[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-027":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-027","fire-107-1-alarm-evacuation-027",107,1,27,"依各類場所消防安全設備設置標準規定，緊急供電系統之配線除依屋內線路裝置規則外，緊急用電源回路及操作回路，應使用多少伏特耐熱絕緣電線，或同等耐熱效果以上之電線？",{"A":16,"B":17,"C":18,"D":19},"300 伏特","400 伏特","500 伏特","600 伏特","D",null,[],false,"本題考點：緊急供電系統中，緊急用電源回路及操作回路所應使用的電線耐熱絕緣等級。\n【正解理由】依《各類場所消防安全設備設置標準》關於緊急供電系統配線之規定，緊急用電源回路及操作回路，應使用六百伏特耐熱絕緣電線，或同等耐熱效果以上之電線；本題問的正是此一電線規格，故選 D。\n【逐項排除】\n(A) 300 伏特是一般低壓絕緣電線常見的標稱等級，並非本規定所要求的耐熱絕緣電線規格。\n(B) 400 伏特不是絕緣電線的標稱電壓級距，規定中亦未出現此數值，屬純干擾選項，以三相電源電壓推想即會誤選。\n(C) 500 伏特常見於絕緣電阻計的測定電壓，屬量測時施加的電壓，與電線本身的耐熱絕緣等級是不同層次的概念。\n(D) 600 伏特耐熱絕緣電線正是規定所列之規格，並允許以同等耐熱效果以上之電線替代，判準在耐熱效果而非特定品項。\n【記憶點】「電源回路與操作回路，600 伏特耐熱絕緣線」；伏特講的是電線規格，毫米與管槽講的是配線工法。","「六百伏特耐熱絕緣電線」中的六百伏特是電線的標稱使用電壓，也就是絕緣等級，而不是火災時的耐熱溫度；耐熱絕緣電線的絕緣體採用耐熱性較高的材質，受熱時仍能維持絕緣而不致短路，屬於電線本體的規格。這與耐燃保護、耐熱保護所講的配線工法是兩個層次：前者決定買什麼線，後者決定怎麼裝——電線裝於金屬導線管槽內、埋設於防火構造物之混凝土內、或改用 MI 電纜與耐燃電纜直接敷設，都屬工法層次。命題常把兩層混在一起問，看到「伏特」就是問電線規格，看到「毫米」「管槽」「混凝土」就是問工法。\n同一節還規定電氣配線應設專用回路，不得與一般電路相接，且開關應有消防安全設備別之明顯標示，用意是避免一般用電的故障或維修動作波及消防安全設備的供電，也讓救災與檢查能快速辨識。\n可延伸到第 191 條的緊急電源插座：裝設於樓梯間或緊急昇降機間等（含各該處五公尺以內之場所）消防人員易於施行救火處，且每一層任何一處至插座之水平距離在五十公尺以下；電流供應容量為交流單相一百一十伏特（或一百二十伏特）十五安培，容量約為一點五瓩以上；為接地型，裝設高度距離樓地板一公尺以上一點五公尺以下，並裝設二個於崁裝式保護箱內；應從主配電盤設專用回路，各層至少設二回路以上，每一回路連接插座數在十個以下，且該專用回路不得設漏電斷路器。伏特、安培、瓩三個數值常被合併命題。\n※ 法規時點提醒：本題所涉之緊急供電系統配線條文，於本場考試（107 年 6 月 3 日）後曾經修正，故本詳解採章節級引用、不標註條號，避免以現行條次套用於當年試題。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，緊急供電系統之配線除依屋內線路裝置規則外，有關電源回路之配線耐燃保護，若電線裝於金屬導線管槽內，並埋設於防火構造物之混凝土內，混凝土保護厚度應為多少毫米以上？",26,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-028","依各類場所消防安全設備檢修及申報作業基準規定，對火警自動警報設備進行二信號性能檢查時，有關判定方法，下列敘述何者錯誤？",28,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-025","有一飯店，其三樓之樓地板面積為 1200 平方公尺，依各類場所消防安全設備設置標準規定，於設置出口標示燈時，除應使用 A 級或 B 級外，出口標示燈標示面光度應在多少燭光（cd）以上？",25,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-029","依各類場所消防安全設備設置標準規定，有關標示設備之敘述，何者正確？",29,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-024","P 型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，依各類場所消防安全設備設置標準規定，不得超過多少個？",24,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-030","偵煙式探測器除光電式分離型外，下列裝置規定何者錯誤？",30,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-027",110,"依緊急廣播設備之揚聲器設置規定，廣播區域超過 100 平方公尺時，距揚聲器 1 公尺處所測得之音壓應為多少分貝以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-027",109,"有關緩降機支固器具之裝置，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-027",108,"依各類場所消防安全設備設置標準第 112 條，有關火警自動警報設備之火警分區劃定規定，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-027",106,"避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度，應在多少勒克司（lx）以上？",1785123172416]