[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-022":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-022","fire-107-1-water-chemical-022",107,1,22,"可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽設置滅火器，其設置規定，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"儲槽設置 2 具以上","加氣站用火設備處所設置 2 具以上","每具滅火器對普通火災具有 3 個以上之滅火效能值","每具滅火器對油類火災具有 10 個以上之滅火效能值","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 228 條把高壓氣體類場所的滅火器分成兩層來規定——各種場所各須設置幾具,以及每一具應具備的滅火效能值下限;四個選項即在這兩層數值之間交叉設誘答。\n【正解理由】依《各類場所消防安全設備設置標準》第 228 條第六款,「每具滅火器對普通火災具有四個以上之滅火效能值,對油類火災具有十個以上之滅火效能值」,選項 D 所稱油類火災十個以上與條文相符,故選 D。\n【逐項排除】\n(A) 同條第二款為「儲槽設置三具以上」,本選項寫 2 具,具數不足;設二具的是製造、儲存或處理場所,樓地板面積二百平方公尺以上者另須每五十平方公尺增設一具。\n(B) 同條第三款第三目為加氣站「用火設備處所一具以上」,不是 2 具;需四具以上的是儲氣槽區,兩者被對調。\n(C) 同條第六款普通火災為四個以上滅火效能值,3 個低於下限,且此為每一具滅火器均須達到的能力,不得以多具合計。\n(D) 與第 228 條第六款「對油類火災具有十個以上之滅火效能值」逐字相符,為正解。\n【記憶點】具數記「槽三具、槽區四具、加氣機一具、用火處所一具」,效能值記「普四油十」,兩組分開背就不會互相干擾。","第 228 條是把「具數」與「能力」兩件事寫在同一條的典型條文,考題常把兩者的數字互換來設誘答,拆解成兩層來記最有效。第一層是具數:製造、儲存或處理場所設置二具,樓地板面積二百平方公尺以上者,每五十平方公尺(含未滿)增設一具;儲槽設置三具以上;加氣站再細分四種情形——儲氣槽區四具以上、加氣機每臺一具以上、用火設備處所一具以上、建築物每層樓地板面積在一百平方公尺以下設置二具,超過一百平方公尺時每增加(含未滿)一百平方公尺增設一具。第二層是能力與配置:每具滅火器對普通火災具有四個以上、對油類火災具有十個以上之滅火效能值;儲存場所任一點至滅火器之步行距離在十五公尺以下,並不得妨礙出入作業;設於屋外者,滅火器置於箱內或有不受雨水侵襲之措施。\n立法上,這一編是針對高風險場所所設的加重規定。可燃性高壓氣體洩漏後與空氣混合,火勢發展速度遠快於一般場所,滅火器必須「隨手可及」且「單具能力夠強」,所以步行距離訂得比一般場所嚴格,滅火效能值也拉高,並要求屋外設置者防雨,避免藥劑受潮結塊而失效。\n相關考點連結:第 207 條規定這些場所「應設置滅火器」,是本條的授權前提;第 229 條規定冷卻撒水設備之撒水量為防護面積每平方公尺每分鐘五公升以上,若以厚度二十五毫米以上之岩棉或同等以上防火性能之隔熱材被覆並符合條文所定外側被覆條件者,撒水量得減半,水源容量在連續撒水三十分鐘之水量以上;第 231 條規定射水設備的室外消防栓箱內配置瞄子、開關把手及口徑六十三毫米、長度二十公尺消防水帶二條,同時使用時放水壓力在每平方公分三點五公斤以上、放水量在每分鐘四百五十公升以上。滅火器負責初期、冷卻撒水負責降溫防止儲槽破裂、射水設備負責遠距離防護,三者的分工是本編的整體架構。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-021","有關乾粉滅火設備配管設置規定，下列敘述何者正確？",21,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-023","有關室內消防栓綜合檢查放水量及放水壓力之敘述，下列何者正確？",23,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-020","室內消防栓之水源採重力水箱設置，下列何種裝置不屬於該構造應有之裝置？",20,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-024","竣工查驗時，於屋頂使用口徑 16 mm 瞄子實施第一種室內消防栓綜合檢查，測得放水壓力為 4 kgf\u002Fcm2，所計算之每分鐘放水量約為：",24,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-019","可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽之滅火器，每具滅火器對普通火災應具有 X 個以上之滅火效能值，對油類火災應具有 Y 個以上之滅火效能值，其中 X、Y 分別為下列何者？",19,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-025","泡沫滅火設備進行綜合檢查時，有關泡沫滅火藥劑 25%還原時間標準值敘述，下列何者正確？",25,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-022",111,"有關水道連結型自動撒水設備進行綜合檢查時，其放水壓力應為多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-022",110,"同一建築基地內有二棟以上建築物時，建築物間外牆與中心線水平距離第一層在 X 公尺以下，第二層在 Y 公尺以下，且合計各棟該第一層及第二層樓地板面積在 Z 平方公尺以上者，應設置消防專用蓄水池。X、Y、Z 分別為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-022",109,"室內消防栓之箱面字樣，每字不得小於多少平方公分？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-022",108,"有關潔淨藥劑氣體滅火設備滅火藥劑主要成分之敘述，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-022",106,"下列那一泡沫滅火設備之泡沫濃度，不符泡沫原液與水混合使用濃度之規定？",1785123167975]