[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-fire-law-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-消防法規概要-036","fire-107-1-fire-law-036",107,1,36,"依防火牆及防火水幕設置基準之規定，防火水幕設備之水源應連結加壓送水裝置，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"加壓送水裝置應採用消防幫浦","應為專用。但與其他消防設備並用，無妨礙其他設備之性能時，不在此限","應連接緊急電源。但加壓送水裝置之驅動系統為引擎或渦輪機者，應設緊急電源","加壓送水裝置啟動後 6 分鐘內應能形成水幕","C",null,[],false,"本題考點：《防火牆及防火水幕設置基準》中防火水幕設備加壓送水裝置之要件,題目問「錯誤」者。\n【正解理由】依《防火牆及防火水幕設置基準》關於加壓送水裝置之規定,加壓送水裝置應連接緊急電源,但其驅動系統為引擎或渦輪機者,不在此限;因引擎與渦輪機本身即不依賴市電運轉,停電時仍能啟動,故免再設緊急電源。C 卻寫成「驅動系統為引擎或渦輪機者,應設緊急電源」,把但書的免除規定倒過來寫成加重規定,與基準不符,故選 C。\n【逐項排除】\n(A) 正確。防火水幕設備之加壓送水裝置應採用消防幫浦,以確保揚程與出水量符合水幕形成所需的水力條件。\n(B) 正確。加壓送水裝置應為專用,但與其他消防設備並用而無妨礙其他設備性能時,得不受此限,屬合理的但書設計。\n(C) 錯誤。但書的法律效果是「不在此限」即免設,選項寫成「應設緊急電源」與原意相反,為本題答案。\n(D) 正確。加壓送水裝置啟動後六分鐘內應能形成水幕,此為水幕有效阻隔輻射熱與延燒的時間要求。\n【記憶點】但書關鍵字看「不在此限」:引擎或渦輪機驅動就免設緊急電源;水幕須於啟動後六分鐘內形成。","防火水幕設備的功能定位與一般滅火設備不同:它不以撲滅火勢為目的,而是在建築物或區劃之間形成連續水膜,吸收並阻隔輻射熱、冷卻構件,達到防止延燒的效果,因此《防火牆及防火水幕設置基準》把它與防火牆並列,視為區劃防火的替代或補強手段。理解這個定位,就能推導出許多條文要件:水幕必須「連續且不中斷」,所以水源容量與加壓送水裝置的可靠度要求高;水幕必須「及時形成」,所以有啟動後時間上限的規定;水幕的目的是撐住區劃,所以電源不能是火災時最先失效的市電。\n\n緊急電源但書的邏輯值得單獨記憶。消防法規中凡涉及動力來源,一律追問「這個驅動方式在停電時還能不能動」:電動機驅動的消防幫浦依賴市電,必須另接緊急電源;引擎(柴油引擎)或渦輪機自帶燃料與獨立起動系統,本身即等同緊急電源,再要求外接緊急電源並無實益。命題者最喜歡把「不在此限」改寫成「應設」或「亦同」,這是設置標準與各類設置基準通用的陷阱手法,答題時務必逐字檢視但書的法律效果方向。\n\n「專用但得並用」的設計同樣是比例原則的展現:原則上專用可避免其他設備同時動作時搶水搶壓,但若經水力計算確認並用不影響各設備性能,法規容許共用以降低成本。這種「原則從嚴、例外附條件放寬」的句型,在室內消防栓、自動撒水設備的水源與加壓送水裝置條文中反覆出現,可以整組一起記。\n\n延伸辨析:防火水幕與水霧滅火設備、自動撒水設備的開放式撒水頭在硬體上有相似之處,但目的不同——水霧著重滅火與抑制油類火災、開放式撒水設備著重全區同時放水滅火,防火水幕則專責阻隔延燒,答題時先鎖定題幹引用的法規名稱,即可判斷該套用哪一組數值與要件。\n\n複習建議:把「應…。但…者,不在此限」的句型整理成清單,逐條確認但書指向免除或加重,這類反向改寫在近年試題出現頻率極高。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-fire-law-035","依各類場所消防安全設備檢修及申報作業基準之規定，有關瓦斯漏氣火警自動警報設備性能檢查，下列何者錯誤？",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-fire-law-037","依防火牆及防火水幕設置基準之規定，有一儲槽其水平剖面最大半徑為 5 公尺，內裝有公共危險物品，該公共危險物品之閃火點為攝氏八十度，則假想火面高度為多少公尺？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-fire-law-034","依各類場所消防安全設備設置標準之規定，下列何者非屬甲類場所？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-fire-law-038","依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，呼水裝置應有多少公升以上之有效儲存量？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-fire-law-033","依各類場所消防安全設備設置標準之規定，防災中心樓地板面積應在多少平方公尺以上？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-fire-law-039","依建築技術規則建築設計施工編之規定，常時關閉式防火門之單一門扇面積不得超過多少平方公尺？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-036",111,"受託辦理檢修之檢修機構應依相關規定檢修完成消防安全設備後，依照消防安全設備檢修及申報辦法規定，應附加檢修完成標示檢修機構專業樣式以何種顏色為底？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-036",110,"依建築技術規則建築設計施工編規定，夾層係指夾於樓地板與天花板間之樓層；同一樓層內夾層面積之和，超過多少平方公尺，視為另一樓層？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-036",109,"依避難器具支固器具及固定部之結構、強度計算及施工方法之規定，裝置避難器具固定部材料，使用直徑 1 公分錨定螺栓，設定試驗荷重 500 公斤力（kgf）時，則鎖緊扭力應為多少公斤力\u002F公分（kgf\u002Fcm）？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-law-036",108,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，下列何者不符合呼水裝置之規定？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-036",106,"下列有關各類場所消防安全設備檢修及申報作業基準行政函釋之敘述，何者錯誤？",1785123159665]