[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-107-1-alarm-evacuation-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-警報與避難系統消防安全設備概要-038","fire-107-1-alarm-evacuation-038",107,1,38,"依各類場所消防安全設備設置標準規定，差動式分布型及偵煙式探測器之探測區域，指探測器裝置面之四周以淨高多少公分以上之樑或類似構造體區劃包圍者？",{"A":16,"B":17,"C":18,"D":19},"30","40","60","80","C",null,[],false,"本題考點：探測區域的定義，以及差動式分布型與偵煙式探測器適用的特別淨高規定。\n【正解理由】依《各類場所消防安全設備設置標準》第 119 條，探測器之探測區域「指探測器裝置面之四周以淨高四十公分以上之樑或類似構造體區劃包圍者。但差動式分布型及偵煙式探測器，其裝置面之四周淨高應為六十公分以上」。本題問的正是但書所列的差動式分布型及偵煙式探測器，適用六十公分之標準，故選 C。\n【逐項排除】\n(A) 三十公分是探測器裝置深度的規定，例如差動式局限型等探測器下端裝設在裝置面下方三十公分範圍內，與探測區域之區劃淨高無關。\n(B) 四十公分是第 119 條本文對一般探測器所定之探測區域淨高，本題問的是但書所列的兩種探測器，不適用本文的數值。\n(C) 六十公分正是第 119 條但書對差動式分布型及偵煙式探測器所定之區劃淨高，為本題應選者。\n(D) 第 119 條就探測區域僅定四十公分與六十公分兩種淨高，八十公分並非該條所列之區劃淨高數值。\n【記憶點】探測區域淨高「一般 40、分布型與偵煙式 60」——偵測範圍越大，樑要越高才攔得住。","「探測區域」與「火警分區」是兩個常被混為一談的概念：火警分區是受信總機上一個表示窗所涵蓋的範圍，用來判斷起火位置；探測區域則是計算「這一區要裝幾個探測器」的單位，由裝置面四周的樑或類似構造體區劃出來。第 119 條把門檻定成兩級：一般探測器四十公分，差動式分布型與偵煙式六十公分。\n差別的道理在偵測機制。差動式局限型、補償式局限型與定溫式局限型靠局部熱累積動作，四十公分的樑已足以阻斷熱氣流、形成獨立的蓄熱空間；差動式分布型（空氣管式、熱電偶式、熱半導體式）以整片天花板的空氣管或感熱元件感測大範圍溫升，偵煙式則靠煙層沿天花板擴散，四十公分的樑攔不住煙與大範圍熱流，須達六十公分才認定為獨立的探測區域，否則應併為同一區域計算應設個數。\n六十公分在偵煙式的規定中反覆出現，可一起記：偵煙式探測器（光電式分離型除外）之下端應裝設在裝置面下方六十公分範圍內、探測器應裝設於距離牆壁或樑六十公分以上之位置、探測區域之區劃淨高亦為六十公分以上。相對地，差動式局限型、補償式局限型及定溫式局限型探測器之下端裝設在裝置面下方三十公分範圍內，差動式分布型之空氣管亦裝置在裝置面下方三十公分範圍內，且每一探測區域內空氣管露出部分在二十公尺以上、裝接於一個檢出器之空氣管長度在一百公尺以下；熱電偶式則以探測區域樓地板面積決定應設個數，防火構造建築物在八十八平方公尺以下至少四個，超過部分每增加二十二平方公尺增設一個。「下端深度 30 或 60 看熱式與煙式，區劃淨高 40 或 60 看局限型與分布型、煙式」是最省力的記法。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-alarm-evacuation-037","設置避難器具時，標示其設置位置、使用方法並設置指標，下列規定何者錯誤？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，緊急廣播設備之啟動裝置應符合 CNS 10522 之規定，且設在距樓地板高度 X 公尺以上 Y 公尺以下範圍內，下列何者正確？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-alarm-evacuation-036","依各類場所消防安全設備設置標準規定，下列處所何者不得免設緊急照明設備？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-alarm-evacuation-040","依各類場所消防安全設備檢修及申報作業基準規定，緩降機應以測量下降距離及下降時間，計算出下降速度，最大下降速度應在每秒多少公分以內？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-alarm-evacuation-035","依各類場所消防安全設備檢修及申報作業基準規定，緊急電源插座為單相交流 110 V 者，應用額定 150 V， X 安培之接地型插座。三相交流 220 V 者則適用額定 250 V，Y 安培接地型插座，並確認應無變形、損傷、顯著腐蝕或異物阻塞等，下列何者正確？",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-108-1-alarm-evacuation-001","某一新建建築物地面六層、地下二層，用途為辦公室，每層樓地板面積為 400 平方公尺，設置火警自動警報系統，假設 1 樓發生火警時，依各類場所消防安全設備設置標準規定，其鳴動方式為何？",108,[53,57,61,64],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-038",110,"特別安全梯排煙室設置直接面向戶外之窗戶時，窗戶之有效開口面積應在多少平方公尺以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-038",109,"有關應設置緊急照明設備之場所，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":62,"year":51,"stem":63,"number":13},"fire-108-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，特別安全梯及緊急昇降機間兼用排煙室時排煙閘門面積為 4 m2，忽略溫度的影響，測試點量得的平均風速 V(m\u002Fsec)應為多少以上為合格？",{"webId":65,"year":66,"stem":67,"number":13},"fire-106-1-alarm-evacuation-038",106,"依各類場所消防安全設備設置標準規定，避難指標設於出入口裝設應距樓地板面的高度要求為多少？",1785123172562]