[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-015","fire-107-1-water-chemical-015",107,1,15,"二氧化碳滅火系統進行性能檢查時，音響警報之判定方法為距警報裝置 X 公尺處之音量應在 Y 分貝以上，其中 X、Y 應為下列何者？",{"A":16,"B":17,"C":18,"D":19},"X＝1；Y＝60","X＝1；Y＝90","X＝0.5；Y＝60","X＝0.5；Y＝90","B",null,[],false,"本題考點：二氧化碳滅火設備性能檢查中，音響警報裝置的判定距離與音量門檻。\n【正解理由】依《消防安全設備檢修及申報作業基準》二氧化碳滅火設備性能檢查之音響警報裝置判定方法，於距警報裝置一公尺處測定，音量應在九十分貝以上，故 X＝1、Y＝90，故選 B。設置面的依據則是《各類場所消防安全設備設置標準》第 92 條：手動或自動裝置動作後應自動發出警報，且藥劑未全部放射前不得中斷，音響警報並應有效報知防護區域或防護對象內所有人員；九十分貝的門檻，正是把「有效報知」量化成可實測值。\n【逐項排除】\n(A) 測定距離一公尺無誤，但六十分貝未達判定值，在機房背景噪音下不足以確保人員聽見。\n(B) 一公尺、九十分貝，與基準判定方法一致。\n(C) 測定距離誤為零點五公尺，音量六十分貝亦未達門檻，兩項皆錯。\n(D) 九十分貝正確，但測定距離誤為零點五公尺；距離縮短會使量得音壓偏高，判定基準將失去一致性。\n【記憶點】氣體系統音響警報「一公尺、九十分貝」；瓦斯漏氣檢知區域警報裝置則是一公尺、七十分貝。","音響警報是氣體滅火系統唯一直接對人的介面，設置面與檢修面都訂得嚴。設置面依第 92 條有三項要求：手動或自動裝置動作後應自動發出警報，且藥劑未全部放射前不得中斷；音響警報應有效報知防護區域或防護對象內所有人員；設於全區放射方式之音響警報裝置採用人語發音，但平時無人駐守者不在此限。乾粉滅火設備依第 98 條準用第 92 條，故兩者的音響警報要求完全一致，命題常拿乾粉來包裝同一個考點。檢修面則把抽象的「有效報知」變成可測值：距警報裝置一公尺處音量在九十分貝以上。\n分貝為對數尺度，音壓級相差二十分貝代表音壓相差十倍，因此九十分貝與七十分貝並非「差一點」而是量級之別。訂在九十分貝，是因為氣體滅火設備多設於發電機室、電信機械室等本身噪音就大的空間，警報必須壓過背景噪音，人員才能在遲延時間內離開防護區域。\n橫向比較是整理本考點最好用的方法：瓦斯漏氣火警自動警報設備依第 143 條，檢知器所能檢知瓦斯漏氣之區域內，該檢知器動作時，區域內之檢知區域警報裝置能發出警報音響，其音壓在距一公尺處應有七十分貝以上；但檢知器本身具有發出警報功能者，或設於機械室等常時無人場所及瓦斯導管貫穿牆壁處者，不在此限。同條並要求瓦斯漏氣表示燈設於面向通路部分之出入口附近、距樓地板面高度在四點五公尺以下、亮度在表示燈前方三公尺處能明確識別，並於附近標明瓦斯漏氣表示燈字樣。測定距離一律一公尺，變動的是分貝值——九十對七十，先鎖定距離再記數值，就不會被 X、Y 對調的選項騙過。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-014","二氧化碳滅火系統採全區放射方式高壓式系統，共設有 24 瓶儲存容器，進行綜合檢查時，放射試驗所需之藥劑量，應為下列何者？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-016","有關乾粉滅火系統之放射時間，下列敘述何者正確？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-013","有關二氧化碳滅火設備配管之設置規定，下列何者正確？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-017","一電氣設備室長寬高分別為 12 m、8 m 及 4 m，若採二氧化碳全區放射滅火設備防護，藥劑放射後採機械排放，則其排風機之風量應為每分鐘多少立方公尺？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-012","設置乾粉滅火設備時，全區及局部放射之緊急電源應為自用發電設備或蓄電池設備，其容量應能使設備有效動作多久以上？",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-018","有關大型滅火器之敘述，下列何者正確？",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-015",111,"採用移動式放射方式之乾粉滅火設備，藥劑種類為第四種乾粉時，每一具噴射瞄子所需藥劑放射量為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-015",110,"公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-015",109,"公共危險物品室外儲槽場所設置射水設備時，測試之放水壓力應在多少以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-015",108,"依各類場所消防安全設備檢修及申報作業基準，對蓄壓式二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過多少%以上或壓力表示值在綠色範圍外時，應予以更新？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-015",106,"某一高度危險工作場所，其建築物外面設有 4 具室外消防栓，則其水源容量至少應為多少？",1785123167908]