[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-024":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-024","fire-107-1-alarm-evacuation-024",107,1,24,"P 型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，依各類場所消防安全設備設置標準規定，不得超過多少個？",{"A":16,"B":17,"C":18,"D":19},"1個","3 個","5 個","7 個","D",null,[],false,"本題考點：Ｐ型受信總機以數個火警分區共用一條公用線配線時，該公用線所能供應的分區數上限。\n【正解理由】依《各類場所消防安全設備設置標準》關於火警自動警報設備配線之規定，Ｐ型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數不得超過七個；共用線一旦斷線，掛在其上的分區會同時失去監視與報知，法規因而設此數量上限，本題問的正是這個法定上限值，故選 D。\n【逐項排除】\n(A) 1 個等於未採共用方式，回到各分區獨立回線的配法，且分區數為一時亦無所謂「共用」，與題目所設「數個分區共用一公用線」的前提不合。\n(B) 3 個雖落在安全側，卻不是法規所定的分區數上限，答此值等於把門檻記小。\n(C) 5 個同樣低於法定上限，是常見的干擾數值，規定並未以 5 個為界。\n(D) 7 個與「不得超過七個」之規定相符，正是本題所求的最大分區數。\n【記憶點】「Ｐ型公用線，一條最多帶七區」；超過七區就必須再拉一條公用線。","公用線之所以存在，是Ｐ型受信總機的信號傳送方式使然。Ｐ型以「一分區一固有信號」配線，每一火警分區的探測器回路原本需要一去一回兩條導線；若把各分區的回線合併為一條共用，n 個分區只需 n＋1 條而非 2n 條——七個分區由十四條降為八條，配線量近乎減半，這是實務施工採共用線的誘因。\n但共用有代價：公用線一旦斷線或接觸不良，掛在其上的所有分區會同時失去監視與報知能力，風險隨共用分區數放大。法規因此為一條公用線設下七個分區的上限，在線材成本與風險分散之間取平衡。這也解釋了Ｒ型受信總機為何沒有這項限制——Ｒ型由中繼器把各探測器的動作轉換成固有信號，以多工方式在同一對傳輸線上傳送，分區增加時配線量不會等比成長，長距離傳輸與擴充性都優於Ｐ型，代價是造價較高。\n※ 法規時點提醒：本題所涉之火警自動警報設備配線條文，在本場考試（107 年 6 月 3 日）之後曾經修正，現行條文所依循者已由「屋內線路裝置規則」改稱「用戶用電設備裝置規則」，故本詳解僅以章節級依據說明、不標註條號。\n同體系可一併記憶者：瓦斯漏氣受信總機（第 142 條）應裝置於值日室等平時有人之處所，設有防災中心時設於該中心，具有標示瓦斯漏氣發生之警報分區，操作開關距樓地板面之高度須在零點八公尺以上（座式操作者為零點六公尺）一點五公尺以下；火警自動警報設備之緊急電源（第 128 條）應使用蓄電池設備，容量能使其有效動作十分鐘以上；緊急廣播設備（第 135 條）之緊急電源則準用之。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-023","自居室任一點易於觀察識別其主要出入口，且與主要出入口之步行距離符合規定者，得免設出口標示燈、避難方向指示燈或避難指標，試問下列何者不得免設？",23,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-025","有一飯店，其三樓之樓地板面積為 1200 平方公尺，依各類場所消防安全設備設置標準規定，於設置出口標示燈時，除應使用 A 級或 B 級外，出口標示燈標示面光度應在多少燭光（cd）以上？",25,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-022","依各類場所消防安全設備設置標準規定，火警自動警報設備之緊急電源，應使用蓄電池設備，其容量能使其有效動作多少分鐘以上？",22,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，緊急供電系統之配線除依屋內線路裝置規則外，有關電源回路之配線耐燃保護，若電線裝於金屬導線管槽內，並埋設於防火構造物之混凝土內，混凝土保護厚度應為多少毫米以上？",26,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-021","依各類場所消防安全設備設置標準規定，緊急照明設備除內置蓄電池外，應連接緊急電源，其蓄電池容量應能使其持續動作 a 分鐘以上。但採蓄電池設備與緊急發電機併設方式時，其容量應能使其持續動作分別為 b 分鐘及 c 分鐘以上，請問下列何者正確？",21,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-027","依各類場所消防安全設備設置標準規定，緊急供電系統之配線除依屋內線路裝置規則外，緊急用電源回路及操作回路，應使用多少伏特耐熱絕緣電線，或同等耐熱效果以上之電線？",27,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-024",110,"差動式分布型探測器採熱電偶式時，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-024",109,"有關標示設備設在避難出口避難指標之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-024",108,"某防火構造建築物，供三溫暖洗澡區使用，面積為 130 m2，天花板高度為 3.6 m，請問下列何者為適當的探測器？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-024",106,"依各類場所消防安全設備設置標準規定，特別安全梯或緊急昇降機間排煙室之排煙設備設置排煙、進風風管時，下列何者有誤？",1785123172383]