[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-011","fire-107-1-water-chemical-011",107,1,11,"加壓式乾粉滅火設備，於啟動裝置動作後，為使儲存容器壓力達設定壓力始開啟放出閥，應設置何種裝置？",{"A":16,"B":17,"C":18,"D":19},"壓力調整裝置","選擇閥","排出裝置","定壓動作裝置","D",null,[],false,"本題考點：加壓式乾粉滅火設備中，定壓動作裝置與壓力調整裝置的功能分工。\n【正解理由】依《各類場所消防安全設備設置標準》第 108 條，加壓式乾粉滅火設備應設置定壓動作裝置，條文明定「啟動裝置動作後，儲存容器壓力達設定壓力時，應使放出閥開啟」，且定壓動作裝置設於各儲存容器。題述機能與該條文字完全對應——先讓加壓用氣體把乾粉攪拌揚起並升壓，待壓力足以把粉末推送到噴頭才開閥，故選 D。\n【逐項排除】\n(A) 壓力調整裝置依第 107 條，係將加壓用氣體壓力調整至每平方公分二十五公斤以下，屬於降壓機能，不負責判斷何時開啟放出閥。\n(B) 選擇閥用於同一組儲存容器防護二個以上區域時，把藥劑導向發生火災的該區域，與容器壓力是否達設定值無關。\n(C) 排出裝置依第 102 條第六款，係為排除儲存容器之殘留氣體而設（清洗裝置則處理配管殘留藥劑），屬放射後的善後機能。\n(D) 定壓動作裝置正確，即依設定壓力控制放出閥開啟者。\n【記憶點】加壓式乾粉「先調壓、再定壓、後放出」：第 107 條調壓、第 108 條定壓開閥。","加壓式與蓄壓式是乾粉滅火設備最常考的對照組。加壓式平時儲存容器內無壓，火災時由加壓用氣體容器供氣，經第 107 條的壓力調整裝置把壓力調至每平方公分二十五公斤以下或 2.5 MPa 以下後送入儲存容器，攪拌揚起乾粉並升壓，待達設定壓力時由第 108 條的定壓動作裝置使放出閥開啟；蓄壓式則平時即以氣體與乾粉共同蓄壓於容器內，因此依第 109 條應設置以綠色表示使用壓力範圍之指示壓力表，讓外觀檢查一眼判讀壓力是否落在正常帶，並依第 102 條第五款，內壓在每平方公分十公斤以上或 1 MPa 以上者，設符合 CNS 一○八四八及一○八四九規定之容器閥。看到指示壓力表就是蓄壓式、看到定壓動作裝置就是加壓式，這是判別兩者最快的特徵。\n定壓動作裝置的存在理由在於乾粉是固體粉末，必須先被氣體充分流體化才能穩定輸送；壓力不足就開閥，粉末會在配管內堆積成塊而阻塞管路。同一理由也支撐第 106 條：自儲存容器起，配管任一部分與彎曲部分之距離應為管徑二十倍以上，但能採取乾粉藥劑與加壓或蓄壓用氣體不會分離之措施者不在此限——彎頭離容器太近，氣粉會在離心作用下分層。\n數值面記第 102 條第一款的充填比：第一種乾粉零點八五以上一點四五以下，第二種或第三種乾粉一點零五以上一點七五以下，第四種乾粉一點五以上二點五以下；充填比為容器內容積（公升）與滅火藥劑重量（公斤）之比值，數值越大代表粉裝得越蓬鬆。同條並要求儲存容器置於防護區域外、溫度攝氏四十度以下且溫度變化較少處、不得日光曝曬或雨水淋濕，並於明顯處所標示充填藥劑量、藥劑種類、最高使用壓力（限加壓式）、製造年限及製造廠商。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-010","第一種室內消防栓採用消防幫浦做為加壓送水裝置時，假設水帶摩擦損失水頭為 3 m，配管磨擦損失水頭為 7 m，落差為 30 m，則依規定，幫浦的全揚程應為多少公尺？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-012","設置乾粉滅火設備時，全區及局部放射之緊急電源應為自用發電設備或蓄電池設備，其容量應能使設備有效動作多久以上？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-009","某一學校教學大樓每一樓層皆設有第一種室內消防栓 3 具，則其水源容量應為多少立方公尺？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-013","有關二氧化碳滅火設備配管之設置規定，下列何者正確？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-008","水滅火系統中，以立管連接屋頂水箱使配管平時充滿水，屋頂水箱之容量要求，下列何者錯誤？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-014","二氧化碳滅火系統採全區放射方式高壓式系統，共設有 24 瓶儲存容器，進行綜合檢查時，放射試驗所需之藥劑量，應為下列何者？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-011",111,"依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-011",110,"室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-011",109,"乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-011",108,"二氧化碳滅火設備使用氣體啟動者，啟動用氣體容器之內容積應有 1 公升以上，其所儲存之二氧化碳重量在 0.6 公斤以上，且其充填比應在多少以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-011",106,"鹵化烴滅火設備進行性能檢查時，控制裝置之遲延裝置檢查項目，於操作啟動按鈕後至容器閥開放裝置動作，其所需時間應為：",1785123167865]