[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-031","fire-107-1-water-chemical-031",107,1,31,"惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",{"A":16,"B":17,"C":18,"D":19},"5%","10%","15%","20%","B",null,[],false,"本題考點：惰性氣體滅火設備性能檢查時，滅火藥劑量測定結果與原始資料核對所容許的差值上限。\n【正解理由】依《消防安全設備檢修及申報作業基準》關於惰性氣體滅火設備滅火藥劑量之性能檢查，係將實際測定所得之藥劑量，與重量表、圖面明細表或原廠技術手冊規範等資料逐一核對，其差值在充填值百分之十以下者為合格；一旦超過此差值，即代表容器有洩漏、充填不足或測定條件有誤，該容器須予再充填或更換，故選 B。\n【逐項排除】\n(A) 百分之五嚴於基準所定容許值；惰性氣體以氣態高壓充填，讀值受溫度影響大，測定本身即帶有誤差，訂到百分之五並不合理。\n(B) 百分之十與基準所定容許差值相符，為正解。\n(C) 百分之十五已超出基準容許範圍，此時實際藥劑量不足以在防護區域內建立設計濃度，屬不合格而非合格。\n(D) 百分之二十差距更大，代表容器已嚴重洩漏，更不可能被列為合格的判定值。\n【記憶點】藥劑量與帳面資料對帳，差值落在一成以內才算合格。","惰性氣體滅火藥劑是氮氣（IG-100）、氬氣（IG-01）及其與二氧化碳的混合氣體（IG-55、IG-541），共同特徵是在常溫下不會液化，只能以極高的壓力充填成壓縮氣體儲存。這個物理性質直接決定了藥劑量的測定方式：二氧化碳、鹵化烴等可液化藥劑能用液面計或磅秤量出液相重量，惰性氣體卻沒有液面可讀，只能量測容器壓力，再依當時溫度換算回充填量，因此測定結果天生帶有誤差。容許差值訂在充填值一成，正是把溫度修正與量測誤差一併涵蓋進去的結果。\n為什麼短少一成仍可判為合格？惰性氣體的滅火機制是稀釋，把防護區域的氧濃度自約百分之二十一降到約百分之十二至十五，使燃燒無法持續；而設計濃度本身即已內含安全係數，藥劑短少一成時，實際濃度仍在滅火濃度之上。但差值一旦超過一成，就代表容器閥或接頭存在持續洩漏，屬於必須再充填或更換的狀態。\n易混淆之處在於核對對象：基準列的是「重量表、圖面明細表或原廠技術手冊規範等資料」，只記住重量表會漏掉另外兩者，這正是選項常見的改寫點。此外，藥劑「量」的判定與容器「壓力」的判定是兩個不同項目，各有其判定範圍，不可混為一談。延伸考點常把百分之十改寫成百分之五或百分之十五，或把合格條件由「以下」改成「以上」，都是純粹的閱讀陷阱。\n再往上一層看，滅火藥劑量之所以被歸入性能檢查而非外觀檢查，是因為它無法以目視確認：外觀檢查只能看容器有無變形、固定是否牢固、標示是否完整，實際存量必須拆表量測後與帳面資料核對。這種「量測後對帳」的檢查型態，正是性能檢查的定義，也是檢修三階段分類題的判斷關鍵。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-030","實施二氧化碳滅火設備檢修，於進行性能檢查時，皮管連接部應無鬆動，皮管損傷、老化等情形，且皮管長度應在幾公尺以上？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-032","泡沫滅火設備之場所，於進行性能檢查時，製造年份超過幾年或無法辨識製造年份之水帶，應進行水壓試驗？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-029","全區放射二氧化碳滅火設備進行綜合檢查時，如為高壓式儲存系統，在放射試驗時需放射多少藥劑量？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-033","自動撒水設備竣工時進行加壓試驗，下列何者錯誤？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-028","有關滅火器性能檢查頻率之規定，下列敘述何者正確？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-034","依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列敘述何者正確？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-031",111,"應設置消防專用蓄水池之場所規定，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-031",110,"公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-031",109,"使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-031",108,"第四種乾粉滅火藥劑儲存容器，有關充填比之規定，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-031",106,"B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",1785123168075]