[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-029","fire-107-1-water-chemical-029",107,1,29,"全區放射二氧化碳滅火設備進行綜合檢查時，如為高壓式儲存系統，在放射試驗時需放射多少藥劑量？",{"A":16,"B":17,"C":18,"D":19},"為該放射區域所設儲存容器瓶數之 5%以上","為該放射區域所設儲存容器瓶數之 10%以上","為該放射區域所設儲存容器瓶數之 15%以上","為該放射區域所設儲存容器瓶數之 20%以上","B",null,[],false,"本題考點：全區放射方式二氧化碳滅火設備綜合檢查時，高壓式儲存系統於放射試驗所需之藥劑量比例。\n【正解理由】依《消防安全設備檢修及申報作業基準》二氧化碳滅火設備綜合檢查之規定，全區放射方式採高壓式者，放射試驗所需之藥劑量為該放射區域所設儲存容器瓶數之百分之十以上（核算結果未滿一瓶者進位為一瓶）；採低壓式者，則以該放射區域應設滅火藥劑量之百分之十以上實施放射。兩者比例同為一成，差別僅在高壓式以「瓶數」為計算基礎、低壓式以「藥劑量」為計算基礎，故選 B。\n【逐項排除】\n(A) 百分之五低於基準所定比例，放射量不足以確認容器閥開放裝置、選擇閥與配管能否確實動作，基準未採此值。\n(B) 百分之十正是高壓式以儲存容器瓶數核算之放射量，與基準相符，為正解。\n(C) 百分之十五並非基準所列數值；綜合檢查採一成即足以驗證系統連動，再提高只是徒增藥劑再充填成本。\n(D) 百分之二十同樣不是基準數值，且放射量愈大，防護區域內二氧化碳濃度愈高，對在場檢查人員愈不利。\n【記憶點】高壓算瓶數、低壓算藥劑量，比例都是一成。","《消防安全設備檢修及申報作業基準》把消防安全設備的檢查分為外觀檢查、性能檢查與綜合檢查三個層次：外觀檢查以目視確認設置狀態與標示，性能檢查逐項確認個別零組件的機能，綜合檢查則是實際使系統動作、驗證各機件能否連動的最後一關。二氧化碳滅火設備的綜合檢查採「抽樣放射」而非全量放射，正是因為藥劑昂貴、再充填耗時，且高濃度二氧化碳對人體有窒息危險，故以一成的放射量驗證啟動裝置、遲延裝置、音響警報裝置、放射表示燈、開口部自動關閉裝置與通風換氣裝置停止運轉等連動機能是否正常。\n高壓式與低壓式的差別在儲存型態：高壓式於常溫下以液化狀態高壓充填於多支鋼瓶，藥劑量本來就以瓶數呈現，放射量自然以「瓶數的一成」核算；低壓式則以冷凍機把容器內部維持在極低溫，藥劑集中儲存於單一大型容器，根本無瓶數可數，只能改以「應設滅火藥劑量的一成」計算。這組對照是命題者最愛設計的切換點，把高壓式寫成「藥劑量的百分之十」也是常見的錯誤選項。\n判定要領上，除藥劑確實放射外，尚須確認警報裝置動作、遲延時間足以使人員避難、放射表示燈亮起；為避免試驗過程誤放射，啟動用氣體容器與容器閥開放裝置須先行分離處理。延伸考點還包括局部放射方式的放射試驗同樣以一成核算，以及綜合檢查後容器應回復至原充填狀態。\n命題常見的改寫方式有三種：把一成改成半成或一成五、把高壓式的計算基礎由瓶數換成藥劑量、把「以上」改成「以下」。三者都可以用同一句話擋掉——高壓式放射該區域所設儲存容器瓶數的一成以上，低壓式放射該區域應設滅火藥劑量的一成以上，其餘寫法一律是錯的。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-028","有關滅火器性能檢查頻率之規定，下列敘述何者正確？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-030","實施二氧化碳滅火設備檢修，於進行性能檢查時，皮管連接部應無鬆動，皮管損傷、老化等情形，且皮管長度應在幾公尺以上？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-027","有關二氧化碳滅火設備放射時間之敘述，下列何者正確？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-031","惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-026","室內消防栓設備之消防立管管系竣工時，應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程 A 倍以上之水壓。試驗壓力以繼續維持 B 小時無漏水現象為合格，A、B 分別為：",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-032","泡沫滅火設備之場所，於進行性能檢查時，製造年份超過幾年或無法辨識製造年份之水帶，應進行水壓試驗？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-029",111,"變電站場所設置水霧滅火設備，放射區域 6 個分區，其消防幫浦出水量需達每分鐘 X 公升以上；且每顆水霧噴頭放水壓力均能達每平方公分 Y 公斤以上，請問前述 X、Y 為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-029",110,"公共危險物品等場所消防設計及消防安全設備，設置第五種滅火設備者，公共危險物品每達管制量之幾倍（含未滿）應有一滅火效能值？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-029",109,"泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-029",108,"有一室內停車空間，其防護區為 25 m × 16 m × 4 m，未設自動關閉裝置之開口部面積為 10 m2，擬設置全區放射式乾粉滅火設備，試問所需法定滅火藥劑量最少為多少公斤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-029",106,"10 型乾粉滅火器乾粉充填量約為多少公斤重？",1785123168049]