[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-fire-law-020":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-消防法規概要-020","fire-107-1-fire-law-020",107,1,20,"依各類場所消防安全設備設置標準之規定，特別安全梯或緊急昇降機間排煙室之排煙設備，其排煙機、進風機之排煙量、進風量應在每秒 a 立方公尺（兼用時，每秒 b 立方公尺）以上，且可隨排煙口、進風口開啟而自動啟動。a、b 各為何值？",{"A":16,"B":17,"C":18,"D":19},"a=4；b=6","a=5；b=7","a=6；b=9","a=7；b=7","A",null,[],false,"本題考點：特別安全梯或緊急昇降機間排煙室之排煙機、進風機風量下限，單獨使用每秒四立方公尺、兼用每秒六立方公尺。\n【正解理由】依《各類場所消防安全設備設置標準》第 189 條，特別安全梯或緊急昇降機間排煙室之排煙設備，其排煙機、進風機之排煙量、進風量應在每秒四立方公尺以上；兩者兼用（即同一排煙室兼供特別安全梯與緊急昇降機間使用）時，應在每秒六立方公尺以上，並應能隨排煙口、進風口之開啟而自動啟動。故 a=4、b=6，故選 A。\n【逐項排除】\n(A) 正確，四與六的組合即條文所定單獨用與兼用之風量下限，且兼用時因防護空間加大而提高風量。\n(B) 五與七並非條文數值，屬純干擾項；本條並無以五立方公尺為基準之規定。\n(C) 六與九是把單獨用誤記成兼用值後再等比放大，兼用值為六而非九。\n(D) 七與七將單獨用與兼用設為同值，忽略兼用時防護體積增加須提高風量的立法設計，數值亦非條文所定。\n【記憶點】排煙室風量「單獨四、兼用六」，兼用多兩立方公尺。","特別安全梯與緊急昇降機間的排煙室，功能定位與一般居室排煙完全不同：一般居室排煙是把已生成的煙排掉以維持可視高度；排煙室排煙則是「防止煙侵入」，要在避難層以外各樓層形成正壓或足夠的氣流方向，確保避難者進入排煙室後煙不會跟著灌進樓梯間，讓垂直逃生動線與消防隊的攻擊據點保持無煙。因此條文除了規定風量，還要求排煙口、進風口開啟時排煙機與進風機自動啟動，並在必要處設手動啟動裝置，避免因偵測失效而失去防護。兼用之所以要求每秒六立方公尺，是因為同一排煙室同時服務特別安全梯與緊急昇降機間時，開口面積與防護容積都變大，維持相同氣流條件所需的風量隨之增加。\n同條相關常考數值可一併整理：排煙口、進風口之開口面積各須在二平方公尺以上（兼用時三平方公尺以上）；進風口設於排煙室之下方，排煙口設於上方，形成由下而上的氣流；排煙機、進風機應能連續運轉三十分鐘以上；電源應接至緊急電源。至於一般居室排煙設備則屬第 188 條體系，排煙機每分鐘排煙量在一二〇立方公尺以上，且防煙區劃面積每平方公尺每分鐘一立方公尺以上，並以較大者為準，與本條的「每秒」單位不同，答題時務必先確認題幹問的是排煙室還是居室，單位是每秒還是每分鐘。\n易混淆對照：排煙設備與防煙垂壁常被併考——防煙垂壁是被動的區劃構件，用以把煙侷限於防煙區劃內爭取排煙效率；排煙機則是主動排出。另需區辨排煙室（附室）與特別安全梯本體，風量規定針對排煙室，樓梯間本身不另設排煙機。\n※ 本條數值歷年沿用，惟排煙相關條文曾配合建築技術規則調整用語，引用時以現行條文為準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-fire-law-019","依各類場所消防安全設備檢修及申報作業基準之規定，有關室內消防栓加壓送水裝置的減壓措施性能檢查，若公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之消防栓，其放水壓力應在 a kgf\u002Fcm2 以上、b kgf\u002Fcm2 以下。a、b 各為何值？",19,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-fire-law-021","依消防法之規定，下列何者錯誤？",21,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-fire-law-018","依各類場所消防安全設備檢修及申報作業基準之規定，供第四類公共危險物品之顯著滅火困難場所之冷卻撒水設備的加壓送水裝置，除非設有保壓措施，否則，啟動後 a 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 b 公尺以下。a、b 各為何值？",18,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-fire-law-022","下列場所，何者不屬於消防法施行細則所定一定規模以上供公眾使用建築物？",22,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-fire-law-017","依各類場所消防安全設備檢修及申報作業基準之規定，瓦斯漏氣檢知器的設置位置，當瓦斯對空氣之比重未滿 1 時，檢知器下端，應裝設在天花板下方 a 公分範圍內；瓦斯對空氣之比重大於 1 時，檢知器上端，應裝設在距樓地板面 b 公分範圍內。a、b 各為何值？",17,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-fire-law-023","依消防法施行細則之規定，防火管理人應為管理或監督層次人員，並經中央消防機關認可之訓練機構或直轄市、縣（市）消防機關講習訓練合格領有證書始得充任。其講習訓練時數，初訓不得少於 X 小時；複訓不得少於 Y 小時，X、Y 分別為多少？",23,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-020",111,"依消防法規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-020",110,"依法應裝設火警自動警報設備之建築物，其裝設受信總機及探測器等相關規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-020",109,"依可燃性高壓氣體儲存場所防護牆設置基準之規定，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-law-020",108,"依據消防設備師及消防設備士管理辦法規定，消防設備師及消防設備士，自取得證書日起每 3 年應接受講習一次或取得累計積分達多少分以上之訓練證明文件？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-020",106,"依據各類場所消防安全設備設置標準規定，設置於可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽之滅火器，其滅火效能值規定，下列何者正確？",1785123159496]