[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-010":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-010","fire-107-1-alarm-evacuation-010",107,1,10,"依各類場所消防安全設備設置標準第 23 條規定，各類場所均應設置避難指標。但設有以下那一個設備時，在其有效範圍內，得免設置避難指標？",{"A":16,"B":17,"C":18,"D":19},"避難方向指示燈","緊急照明設備","觀眾席引導燈","自動照明燈","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 23 條標示設備應設場所中，避難指標之免設要件。\n【正解理由】第 23 條第 4 款明定「各類場所均應設置避難指標。但設有避難方向指示燈或出口標示燈時，在其有效範圍內，得免設置避難指標」，免設要件經法條文字限定於避難方向指示燈與出口標示燈二者，四個選項中僅避難方向指示燈在列，故選 A。\n【逐項排除】\n(A) 避難方向指示燈為第 10 條第 1 款列舉之標示設備，本身持續發光指示避難方向，引導功能涵蓋被動式指標，是第 23 條第 4 款但書明文列舉的免設要件。\n(B) 緊急照明設備依第 10 條為與標示設備並列之獨立種類，功能在維持避難路徑照度，不具方向指示功能，但書未將其列入。\n(C) 觀眾席引導燈雖同屬第 10 條之標示設備，但依第 23 條第 3 款僅戲院、電影院、歌廳、集會堂等場所應設，功能為照亮觀眾席通道，非指引出口方向，不在但書之列。\n(D) 自動照明燈非第 10 條所定設備名稱，法規並無此用語。\n【記憶點】能頂替避難指標的，只有會發光又會指路的出口標示燈與避難方向指示燈。","《各類場所消防安全設備設置標準》第 10 條把避難逃生設備分為標示設備、避難器具與緊急照明設備三類，其中標示設備又含出口標示燈、避難方向指示燈、觀眾席引導燈、避難指標四種。四者位階不同：前兩者屬主動發光式，須接電並連接緊急電源，停電、濃煙時仍能自行發光；避難指標則是被動式標示板，第 154 條僅要求其構造符合 CNS 一○二○八，並無自行發光之要求。正因為發光式設備的引導效果涵蓋被動標示板，第 23 條第 4 款才設計成單向免設——有出口標示燈或避難方向指示燈可免避難指標，反之不成立。\n免設規定的層次感：第 146 條另以「步行距離」訂免設門檻，自居室任一點易於觀察識別主要出入口時，該步行距離在避難層二十公尺以下、避難層以外樓層十公尺以下者，得免設出口標示燈；四十公尺、三十公尺以下者，得免設避難方向指示燈；三十公尺以下者，得免設避難指標。門檻由嚴而寬，正對應三種設備引導能力的高低；且位於地下建築物、地下層或無開口樓層者不適用，因為這些場所缺乏自然採光與外部方位參考。\n易混淆對照：觀眾席引導燈管的是「腳下」，依第 23 條第 3 款僅戲院、電影院、歌廳、集會堂及類似場所應設，用於照亮暗場中的觀眾席通道；緊急照明設備管的是「亮度」；能管「方向與出口位置」的只有避難方向指示燈與出口標示燈。\n相關考點連結：本條常與第 146 條免設步行距離、第 154 條構造依據合併命題，也常以「下列何者非標示設備」的反向題出現，第 10 條四種標示設備名稱須逐字記牢。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-009","以下有關各類場所消防安全設備設置標準對火警分區的規定，何者錯誤？",9,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-011","依各類場所消防安全設備設置標準規定，火警受信總機、中繼器及偵煙式探測器，有設定蓄積時間時，其蓄積時間之合計，每一火警分區在多少秒以下？",11,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-008","當差動式分布型探測器為空氣管式時，下列那一項的敘述不符合設置標準？",8,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-012","有關光電式分離型探測器光軸，下列設置規定何者正確？",12,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-007","有一防火構造建築物，其探測區域樓地板面積為 100 平方公尺，欲設置差動式分布型熱電偶式探測器，至少應該設置多少探測器數量？",7,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-013","依各類場所消防安全設備設置標準規定，火警自動警報設備之配線，除依屋內線路裝置規則外，其電源回路導線間及導線與大地間之絕緣電阻值，以直流 250 伏特額定之絕緣電阻計測定，對地電壓在 150 伏特以下者，應該在多少 MΩ 以上？",13,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-010",110,"各型探測器在性能試驗中，下列有關其動作試驗的動作時間，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-010",109,"緩降機之設置應保有必要操作面積（不含避難器具所占面積），其相關規定下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-010",108,"某一廣播區域面積為 150 平方公尺，設有揚聲器，請問距所設揚聲器 1 m 處所測得之音壓須達多少以上才符合規定？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-010",106,"緩降機設置周圍為避免有操作障礙，因此限制必要操作面積為 M 平方公尺以上（不含避難器具所占面積），但邊長應為 N 公分以上。下列何者正確？",1785123172245]