[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-009","fire-107-1-water-chemical-009",107,1,9,"某一學校教學大樓每一樓層皆設有第一種室內消防栓 3 具，則其水源容量應為多少立方公尺？",{"A":16,"B":17,"C":18,"D":19},"7.8","5.2","9.0","6.0","B",null,[],false,"本題考點：室內消防栓設備水源容量的核算式——放水量×繼續放水時間×消防栓支數上限。\n【正解理由】依《各類場所消防安全設備設置標準》第 36 條，室內消防栓設備之水源容量，應在「裝置室內消防栓最多樓層之全部消防栓繼續放水二十分鐘之水量以上」，同條並明定該樓層內全部消防栓數量超過二支時，以二支計算之。第一種室內消防栓每支放水量在每分鐘一百三十公升以上，故該層雖設 3 具仍以 2 支計：130 L\u002Fmin × 2 支 × 20 min ＝ 5,200 L ＝ 5.2 m³，故選 B。\n【逐項排除】\n(A) 7.8 係把 3 具全部計入（130×3×20＝7,800 L），忽略「超過二支以二支計算」的上限。\n(B) 5.2 正確，即 2 支×130 L\u002Fmin×20 min 之水量。\n(C) 9.0 係誤取幫浦出水量每支每分鐘一百五十公升並以 3 支計（150×3×20＝9,000 L）；出水量是幫浦規格，不是水源容量的核算基準。\n(D) 6.0 同樣誤取每分鐘一百五十公升，只是改以 2 支計（150×2×20＝6,000 L）。\n【記憶點】第一種室內消防栓水源＝130×2×20＝5.2 立方公尺，「一三○、兩支、二十分」一組背。","第 36 條把水源容量寫成三段式：時間固定二十分鐘，支數以「裝置室內消防栓最多樓層」為準且封頂二支，放水量則回到各消防栓本身的規格。封頂二支的理由是同一樓層火災時不會全部消防栓同時使用，取兩線水射水已足以應付初期滅火，避免為滿足帳面水源而蓋出不合比例的蓄水池。\n同條第二項另定消防用水與普通用水合併使用者，應採取必要措施確保水源容量在有效水量範圍內——水池底部沉泥層與吸水管吸不到的死水不列入計算；第三項則允許水源與同章其他滅火設備併設，但總容量應在各滅火設備應設水量之合計以上，這是常見的申論延伸點。\n易混淆對照：一般場所走第 36 條（二十分鐘、上限二支）；公共危險物品等場所依第 209 條整組加嚴，室內消防栓放水壓力在每平方公分三點五公斤以上、放水量在每分鐘二百六十公升以上、水源容量為繼續放水三十分鐘之水量，且超過五支時以五支計算，同條並把緊急電源供電容量拉長到四十五分鐘。屋頂水箱又是另一個水量，依第 32 條第三款，第一種消防栓有零點五立方公尺以上、第二種消防栓有零點三立方公尺以上，與本題的水源容量分屬兩個概念，不可相加或互換。水霧滅火設備則採定值制，依第 64 條水源容量保持二十立方公尺以上，放射區域在二區域以上者保持四十立方公尺以上。\n另須留意第 36 條的支數上限是「裝置室內消防栓最多樓層之全部消防栓」，也就是逐層比較後取支數最多的那一層，不是全棟支數加總；題目常以「每一樓層皆設 N 具」的敘述誘導考生把各層相加，實際上只要比出最多的一層再套上限即可。同一考點會反向命題：給水源容量反求可設支數，或改問第二種消防栓之水源，代入該型消防栓的放水量規格於同一式即可。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-008","水滅火系統中，以立管連接屋頂水箱使配管平時充滿水，屋頂水箱之容量要求，下列何者錯誤？",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-010","第一種室內消防栓採用消防幫浦做為加壓送水裝置時，假設水帶摩擦損失水頭為 3 m，配管磨擦損失水頭為 7 m，落差為 30 m，則依規定，幫浦的全揚程應為多少公尺？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-007","自動撒水設備應裝置適當之流水檢知裝置，有關流水檢知裝置之設置規定，下列何者正確？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-011","加壓式乾粉滅火設備，於啟動裝置動作後，為使儲存容器壓力達設定壓力始開啟放出閥，應設置何種裝置？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-006","泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-012","設置乾粉滅火設備時，全區及局部放射之緊急電源應為自用發電設備或蓄電池設備，其容量應能使設備有效動作多久以上？",12,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-009",111,"泡沫滅火設備之減水警報裝置進行性能檢查時，當呼水槽水量減少到多少時，應發出警報？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-009",110,"依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-009",109,"進行低發泡水成膜泡沫放射試驗時，其 25%還原時間應在多久時間以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-009",108,"有一總機室，設置二氧化碳滅火設備，採全區放射方式，其每立方公尺防護區域所需滅火藥劑量為多少公斤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-009",106,"如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",1785123167844]