[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-005":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-005","fire-107-1-water-chemical-005",107,1,5,"泡沫滅火設備使用泡沫噴頭時，每一放射區域之樓地板面積規定應為何？",{"A":16,"B":17,"C":18,"D":19},"50 平方公尺以上，100 平方公尺以下","100 平方公尺以上，200 平方公尺以下","占樓地板面積 1\u002F3 以上","至少 200 平方公尺","A",null,[],false,"本題考點：泡沫滅火設備放射區域的面積範圍，並須辨別泡沫噴頭與泡水噴頭的不同規定。\n【正解理由】依《各類場所消防安全設備設置標準》第 75 條第一款，使用泡沫噴頭時，每一放射區域在樓地板面積五十平方公尺以上一百平方公尺以下。條文同時設下限與上限：下限確保單一放射區域具備足夠的滅火規模、不致把防護面積切得太碎；上限則限制單區面積過大而使泡沫水溶液供給量與加壓送水裝置出水量無法負荷。故選 A。\n【逐項排除】\n(A) 正確。五十平方公尺以上、一百平方公尺以下，與條文逐字相符。\n(B) 錯誤。一百至二百平方公尺並無此規定；二百平方公尺出現在同條第二款泡水噴頭之「至少二百平方公尺」。\n(C) 錯誤。占樓地板面積三分之一以上，是第 75 條第二款針對泡水噴頭放射區域的規定，不適用於泡沫噴頭。\n(D) 錯誤。至少二百平方公尺同屬泡水噴頭之要件，且該款尚須併同占樓地板面積三分之一以上一起判斷，單獨引用亦不完整。\n【記憶點】泡沫噴頭一區五十至一百平方公尺；泡水噴頭占三分之一以上且至少二百平方公尺。","泡沫噴頭與泡水噴頭是本節最容易混淆的一組。泡水噴頭出泡量大、以大量泡沫覆蓋高火載量空間，依第 71 條第一款用於飛機庫等場所，樓地板面積每八平方公尺設置一個；泡沫噴頭則依同條第二款用於室內停車空間或汽車修理廠等場所，樓地板面積每九平方公尺設置一個。兩者的放射區域規定也隨之分流：泡沫噴頭走五十至一百平方公尺的絕對面積區間，泡水噴頭走三分之一比例加二百平方公尺的門檻。記憶方法是把「八平方公尺一個、三分之一、二百平方公尺」綁成泡水噴頭一組，「九平方公尺一個、五十至一百平方公尺」綁成泡沫噴頭一組。第 71 條另規定放射區域內任一點至泡沫噴頭之水平距離在二點一公尺以下，這個數值與一般反應型撒水頭相同，可一併記。\n水源與加壓送水裝置是同一條文串下來的延伸考點。依第 76 條第一款，使用泡沫頭時，應以核算所得之最低放射量，在最大一個泡沫放射區域能繼續放射二十分鐘以上；同條第二項並要求計算之水溶液量應加算充滿配管所需之泡沫水溶液量，且加算總量的百分之二十作為餘裕。依第 77 條，使用消防幫浦時，出水量在泡沫放射區域有二區域以上時，以最大一個泡沫放射區域之最低出水量加倍計算；出水壓力則須核算最末端一個放射區域全部泡沫噴頭放射壓力均達每平方公分一公斤以上或 0.1MPa 以上。放射區域面積之所以設上限，正是為了讓這條出水量算式不致失控。\n公共危險物品場所另有一套：依第 217 條，採泡沫噴頭方式者，防護對象表面積每九平方公尺設置一個泡沫噴頭，每一放射區域在一百平方公尺以上，表面積未滿一百平方公尺時依實際表面積計；依第 220 條第一款，使用泡沫頭放射時水源以最大泡沫放射區域繼續射水十分鐘以上之水量計，移動式者則為四具瞄子同時放水三十分鐘。一般場所是「五十至一百、二十分鐘」，公共危險物品場所是「一百以上、十分鐘」，方向恰好相反，作答前先確認題幹章別。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-004","移動式泡沫滅火設備之水源容量，依規定為 2 具泡沫瞄子同時放水多少分鐘之水量以上？",4,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-006","泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",6,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-003","水霧滅火設備之水源容量規定，下列何者正確？",3,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-007","自動撒水設備應裝置適當之流水檢知裝置，有關流水檢知裝置之設置規定，下列何者正確？",7,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-002","有關連結送水管之送水口設置規定，下列何者錯誤？",2,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-008","水滅火系統中，以立管連接屋頂水箱使配管平時充滿水，屋頂水箱之容量要求，下列何者錯誤？",8,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-005",111,"有關移動式泡沫滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-005",110,"消防幫浦加壓送水裝置之啟動用水壓開關裝置，下列規定何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-005",109,"某電信機械室設置二氧化碳全區放射滅火設備，其核算之滅火藥劑量應於多少時間內全部放射完畢？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-005",108,"開放式自動撒水設備之自動及手動啟動裝置，下列設置規定何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-005",106,"某一鍋爐房之長寬高分別為 8 m、5 m 及 4 m，若設置全區放射 CO2 滅火設備，其所有開口皆可在放射前自動關閉，試問所需 CO2 藥劑量至少應為多少公斤？",1785123167802]