[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-034","fire-107-1-alarm-evacuation-034",107,1,34,"依各類場所消防安全設備檢修及申報作業基準規定，緊急照明設備在建築物總樓地板面積為 5000 平方公尺時，檢查緊急電源容量能否持續 30 分鐘之檢查數量應在多少個以上？",{"A":16,"B":17,"C":18,"D":19},"5個","10 個","15 個","20 個","C",null,[],false,"本題考點：緊急照明設備緊急電源容量三十分鐘之檢查數量，屬級距表查表題。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第十九章緊急照明設備之性能檢查，緊急電源容量應持續三十分鐘以上，其檢查數量依總樓地板面積分級查表，非按比例計算：1000 m² 以下 5 個以上、3000 m² 以下 10 個以上、6000 m² 以下 15 個以上、10000 m² 以下 20 個以上，超過 10000 m² 者為 20 個加上每增加 5000 m² 增加 5 個。本題 5000 m² 超過 3000 m²、未逾 6000 m²，落在「6000 m² 以下」級距，故選 C。\n【逐項排除】\n(A) 5 個是「1000 m² 以下」級距的數量，本題面積遠超該上限。\n(B) 10 個對應「3000 m² 以下」級距，本題 5000 m² 已超過。\n(C) 15 個對應「6000 m² 以下」級距，5000 m² 落在此級距，為本題應選者。\n(D) 20 個屬「10000 m² 以下」級距，須面積超過 6000 m² 才進入。\n【演算步驟】查表定位非公式：總面積 5000 m² 落在 3000 m² 與 6000 m² 之間 → 「6000 m² 以下」欄 → 15 個以上。\n【記憶點】1000／3000／6000／10000 對應 5／10／15／20 個，往上找第一個「以下」的格子就是答案。","這題的陷阱在於「看到面積就想套公式」。檢修基準的檢查數量是一張級距表，不是比例式：1000 平方公尺以下 5 個以上、3000 平方公尺以下 10 個以上、6000 平方公尺以下 15 個以上、10000 平方公尺以下 20 個以上，超過 10000 平方公尺者為 20 個並每增加 5000 平方公尺增加 5 個。若誤把它當成「每 1000 平方公尺抽幾個」的比例，5000 平方公尺碰巧也能湊出 15，但換成 3000 平方公尺就會算錯——級距表在 3000 那一格是 10 個。凡是選項恰好等於表中各級距的值（5、10、15、20），就要意識到這是查表題。\n為什麼採級距而非比例？緊急照明燈在大型建築物內動輒數百盞，逐盞放電三十分鐘並不可行，抽樣數量隨規模遞增但邊際遞減，才能兼顧檢查成本與可信度；超過 10000 平方公尺後改採「基數 20 個加上每 5000 平方公尺增加 5 個」的遞增式，也是同一個設計邏輯。\n同章其他常考數值：緊急電源容量應能持續三十分鐘以上；照度判定為地下建築物之地下通道，緊急照明燈在地面之水平面照度應達十勒克斯以上，其他場所應達二勒克斯以上；性能檢查項目為照度、檢查開關、保險絲類、結線接續與緊急電源五項。應設場所則見《各類場所消防安全設備設置標準》第 24 條，總樓地板面積在一千平方公尺以上建築物之居室、有效採光面積未達該居室樓地板面積百分之五者等均應設置。※ 該基準線上可得之最早版本為 109.08.21，晚於本題考試日，其級距表與本題四個選項數值完全對應，惟當年版本若另有差異，仍以考試當時版本為準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-033","依各類場所消防安全設備檢修及申報作業基準規定，檢查檢知器時，使用「加瓦斯試驗器」進行加瓦斯測試，對空氣之比重未滿一者應使用何種物質？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-035","依各類場所消防安全設備檢修及申報作業基準規定，緊急電源插座為單相交流 110 V 者，應用額定 150 V， X 安培之接地型插座。三相交流 220 V 者則適用額定 250 V，Y 安培接地型插座，並確認應無變形、損傷、顯著腐蝕或異物阻塞等，下列何者正確？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-032","依各類場所消防安全設備設置標準規定，下列何者非屬消防搶救上之必要設備種類？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-036","依各類場所消防安全設備設置標準規定，下列處所何者不得免設緊急照明設備？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-031","依各類場所消防安全設備設置標準規定，公共危險物品製造場所及一般處理場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-alarm-evacuation-037","設置避難器具時，標示其設置位置、使用方法並設置指標，下列規定何者錯誤？",37,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-034",110,"依消防安全設備及必要檢修項目檢修基準，救助袋進行開口部外觀檢查時，開口部面積之限制，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-034",109,"有關排煙設備綜合檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-alarm-evacuation-034",108,"依各類場所消防安全設備設置標準之規定，下列何種避難器具的開口面積應為高 60 公分以上，寬 60 公分以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-034",106,"在裝設定溫式感知線型探測器場所，進行回路合成阻抗試驗時，會使用下列何種檢查儀器？",1785123172510]