[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-fire-science-018":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"火災學概要","fire-science","火災學 · Fire Science","火災學",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-火災學概要-018","fire-107-1-fire-science-018",107,1,18,"已知木造倉庫高 6 公尺，如延燒係數為 0.15，依木造建築物火災溫度標準曲線，其鄰棟建築物之理論安全距離應在多少公尺以上？",{"A":16,"B":17,"C":18,"D":19},"5.4 公尺","6.3 公尺","9 公尺","12.1 公尺","B",null,[],false,"本題考點：木造建築物火災溫度標準曲線所導出的火災等溫線關係式 h＝p·d²，用來求鄰棟建築物的理論安全距離。\n【正解理由】火災等溫線以失火建築物外牆最下緣為基準點，把鄰棟牆面上溫度相同的各點連成曲線，可用 h＝p·d² 表示：h 為鄰棟建築物高度（公尺）、d 為距火源之水平距離（公尺）、p 為延燒係數。移項得 d＝√(h\u002Fp)，代入 h＝6 公尺、p＝0.15，得 d≈6.32 公尺，理論安全距離須在此值以上，故選 B。\n【逐項排除】\n(A) 5.4 公尺：代回公式相當於 h＝0.15×5.4²≈4.4 公尺高的鄰棟，對 6 公尺高者間隔不足。\n(B) 6.3 公尺：即 √(6÷0.15)＝√40≈6.32 公尺，與公式解相符。\n(C) 9 公尺：代回得 h＝0.15×9²＝12.15 公尺，那是約 12 公尺高鄰棟才需要的距離。\n(D) 12.1 公尺：代回得 h≈0.15×12.1²≈22 公尺，遠超出本題條件。\n【演算步驟】h＝p·d² → d＝√(h\u002Fp)＝√(6 公尺÷0.15)＝√(40 公尺²)≈6.32 公尺 → 取 6.3 公尺以上。\n【記憶點】延燒係數題先寫 h＝pd²，答案就是「√(高度÷係數)」。","火災等溫線的觀念來自對木造建築物火災的實測：以失火建築物外牆最下緣為基準點，量測鄰棟牆面各位置的受熱溫度，再把溫度相同的點連起來，形狀近似拋物線，可用 h＝p·d² 描述。式中 p 稱延燒係數，是把火災規模、開口條件與可燃物量濃縮而成的經驗參數，無因次；p 愈大代表輻射熱愈強，同樣高度所需的間隔就愈遠。\n木構造的延燒危險界限溫度一般取 250℃，即木材表面持續受熱到約 250℃ 就有起火延燒之虞，等溫線公式描述的正是「這條界限溫度落在離火源多遠的位置」。因此 d＝√(h\u002Fp) 求出的是理論安全距離；式中的 h 是鄰棟建築物高度而非火源高度，因為鄰棟愈高，愈高處的牆面愈容易被等溫線掃到，需要的水平距離也就愈長。\n速算與同型題：係數固定為 0.15 時，鄰棟高 6 公尺→√40≈6.3 公尺、高 9 公尺→√60≈7.75 公尺、高 15 公尺→√100＝10 公尺，可整組背起來，考題只是換高度。若改給距離反求高度，直接用 h＝pd² 代回即可。\n易混淆對照：木造建築物火災溫度標準曲線的特徵是升溫極快、約十分鐘前後達到最高溫，隨後可燃物耗盡而急速衰減，屬短時間高強度輻射；耐火建築物所用的標準時間溫度曲線則是持續高溫、時間拉長，兩者用途不同，本題問「依標準曲線」求距離即指等溫線公式。另須分清「理論安全距離」是輻射熱模型的計算值，與建築法規所定防火間隔、外牆開口防火設備等規定屬於不同層次的要求，命題常以此設陷。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-fire-science-017","有關地下建築物火災之敘述，下列何者錯誤？",17,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-fire-science-019","電線因火災燒熔而短路所形成之熔珠，稱為下列何者？",19,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-fire-science-016","下列何者為海龍替代品滅火藥劑 FE-13 之分子式？",16,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-fire-science-020","為防止由窗口噴出的火焰向大樓上層延燒，下列措施何者錯誤？",20,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-fire-science-015","有一火場之消光係數為 2 m-1，請問發光物體之能見度為多少公尺？",15,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-fire-science-021","油罐車在灌裝作業中，其累積電壓為 16 kV（其體積為 20 m3，電容為 1000 pF），試估算此作業所產生靜電能量為多少毫焦耳（mj）？",21,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-science-018",111,"下列何者非電線走火之原因？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-science-018",110,"根據「危害物質災害現場搶救標準作業程序」之規定，其首要工作為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-science-018",109,"化學災害搶救程序 HAZMAT 之說明，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-fire-science-018",108,"當氣體進行「壓縮比=2」的斷熱壓縮時，下列對該氣體的敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-science-018",106,"有關煙囪效應之敘述，下列何者錯誤？",1785123163641]