[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-010":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-010","fire-107-1-water-chemical-010",107,1,10,"第一種室內消防栓採用消防幫浦做為加壓送水裝置時，假設水帶摩擦損失水頭為 3 m，配管磨擦損失水頭為 7 m，落差為 30 m，則依規定，幫浦的全揚程應為多少公尺？",{"A":16,"B":17,"C":18,"D":19},"40","44","57","65","C",null,[],false,"本題考點：室內消防栓採消防幫浦時的全揚程計算式，以及各類設備加算定值（17／25／10 公尺）的辨識。\n【正解理由】依《各類場所消防安全設備設置標準》關於室內消防栓加壓送水裝置之規定，採消防幫浦者，幫浦全揚程＝消防水帶摩擦損失水頭＋配管摩擦損失水頭＋落差＋17 公尺（H＝h1＋h2＋h3＋17 m）；末項 17 公尺是為確保最遠處瞄子仍維持規定放水壓力而加的定值。代入題給數值：3 m＋7 m＋30 m＋17 m＝57 m，故選 C。\n【逐項排除】\n(A) 40 m 只加總 3＋7＋30，漏掉規定加算的 17 公尺定值。\n(B) 44 m 係把定值誤換成連結送水管的消防水帶摩擦損失水頭四公尺（第 184 條第二款），該值與室內消防栓幫浦全揚程無關。\n(C) 57 m 正確，3＋7＋30＋17＝57。\n(D) 65 m 係誤用室外消防栓的定值：依第 42 條，室外消防栓幫浦全揚程加算二十五公尺，3＋7＋30＋25＝65。\n【記憶點】室內 17、室外 25、自動撒水 10，三個定值分開背，題目問哪一種就加哪一個。","三個定值不是憑空訂的，而是各設備「規定放水壓力」換算成水頭的結果：水力學上 1 kgf\u002Fcm² 約等於 10 公尺水柱（1 kgf\u002Fcm²≒0.1 MPa≒10 m 水頭）。室內消防栓瞄子放水壓力要求 1.7 kgf\u002Fcm² 以上，換算即 17 公尺；室外消防栓要求 2.5 kgf\u002Fcm² 以上，換算即 25 公尺，故第 42 條的壓力水箱寫成必要壓力＝消防水帶摩擦損失壓力＋配管摩擦損失壓力＋落差＋2.5 kgf\u002Fcm²；自動撒水設備依第 58 條，幫浦全揚程＝配管摩擦損失水頭＋落差＋10 公尺，對應撒水頭 1 kgf\u002Fcm² 的放水壓力，且該條的撒水頭計算式不含消防水帶摩擦損失水頭，因為撒水頭是固定配管出水、沒有水帶。把「壓力式」與「水頭式」兩種寫法對照著背，就不會加錯定值。\n加壓送水裝置有三種做法可擇一，同一組定值換不同載體：重力水箱以高度差供壓，條文寫「必要落差」；壓力水箱以箱內空氣（占水箱容積三分之一以上）加壓，寫「必要壓力」，單位改為公斤／平方公分，並須設空氣壓縮機且與緊急電源相連接、壓力及液面降低時能自動補充加壓；消防幫浦則寫「全揚程」，且應為專用、連接緊急電源。\n出水量與全揚程是幫浦的兩個規格，常同題出現：室外消防栓依第 42 條，一支消防栓在每分鐘四百公升以上，全部消防栓數量超過二支時以二支計算；消防專用蓄水池依第 186 條，全揚程＝落差＋配管摩擦損失水頭＋15 公尺。減壓門檻亦為考點，第 42 條規定室外消防栓瞄子放水壓力超過每平方公分六公斤或 0.6 MPa 時應採有效減壓措施，第 58 條則規定撒水頭放水壓力應在每平方公分十公斤以下或 1 MPa 以下。反向命題時會給全揚程反求容許落差，移項即得。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-009","某一學校教學大樓每一樓層皆設有第一種室內消防栓 3 具，則其水源容量應為多少立方公尺？",9,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-011","加壓式乾粉滅火設備，於啟動裝置動作後，為使儲存容器壓力達設定壓力始開啟放出閥，應設置何種裝置？",11,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-008","水滅火系統中，以立管連接屋頂水箱使配管平時充滿水，屋頂水箱之容量要求，下列何者錯誤？",8,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-012","設置乾粉滅火設備時，全區及局部放射之緊急電源應為自用發電設備或蓄電池設備，其容量應能使設備有效動作多久以上？",12,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-007","自動撒水設備應裝置適當之流水檢知裝置，有關流水檢知裝置之設置規定，下列何者正確？",7,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-013","有關二氧化碳滅火設備配管之設置規定，下列何者正確？",13,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-010",111,"樓地板面積 250 平方公尺之變壓器室，依各類場所消防安全設備設置標準規定，可選擇下列何種消防安全設備？①水霧 ②泡沫 ③二氧化碳 ④乾粉",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-010",110,"實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-010",109,"全區放射方式之二氧化碳滅火設備，應設置從啟動裝置動作至二氧化碳放出時間至少多久的遲延裝置？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-010",108,"有一電信機械室，設置二氧化碳滅火設備，採全區放射方式，其所核算之滅火藥劑量應於多少秒內全部放射完畢？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-010",106,"一汽車修理廠欲採用移動式乾粉滅火設備，則其外牆開口面積（常時開放部分）須符合下列那一規定？",1785123167858]