十五公尺以上空間。\n(B) 光電式分離型一種以光軸遮蔽率判定,適合挑高與大空間,明列於可設置種類中。\n(C) 光電式局限型一種感度最高,亦在該高度可設置之列。\n(D) 離子式局限型一種同屬高感度偵煙探測器,亦得設於該高度。\n【記憶點】愈高的空間愈要靠煙與火焰,熱感知型爬不上去。","探測器的裝置高度限制,本質上是「偵測訊號在垂直輸送過程中衰減多少」的物理問題。火源產生的熱煙氣柱在上升過程中不斷捲吸周圍冷空氣,質量流量增加而溫度下降,高度愈高、稀釋倍數愈大。熱感知型探測器依賴的是裝置面附近的溫度或溫升速率,在挑高空間中往往等到火勢極大才動作,失去早期偵知的意義,故法規把差動式局限型限制在較低的裝置高度,超過即不得採用。相對地,煙粒子雖同樣被稀釋,但偵煙探測器的動作門檻以減光率或離子電流變化計,對低濃度仍能反應,故可用到較高處;火焰式偵測的是火焰輻射的紫外線或紅外線,以直線視距接收,幾乎不受高度稀釋影響,因此可用於最高的空間。\n把整組高度級距串起來記,效果最好:未滿四公尺幾乎所有種類皆可;四公尺以上未滿八公尺開始排除感度較低者;八公尺以上未滿十五公尺再排除熱感知型,僅留偵煙與火焰式等;十五公尺以上未滿二十公尺再收斂為一種偵煙(離子式局限型、光電式局限型、光電式分離型)與火焰式;二十公尺以上則僅餘光電式分離型一種與火焰式。可用「愈高愈少、熱的先出局」一句話帶過趨勢,再記住最高一級只剩分離型與火焰式這個端點。\n易混淆處在於「一種、二種」在此指感度種別,感度愈高者容許的裝置高度愈高、有效探測面積亦愈大;另需區分裝置高度限制與有效探測面積規定,前者決定「能不能用」,後者決定「要用幾個」,兩者常在同一題中交錯出現。延伸考點還包括:設有樓梯、昇降機坑道等垂直通道時的探測器設置規定,以及裝置面附近有排煙口或空調吹出口時應保持的距離要求。",true,[28,32,36,40,44,47],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-003","下列何者非屬定溫式探測器可裝設場所？",3,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-005","有一地下三層地上十層之建築物，總樓地板面積 5000 平方公尺，若起火樓層位於三樓時，下列那一樓層火警自動警報設備須鳴動？",5,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-002","差動式分布型探測器為熱半導體式時，裝接於一個檢出器之感熱器數量，下列何者正確？",2,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-006","下列何種使用瓦斯之場所，應設置瓦斯漏氣火警自動警報設備？",6,{"webId":45,"stem":46,"number":12,"year":11,"session":12},"fire-107-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，除供甲類場所、地下建築物、高層建築物或應設置偵煙式探測器之場所外，若要以自動撒水設備免設火警自動警報設備，有關密閉型撒水頭之規定，下列那一項正確？",{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-107-1-alarm-evacuation-007","有一防火構造建築物，其探測區域樓地板面積為 100 平方公尺，欲設置差動式分布型熱電偶式探測器，至少應該設置多少探測器數量？",7,[52,56,60,64,68],{"webId":53,"year":54,"stem":55,"number":13},"fire-114-1-alarm-evacuation-004",114,"某電影院放映場所火警自動警報設備所使用之蓄積型偵煙探測器有 10 秒之蓄積時間，其所使用之中繼器有 10 秒之蓄積時間，則其受信總機之蓄積時間，最多可為多少秒？",{"webId":57,"year":58,"stem":59,"number":13},"fire-112-1-alarm-evacuation-004",112,"依據一一九火災通報裝置檢修基準之性能檢查，下列何者非預備電源檢查方法之項目？",{"webId":61,"year":62,"stem":63,"number":13},"fire-110-1-alarm-evacuation-004",110,"有一棟總樓地板面積 4,000 平方公尺的七層辦公建築物，當起火層為地上第二層時，下列有關其火警自動警報設備分區鳴動方式的敘述，何者正確？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-alarm-evacuation-004",109,"某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-alarm-evacuation-004",108,"某一防火構造建築物，地上 5 層且為無開口樓層，1 至 2 層供辦公室用途使用，3 至 5 層供餐廳用途使用，各樓層樓地板面積皆為 200 平方公尺，依照各類場所消防安全設備設置標準之規定，請問本場所火警自動警報設備之設置情形，下列何者正確？",1785123172184]