[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-008":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-008","fire-107-1-water-chemical-008",107,1,8,"水滅火系統中，以立管連接屋頂水箱使配管平時充滿水，屋頂水箱之容量要求，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"第一種室內消防栓在 0.5 立方公尺以上","第二種室內消防栓在 0.3 立方公尺以上","室外消防栓在 1 立方公尺以上","自動撒水設備在 1 立方公尺以上","C",null,[],false,"本題考點：以立管連接屋頂水箱使配管平時充滿水的各水系統，其屋頂水箱法定容量。\n【正解理由】依《各類場所消防安全設備設置標準》第 32 條第三款第一目，室內消防栓設備屋頂水箱之水量，第一種消防栓有零點五立方公尺以上、第二種消防栓有零點三立方公尺以上，與其他滅火設備並用時水量應取其最大值；另依第 44 條第三款，自動撒水設備立管連接屋頂水箱時，屋頂水箱之容量在一立方公尺以上。至於室外消防栓設備，並無「立管連接屋頂水箱且容量在一立方公尺以上」之規定，其防護範圍在建築物外周、不以立管貫穿各層，自無以屋頂水箱維持立管平時充水的設計需求。題目問錯誤者，故選 C。\n【逐項排除】\n(A) 敘述正確。第一種室內消防栓屋頂水箱水量零點五立方公尺以上。\n(B) 敘述正確。第二種室內消防栓屋頂水箱水量零點三立方公尺以上，較第一種為小，與其放水量較低相稱。\n(C) 敘述錯誤，即為本題答案。一立方公尺是自動撒水設備屋頂水箱之容量，被移植到室外消防栓設備而生誤。\n(D) 敘述正確。自動撒水設備立管連接屋頂水箱時，容量在一立方公尺以上。\n【記憶點】屋頂水箱容量：第一種零點五、第二種零點三、自動撒水一點零立方公尺；室外消防栓不在這張表裡。","屋頂水箱不是滅火水源，而是「保壓充水」的裝置。第 32 條第一款第六目要求立管連接屋頂水箱、重力水箱或壓力水箱，使配管平時充滿水，目的有三：其一，避免立管內存在空氣柱，使用時不必先排空氣即可立即出水，縮短起動時延；其二，維持管內靜水壓，便於平時以壓力變化偵知漏水；其三，在加壓送水裝置尚未起動的短暫空檔提供初期水量。理解這個定位，就能明白容量為何訂得這麼小——零點五立方公尺只有五百公升，以第一種室內消防栓每分鐘一百三十公升的放水量計，連四分鐘都撐不到，本來就不是拿來滅火的。\n三個數值的大小順序有其道理：第一種室內消防栓立管管徑在六十三毫米以上、放水量每分鐘一百三十公升，管內容積與需求都較大，故訂零點五立方公尺；第二種立管管徑在五十毫米以上、放水量較低，故訂零點三立方公尺；自動撒水設備管網遍布全樓層、支管密布，充水體積遠大於消防栓立管，故訂一立方公尺。第 32 條第三款第一目並明定與其他滅火設備並用時水量應取其最大值，而不是相加，這一句常被出成陷阱題。同款尚要求屋頂水箱採取有效之防震措施，斜屋頂建築物則得免設。\n配管規定一併整理：立管應為專用，但與室外消防栓、自動撒水設備及連結送水管等滅火系統共用而無礙功能者不在此限；管材須符合 CNS 六四四五配管用碳鋼鋼管、四六二六壓力配管用碳鋼鋼管、六三三一配管用不銹鋼鋼管或具同等以上強度、耐腐蝕性及耐熱性者，或經中央主管機關認可之合成樹脂管；管徑依水力計算配置，但立管與連結送水管共用時管徑在一百毫米以上；立管應裝置於不受外來損傷及火災不易殃及之位置並採防震措施。止水閥應以明顯方式標示開關狀態，逆止閥標示水流方向。第 44 條則規定自動撒水設備之配管、配件及屋頂水箱除準用第 32 條第一款、第二款外，另有乾式與預動式二次側配管的防腐與洩水要求。至於幫浦、電動機、附屬裝置及配管摩擦損失之計算，依第 234 條由中央消防機關另定，屬另一套技術規範。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-007","自動撒水設備應裝置適當之流水檢知裝置，有關流水檢知裝置之設置規定，下列何者正確？",7,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-009","某一學校教學大樓每一樓層皆設有第一種室內消防栓 3 具，則其水源容量應為多少立方公尺？",9,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-006","泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",6,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-010","第一種室內消防栓採用消防幫浦做為加壓送水裝置時，假設水帶摩擦損失水頭為 3 m，配管磨擦損失水頭為 7 m，落差為 30 m，則依規定，幫浦的全揚程應為多少公尺？",10,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-005","泡沫滅火設備使用泡沫噴頭時，每一放射區域之樓地板面積規定應為何？",5,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-011","加壓式乾粉滅火設備，於啟動裝置動作後，為使儲存容器壓力達設定壓力始開啟放出閥，應設置何種裝置？",11,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-008",111,"固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，發泡倍率應在幾倍以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-008",110,"消防搶救上之必要設備中，連結送水管之送水口設置，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-008",109,"預動式自動撒水設備竣工測試進行放水試驗時，開放末端查驗閥後，應在多久時間內正常放水？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-008",108,"移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-008",106,"乾粉滅火設備進行性能檢查時，滅火藥劑檢查注意事項中，溫度超過Ｘ℃以上，濕度超過Ｙ%以上時，應暫停檢查，Ｘ及Ｙ分別為：",1785123167833]