[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-017","fire-107-1-water-chemical-017",107,1,17,"一電氣設備室長寬高分別為 12 m、8 m 及 4 m，若採二氧化碳全區放射滅火設備防護，藥劑放射後採機械排放，則其排風機之風量應為每分鐘多少立方公尺？",{"A":16,"B":17,"C":18,"D":19},"32","64","307","384","A",null,[],false,"本題考點：全區放射方式防護區域藥劑排放，採機械排放時的風量計算（每小時五次換氣量）。\n【正解理由】依《各類場所消防安全設備設置標準》第 94 條，放射之滅火藥劑應於一小時內排至安全地方，採機械排放時，排風機為專用且「具有每小時五次之換氣量」。防護區域體積 V＝12 m×8 m×4 m＝384 m³；每小時換氣五次之風量＝384 m³×5＝1,920 m³\u002Fh；換算為每分鐘＝1,920 m³\u002Fh ÷ 60 min\u002Fh＝32 m³\u002Fmin，故選 A。二氧化碳比空氣重且易滯留低處，排放不完全會使人員進入時缺氧，故同條並要求排放至室外之滅火藥劑不得有局部滯留之現象。\n【逐項排除】\n(A) 32 m³\u002Fmin 正確，即 384×5÷60。\n(B) 64 係以每小時十次換氣計算（384×10÷60），換氣次數規定為五次而非十次。\n(C) 307 約為 384×0.8 之值，與每小時五次換氣的規定無關，無法由條文核算得出。\n(D) 384 是防護區域體積本身，把體積直接當成每分鐘風量，漏掉換氣次數與時間單位換算。\n【記憶點】機械排放風量（m³\u002Fmin）＝防護區域體積×5÷60：先算體積、乘五次、除六十。","藥劑排放規定的核心是「人能不能安全進去」。二氧化碳的蒸氣密度約為空氣的一點五倍，放射後會沉積於地面與電纜溝、坑溝等低處，濃度足以致命卻無色無味，因此第 94 條要求全區放射或局部放射方式防護區域內的藥劑須於一小時內排至安全地方，排放裝置之操作開關並須設於防護區域外便於操作處，且在其附近設有標示——開關設在區域外，正是為了避免人員為了排放而先進入高濃度空間。\n兩種排放方式擇一：採機械排放時，排風機為專用且具有每小時五次之換氣量，但與其他設備之排氣裝置共用而無排放障礙者得共用之；採自然排放時，設有能開啟之開口部，其面向外氣部分（限防護區域自樓地板面起高度三分之二以下部分）之大小，占防護區域樓地板面積百分之十以上，且容易擴散滅火藥劑。條文特意限定「自樓地板面起高度三分之二以下部分」，與二氧化碳沉降的物理特性一致——開口若只開在天花板附近，重氣體根本排不掉。\n計算上把公式定型即可：每分鐘風量（m³\u002Fmin）＝防護區域體積（m³）×每小時換氣次數五次÷60 分鐘。本題 384×5÷60＝32；若題目改問每小時風量則為 1,920 m³\u002Fh，兩者只差一個 60，作答前務必看清所問單位，這是本題型最常見的失分點。\n相關考點是第 85 條：全區或局部放射方式防護區域內之通風換氣裝置，應在滅火藥劑放射前停止運轉。停通風與啟動排放恰成一組時序——放射前停止通風以免藥劑濃度被稀釋而滅不了火，放射後才啟動排放以免人員中毒，把「先停後排」四個字記牢，兩條就不會互相干擾。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-016","有關乾粉滅火系統之放射時間，下列敘述何者正確？",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-018","有關大型滅火器之敘述，下列何者正確？",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-015","二氧化碳滅火系統進行性能檢查時，音響警報之判定方法為距警報裝置 X 公尺處之音量應在 Y 分貝以上，其中 X、Y 應為下列何者？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-019","可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽之滅火器，每具滅火器對普通火災應具有 X 個以上之滅火效能值，對油類火災應具有 Y 個以上之滅火效能值，其中 X、Y 分別為下列何者？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-014","二氧化碳滅火系統採全區放射方式高壓式系統，共設有 24 瓶儲存容器，進行綜合檢查時，放射試驗所需之藥劑量，應為下列何者？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-020","室內消防栓之水源採重力水箱設置，下列何種裝置不屬於該構造應有之裝置？",20,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-017",111,"惰性氣體滅火設備進行綜合檢查時，採低壓式者進行放射試驗時，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之多少以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-017",110,"密閉乾式或預動式之流水檢知裝置二次側配管，為有效排水，支管每 10 公尺傾斜 A 公分，主管每 10 公尺傾斜 B 公分。下列 A，B 何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-017",109,"某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-017",108,"依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備之第一種消防栓水帶及瞄子檢查方法，製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。則 X+Y 為若干？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-017",106,"有關撒水頭之設置，下列敘述何者錯誤？",1785123167928]