[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-016":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-016","fire-107-1-alarm-evacuation-016",107,1,16,"避難器具之設置數量與場所之收容人數有很大的關係，依各類場所消防安全設備設置標準規定，有關醫療機構（醫院、診所）候診室之收容人數之計算，應以各候診室之樓地板面積和除多少平方公尺所得之數，做為候診室之收容人數？",{"A":16,"B":17,"C":18,"D":19},"3 平方公尺","4 平方公尺","5 平方公尺","6 平方公尺","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 160 條收容人員計算方式中，醫療機構候診室之計算基準。\n【正解理由】避難器具應設數量以收容人員為基準，收容人員之計算依第 160 條附表；醫療機構（醫院、診所）之收容人員，為從業員工數、病房內病床數，及各候診室樓地板面積和除三平方公尺所得之數三者合計。題目問的是候診室部分之除數，即 3 平方公尺，故選 A。\n【逐項排除】\n(A) 3 平方公尺為表列候診室之除數，候診室屬密集等候空間，除數訂得小、算出人數多，避難器具才不致設置不足。\n(B) 4 平方公尺非表列數值，屬憑印象放大除數的干擾項。\n(C) 5 平方公尺非表列數值，容易與同表「其他部分以該部分樓地板面積除零點五平方公尺」的零點五混為一談。\n(D) 6 平方公尺非表列數值，除數愈大算出的收容人員愈少，與候診室高密度使用的事實不符。\n【記憶點】醫療機構候診室「面積除以三」，員工數與病床數還要另外加。","收容人員在本標準中是「要不要設、要設幾具避難器具」的入口參數：先依《各類場所消防安全設備設置標準》第 160 條附表算出各樓層收容人員，再對照表列數量決定應設避難器具數——第 160 條開宗明義即為「第一百五十七條表列收容人員之計算，依下表規定」。除數愈小，代表法規假設該空間人員密度愈高；醫療機構候診室採三平方公尺，反映等候期間人員密集、且行動不便者比例偏高的事實。要注意醫療機構的收容人員不是只算候診室，而是從業員工數、病房內病床數與候診室換算人數三者合計。\n同表其他常考除數可對照記憶：電影片映演場所（戲院、電影院）、歌廳、集會堂、體育館、活動中心，其收容人員為從業員工數，加上觀眾席部分之合計——設固定席位部分以該部分座椅數計，如為連續式席位，為該座椅正面寬度除零點四公尺所得之數（未滿一之零數不計）；設立位部分以該部分樓地板面積除零點二平方公尺所得之數；其他部分以該部分樓地板面積除零點五平方公尺所得之數。由此可看出「站著比坐著擠、走道比席位鬆」的密度邏輯。\n算出收容人員之後還有減設規定：第 158 條規定建築物主要構造為防火構造，且設有二座以上不同避難方向之安全梯（剪刀式樓梯視為一座）者，前條附表所列收容人員一百人、二百人及三百人，得分別以其加倍數值重新核算應設避難器具數；設有避難橋之屋頂平臺或架空走廊之樓層，另可各減設二具。\n相關考點連結：收容人員計算常與避難器具應設數量、減設條件合併命題，計算題則會給樓地板面積要求換算人數後再查表。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-015","有關緊急供電系統之電源，下列何者錯誤？",15,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-017","供緩降機或救助袋使用之支固器具及供懸吊型梯、滑杆或避難繩索使用之固定架，若使用螺栓固定時，下列何者錯誤？",17,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-014","依各類場所消防安全設備設置標準規定，火警受信總機若為壁掛型，總機操作開關距離樓地板面之高度，應該為多少公尺範圍？",14,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-018","依各類場所消防安全設備設置標準規定，每一火警分區，依規定設置火警發信機，其標示燈應平時保持明亮，其透明罩為圓弧形，裝置後突出牆面，標示燈與裝置面應成幾度角？",18,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-013","依各類場所消防安全設備設置標準規定，火警自動警報設備之配線，除依屋內線路裝置規則外，其電源回路導線間及導線與大地間之絕緣電阻值，以直流 250 伏特額定之絕緣電阻計測定，對地電壓在 150 伏特以下者，應該在多少 MΩ 以上？",13,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-019","在設置避難器具時，皆必須考慮其開口部保有必要開口面積、無操作障礙之面積、下降空間及下降空地等因素，試問於設置避難器具為緩降機時，下列敘述何者錯誤？",19,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-016",110,"建築物之避難器具設置緩降機時，對其開口部進行外觀檢查之判定，下列何者合格？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-016",109,"防煙壁為自天花板下垂 X 公分以上之垂壁，但地下建築物之地下通道，防煙壁應自天花板下垂 Y 公分以上，其中 X、Y 分別為：",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-016",108,"依照各類場所消防安全設備檢修及申報作業基準之規定，某燃燒器具的瓦斯，對空氣比重大於 1 時，其檢知器應設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離 A 公尺以內；檢知器上端，應裝設在距樓地板面 B 公分範圍內。請問前述 A、B 為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-016",106,"瓦斯漏氣火警自動警報設備裝置於瓦斯對空氣之比重未滿一之建築物室內時，檢知器設置位置應距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離多少以內？",1785123172297]