[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-032","fire-107-1-water-chemical-032",107,1,32,"泡沫滅火設備之場所，於進行性能檢查時，製造年份超過幾年或無法辨識製造年份之水帶，應進行水壓試驗？",{"A":16,"B":17,"C":18,"D":19},"3 年","5 年","10 年","15 年","C",null,[],false,"本題考點：泡沫滅火設備性能檢查中，水帶以「製造年份」作為是否強制實施水壓試驗的判定門檻。\n【正解理由】依《消防安全設備檢修及申報作業基準》泡沫滅火設備性能檢查之水帶項目，製造年份超過十年，或已無法辨識製造年份之水帶，應實施水壓試驗，其後並定期複驗。理由在於水帶的內襯橡膠與外層織布會隨時間老化，耐壓能力衰退從外觀完全看不出來，故以使用年限作為強制加驗的客觀門檻；年份不明者則從嚴比照已超過年限處理，故選 C。\n【逐項排除】\n(A) 三年是水帶經水壓試驗合格後再次實施試驗的週期，與「起驗年限」是兩個不同概念，最常被對調。\n(B) 五年並非基準所定之年限門檻，水帶在此期間內仍屬正常使用階段，尚不須強制加驗。\n(C) 十年與基準所定門檻相符，且含無法辨識製造年份者，為正解。\n(D) 十五年已遠超基準門檻；若拖到此時才首次加驗，水帶可能早已在放水時破裂而失去滅火能力。\n【記憶點】十年起驗、其後三年一次；年份看不清就當作已經超過十年。","水帶是泡沫滅火設備中少數會隨時間單向劣化的組件。金屬管件的腐蝕可以靠目視發現，水帶的內襯橡膠硬化、織布纖維疲勞卻看不見，唯一可靠的驗證方式是實際加壓：把水帶充水加壓至規定試驗壓力並維持一定時間，確認無滲漏、無異常膨出與接頭鬆脫。基準因此不採「看起來還好就好」的標準，而以製造年份劃出一條客觀的線，並把年份不明者一併納入。\n移動式泡沫滅火設備正是水帶的主戰場。依《各類場所消防安全設備設置標準》第六十九條，移動式放射方式之水帶接頭至防護對象任一點之水平距離在十五公尺以下；第八十條進一步規定，同一樓層各泡沫瞄子放射量應在每分鐘一百公升以上，泡沫瞄子放射壓力應在每平方公分三點五公斤以上或 0.35MPa 以上，泡沫原液應使用低發泡，並於水帶接頭三公尺範圍內設置泡沫消防栓箱，箱內配置長二十公尺以上之水帶及泡沫瞄子乙具，箱面表面積在零點八平方公尺以上，箱上方設紅色幫浦啟動表示燈。水帶一旦耐壓不足，上述放射壓力與放射量的規定全部落空，這就是把水帶年限寫進性能檢查的用意。\n數值可以這樣串起來記：水帶「十年起驗、三年複驗」，移動式泡沫「水平十五、水帶二十、放射量一百、壓力零點三五」。延伸考點常把水壓試驗的門檻與週期對調，或把「無法辨識製造年份」的處理方式改成免驗，均與基準不符。\n另需分清層次：水壓試驗的對象是水帶本體與接頭的耐壓能力，屬性能檢查；水帶有無明顯破損、發霉、扭結或收納不良，在外觀檢查階段即可發現。兩個階段的判定內容不同，卻常在題目中被混寫成同一項，是分類型考題最常見的切入點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-031","惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-033","自動撒水設備竣工時進行加壓試驗，下列何者錯誤？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-030","實施二氧化碳滅火設備檢修，於進行性能檢查時，皮管連接部應無鬆動，皮管損傷、老化等情形，且皮管長度應在幾公尺以上？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-034","依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列敘述何者正確？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-029","全區放射二氧化碳滅火設備進行綜合檢查時，如為高壓式儲存系統，在放射試驗時需放射多少藥劑量？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-035","採用移動式放射方式之乾粉滅火設備，藥劑種類為第一種乾粉時，每一具噴射瞄子所需藥劑放射量為：",35,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-032",111,"二氧化碳滅火設備屬於公共危險物品等場所的那一類滅火設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-032",110,"公共危險物品等場所消防設計及消防安全設備，有關設置冷卻撒水設備規定，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-032",109,"二氧化碳滅火設備採用移動放射方式時，每一具噴射瞄子所需滅火藥劑量在多少公斤以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-032",108,"依法令規定下列場所何者應設置滅火器？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-032",106,"二氧化碳全區放射方式之安全裝置，啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有多少秒以上之遲延裝置？",1785123168082]