[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-030":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-030","fire-107-1-alarm-evacuation-030",107,1,30,"偵煙式探測器除光電式分離型外，下列裝置規定何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"居室天花板距樓地板面高度在 2.3 公尺以下或樓地板面積在 40 平方公尺以下時，應設在居室中央為原則","探測器下端，裝設在裝置面下方 60 公分範圍內","探測器裝設於距離牆壁 60 公分以上之位置","探測器裝設於距離樑 60 公分以上之位置","A",null,[],false,"本題考點：偵煙式探測器（光電式分離型除外）之裝置位置規定，低天花板或小面積居室究竟要裝在居室中央還是出入口附近。\n【正解理由】依《各類場所消防安全設備設置標準》第 122 條第一款，居室天花板距樓地板面高度在二點三公尺以下，或樓地板面積在四十平方公尺以下時，「應設在其出入口附近」；矮而小的空間煙一形成便充滿全室，設於出入口附近可在煙流出居室前先行動作。題述以居室中央為原則與該款不符，故選 A。\n【逐項排除】\n(A) 二點三公尺以下或四十平方公尺以下之居室應設於出入口附近，以居室中央為原則之敘述與第 122 條第一款牴觸，為本題應選者。\n(B) 第 122 條第二款明定探測器下端裝設在裝置面下方六十公分範圍內，題述之數值與範圍均相符。\n(C) 第 122 條第三款要求裝設於距牆壁六十公分以上，避免牆角氣流滯留延誤感知，敘述正確。\n(D) 同條第三款一併規定距樑六十公分以上，樑會阻擋煙沿頂棚流動，敘述亦屬正確。\n【記憶點】偵煙式記「下端六十、離牆離樑六十」；矮房小間裝出入口，不裝正中央。","本標準把探測器的裝置規定分成兩層：第 115 條規範所有探測器共通的環境條件，第 120 條至第 123 條再依探測器型式分別規定。第 115 條第四款「局限型探測器以裝置在探測區域中心附近為原則」，正是本題 (A) 的陷阱來源——把局限型的中心原則誤套到偵煙式的低天花板、小面積居室情形。煙與熱的行為並不相同：天花板高度在二點三公尺以下或面積在四十平方公尺以下的居室，煙一旦生成幾乎瞬間充滿全室，中央與周邊濃度差極小，反而是煙外流的出入口最能代表全室狀態；設在出入口附近，可在煙侵入走廊前先動作，替走廊上的避難人員爭取時間。\n數值可整理成兩組對照：熱感知型（第 120 條差動式局限型、補償式局限型、定溫式局限型；第 121 條差動式分布型之空氣管與熱電偶）一律要求裝設在裝置面下方三十公分範圍內；偵煙式（第 122 條）則放寬為下端在裝置面下方六十公分範圍內，並要求距牆壁或樑六十公分以上，記法是「熱三十、煙六十」。\n光電式分離型之所以被第 122 條排除在外，是因為它以受光器與送光器間的光軸減光量偵測，並非點狀感知；第 123 條另定受光面設在無日光照射之處、與光軸平行牆壁距離六十公分以上、光軸高度在天花板等高度百分之八十以上、光軸與警戒區任一點水平距離在七公尺以下。同組條文尚常考第 122 條第五款走廊步行距離每三十公尺至少一個（第三種每二十公尺）、第六款樓梯與斜坡通道垂直距離每十五公尺至少一個。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-029","依各類場所消防安全設備設置標準規定，有關標示設備之敘述，何者正確？",29,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-031","依各類場所消防安全設備設置標準規定，公共危險物品製造場所及一般處理場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",31,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-028","依各類場所消防安全設備檢修及申報作業基準規定，對火警自動警報設備進行二信號性能檢查時，有關判定方法，下列敘述何者錯誤？",28,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-032","依各類場所消防安全設備設置標準規定，下列何者非屬消防搶救上之必要設備種類？",32,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-027","依各類場所消防安全設備設置標準規定，緊急供電系統之配線除依屋內線路裝置規則外，緊急用電源回路及操作回路，應使用多少伏特耐熱絕緣電線，或同等耐熱效果以上之電線？",27,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-033","依各類場所消防安全設備檢修及申報作業基準規定，檢查檢知器時，使用「加瓦斯試驗器」進行加瓦斯測試，對空氣之比重未滿一者應使用何種物質？",33,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-030",110,"火警自動警報設備之緊急電源，其容量能使其有效動作 A 分鐘以上；緊急廣播設備之緊急電源，其容量能使其有效動作 B 分鐘以上，其中 A 及 B 分別為：",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-030",109,"有關緊急廣播設備標示燈外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準規定相同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-030",108,"利用各種減光罩對光電式分離型探測器進行測試，以確認其火災動作試驗、不作動試驗、故障警報試驗並判定是否符合規定，下列方式何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-030",106,"在某飯店檢查瓦斯漏氣火警自動警報設備時，何項試驗必須切換成緊急電源之狀態？",1785123172450]